6
|
Application guidelines
Installer reference guide
36
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01
Underfloor heating or radiators – Wireless room thermostat
Setup
B
b
a
A
A
Main leaving water temperature zone
B
One single room
a
Receiver for wireless external room thermostat
b
Wireless external room thermostat
▪
For more information about connecting the electrical wiring to the unit, see:
-
"9.2 Connections to the outdoor unit"
-
"9.3 Connections to the indoor unit"
▪
The underfloor heating or radiators are directly connected to the indoor unit.
▪
The room temperature is controlled by the wireless external room thermostat
(optional equipment EKRTR1).
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
1 (
External room thermostat
):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
0 (
Single zone
): Main
External room thermostat for the
main
zone:
▪
#: [2.A]
▪
Code: [C-05]
1 (
1 contact
): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Benefits
▪
Wireless.
The Daikin external room thermostat is available in a wireless version.
▪
Efficiency.
Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heat pump system.
▪
Comfort.
In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.