background image

 

ERQ100~14 ERQ125~250A7W1B
Inverter condensing unit
4PW51322-1B – 2018.04

Operation manual

3

4.

R

EMOTE

 

CONTROLLER

Refer to the operation manual of the remote controller.

5.

C

HANGEOVER

 

SWITCH

: N

AME

 

AND

 

FUNCTION

 

OF

 

EACH

 

SWITCH

 

(See figure 3)

1

FAN ONLY/AIR CONDITIONING SELECTOR SWITCH
Set the switch to 

 for fan only operation or to 

 for heating or

cooling operation.

2

COOL/HEAT CHANGEOVER SWITCH
Set the switch to 

 for cooling or to 

 for heating operation.

6.

O

PERATION

 

RANGE

Operation range

Use the system in the following temperature and humidity ranges for
safe and effective operation.

7.

O

PERATION

 

PROCEDURE

Operation procedure varies according to the combination of
outdoor unit and remote controller. Read 

"3. What to do before

operation" on page 2

.

To protect the unit, turn on the main power switch 6 hours before
operation.

If the main power supply is turned off during operation, operation
will restart automatically after the power turns back on again.

Refer to the manual supplied with the control box for operation
and functionality.

Refer to the manual supplied with the remote controller for
operation and functionality.

7.1.

Cooling, heating, and fan only operation 

(See

figure 4

 and 

figure 6

)

The fan may keep on running for a while after the heating operation
stops.

For systems with Daikin remote controller and without cool/
heat changeover remote control switch 

(See figure 4)

1

Press the operation mode selector button several times and
select the operation mode of your choice.

2

Press the on/off button.
The operation lamp lights up and the system starts operation.

For systems with cool/heat changeover remote control switch

1

Select operation mode with the cool/heat changeover remote
control switch as follows:

2

Press the on/off button or close T1/T2.
The operation lamp lights up and the system starts operation.

For systems without Daikin remote controller, without cool/
heat changeover remote control switch and with a field 
supplied controller

1

Select operation mode with the field supplied controller.

2

Close T1/T2.
The operation lamp lights up and the system starts operation.

Adjustment

For programming temperature refer to the operation manual of the
remote controller.

Stopping the system

3

Press the on/off button once again or open T1/T2.
The operation lamp goes off and the system stops operation.

Explanation of heating operation

It may take longer to reach the set temperature for general heating
operation than for cooling operation.

The following operation is performed in order to prevent the heating
capacity from dropping or cold air from blowing.

Defrost operation

In heating operation, freezing of the outdoor unit coil increases.
Heating capability decreases and the system goes into defrost
operation.

The air handling unit fan stops and the remote controller
displays .

In case no remote controller is installed, a defrost signal is
outputted from the control box.

After maximum 10 minutes of defrost operation, the system
returns to heating operation again.

Hot start

In order to prevent cold air from blowing out of an air handling unit at
the start of heating operation, the air handling unit fan can be
stopped, depending on the control of the air handling unit.

In case a remote controller is installed, the remote controller displays

. It may take some time before the fan starts. This is not a

malfunction.

ERQ125~250_W1

ERQ100~140_V1

Outdoor 
temperature

–5~43°C DB

–20~21°C DB

–5~46°C DB –20~24°C DB

(*)

(*) Range for operation: –20~–15°C WB. Range for continuous operation: 

–15~15.5°C WB.

–20~15.5°C WB

–20~15.5°C WB

Indoor 
temperature

21~32°C DB

15~27°C DB

21~32°C DB

15~27°C DB

14~25°C WB

14~25°C WB

Indoor 
humidity

80%

(†)

(†) to avoid condensation and water dripping out the unit.

If the temperature or the humidity is beyond these conditions, safety devices may 
work and the air conditioner may not operate.

80%

(†)

Cooling operation

Heating operation

Fan only operation

 

Cooling operation (

figure 6

)

 

Heating operation (

figure 7

)

Fan only operation (

figure 8

)

NOTE

Do not turn off power immediately after the unit stops,
but wait for at least 5 minutes.

4PWEN51322-1B_2018_04.book  Page 3  Thursday, June 7, 2018  9:42 PM

Summary of Contents for ERQ100A7V1B

Page 1: ...OPERATION MANUAL ERQ100A7V1B ERQ125A7V1B ERQ140A7V1B ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B Inverter condensing unit ...

Page 2: ...6 2 3 1 1 7 2 3 1 1 8 2 3 1 4 1 2 5 UNIT NO 1 2 3 4 3 1 2 1 2 1 5 6 3 10 14 11 7 9 8 13 2 1 5 6 3 12 4 7 9 8 2 NOTES 1 2 3 4 5 6 7 8 ...

Page 3: ...k or a fire Never use a flammable spray such as hair spray lacquer or paint near the unit It may cause a fire Never replace a fuse with that of wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire Never put any objects into the air inlet or outlet Objects touching the fan at high operating speed can be dangerous Never...

Page 4: ...e panel may get discolored or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth Never touch the internal parts of the controller Do not remove the front panel Some parts inside are dangerous to touch and a machine trouble may happen For checking and adjusting the internal parts conta...

Page 5: ... with a field supplied controller 1 Select operation mode with the field supplied controller 2 Close T1 T2 The operation lamp lights up and the system starts operation Adjustment For programming temperature refer to the operation manual of the remote controller Stopping the system 3 Press the on off button once again or open T1 T2 The operation lamp goes off and the system stops operation Explanat...

Page 6: ... and fan only operation on page 3 for details on fan only operation Turn off the power The remote controller displays disappear Clean air filters and casings of air handling units Refer to the operation manual supplied with the air handling units for details on how to proceed and make sure to install cleaned air filters back in the same position 10 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROUBL...

Page 7: ...the fan is controlled in order to optimize product operation Symptom 10 The display shows Only when a remote controller is connected This is the case immediately after the main power supply switch is turned on and means that the remote controller is in normal condition This continues for one minute Symptom 11 The compressor in the outdoor unit does not stop after a short heating operation This is ...

Page 8: ...nd maintenance cycles Be aware that the mentioned maintenance and replacement cycles do not relate to the warranty period of the components Table 1 Inspection Cycle and Maintenance Cycle list Table 1 assumes the following conditions of use 1 Normal use without frequent starting and stopping of the unit Depending on the model we recommend not starting and stopping the machine more than 6 times hour...

Page 9: ...estruction regulations NOTES Component Inspection cycle Maintenance cycle replacements and or repairs Air filter 1 year 5 years High efficiency filter Optional 1 year Fuse 10 years Crankcase heater 8 years NOTE 1 Table 2 indicates main components Refer to your maintenance and inspection contract for more details 2 Table 2 indicates recommended intervals of replacement cycles However in order to ke...

Page 10: ......

Page 11: ......

Page 12: ...4PW51322 1B 2018 04 Copyright Daikin 4PW51322 1 B 0000000G ...

Reviews: