background image

 

ERQ100~140A7V1B
Inverter condensing unit
4PW51321-1

Installation manual

6

(C) In case of multiple-row installation (for roof top use, etc.)

1.

In case of installing one unit per row.

2.

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions between H, A and L is shown in the table
below.

7.

R

EFRIGERANT

 

PIPE

 

SIZE

 

AND

 

ALLOWABLE

 

PIPE

 

LENGTH

7.1.

Selection of piping material

Foreign materials inside pipes (including oils for fabrication)
must be 

30 mg/10 m.

Construction material: phosphoric acid deoxidized seamless
copper for refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R410A piping must be in accordance with the table
below.

O = Annealed
1/2H = Half hard

In case the required pipe sizes (inch sizes) are not available, it is
also allowed to use other diameters (mm sizes), taken the
following into account:

select the pipe size nearest to the required size.

use the suitable adapters for the change-over from inch to
mm pipes (field supply).

8.

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R410A only when adding refrigerant
Installation tools:

Make sure to use installation tools (gauge manifold charge
hose, etc.) that are exclusively used for R410A installations
to withstand the pressure and to prevent foreign materials
(e.g. mineral oils and moisture) from mixing into the system.

Vacuum pump:

Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the
system while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa
(5 Torr, –755 mm Hg).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.

Great caution is needed when passing copper tubes through
walls.

For handling of stop valves, refer to 

"9.3. How to use the stop

valve" on page 8

.

Only use the flare nuts included with the unit. Using different
flare nuts may cause the refrigerant to leak.

Always use the supplied copper gasket when connecting the
gas pipe supplied with the unit. See 

"9. Refrigerant piping" on

page 7.

NOTE

Do not stack more than one unit.

About 100 mm is required as the dimension
for laying the upper outdoor unit’s drain pipe.

Get the portion A sealed so that air from the
outlet does not bypass.

L

A (mm)

L

H

0<L

1/2H

250

1/2H<L

H

300

H<L

Installation impossible

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.

To persons in charge of piping work:

Be sure to open the stop valve after piping installing
and vacuuming is complete. (Running the system with
the valve closed may break the compressor.)

It is forbidden to discharge refrigerant into the
atmosphere. Collect the refrigerant in accordance
with the freon collection and destruction law.

Do not use flux when brazing the refrigerant piping.
For brazing, use phosphor copper brazing filler metal
(BCuP) which does not require a flux.
(If a chlorine flux is used, the piping will corrode, and if
the flux contains fluoride, it will cause the coolant oil to
deteriorate, adversely affecting the coolant piping
system.

Do not use materials not compatible with copper.
Example: Aluminium heat exchanger may be cause of
corrosion.

1000

200

2000

100

1500

600

3000

A

H

L

Pipe Ø

Temper grade of piping 

material

Minimal thickness t 

(mm)

6.4 / 12.7

O

0.80

15.9

O

1

19.1

1/2H

1

Installation period

Protection method

More than a month

Pinch the pipe

Less than a month

Pinch or tape the 

pipe

Regardless of the 

period

Summary of Contents for ERQ100A7V1B

Page 1: ...INSTALLATION MANUAL ERQ100A7V1B ERQ125A7V1B ERQ140A7V1B Inverter condensing unit ...

Page 2: ...H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 1000 1000 1000 1000 500 500 1000 500 1000 1000 300 300 300 250 300 300 500 200 1000 1000 1000 1000 1000 1250 1500 1500 1000 1000 100 5 4 4 3 2 1 7 8 9 10 A D C B 5 6 11 7 6 1 2 3 4 5 6 7 9 8 12 13 10 11 ...

Page 3: ... gitt i henhold til bestemmelsene i 13 noudattaen määräyksiä 14 za dodržení ustanovení předpisu 15 prema odredbama 16 követi a z 17 zgodnie z postanowieniami Dyrektyw 18 în urma prevederilor 19 ob upoštevanju določb 20 vastavalt nõuetele 21 следвайки клаузите на 22 laikantis nuostatų pateikiamų 23 ievērojot prasības kas noteiktas 24 održiavajúc ustanovenia 25 bunun koşullarına uygun olarak 01 Note...

Page 4: ... here are divided into the following two types Both cover very important topics so be sure to follow them carefully Warning Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation m...

Page 5: ...e air handling and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient to eliminate the noise Do not rinse the outdoor unit This may cause electric shocks or fire Do not install the air conditioner in places such as the following Where there is m...

Page 6: ...ect an installation site where the following conditions are satisfied and that meets with your customer s approval Places which are well ventilated Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibility of flammable gas or product leak Places where serv...

Page 7: ...he drain water dripping 10 The equipment is not intended for use in a potentially explosive atmosphere 5 PRECAUTIONS ON INSTALLATION Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation In accordance with the foundation drawing in the figure fix the unit securely by means of the foundation bolts Prepare four set...

Page 8: ...plied vinyl hose internal diameter of 25 mm to the drain socket A If the hose is too long and hangs down fix it carefully to prevent kinks 6 INSTALLATION SERVICING SPACE The connection piping outlet direction in the installation shown in figure 4 is frontward or downward The unit of numeric values is mm When routing the piping backward secure space of 250 mm on the right side of the unit A In case...

Page 9: ...ly into the system while the pump is not working Use a vacuum pump which can evacuate to 100 7 kPa 5 Torr 755 mm Hg In order to prevent dirt liquid or dust from entering the piping cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls For handling of stop valves refer to 9 3 How to use the stop valve on page 8 Only use the flare nuts included with t...

Page 10: ... install the connecting pipe to the unit in a downward direction make a knockout hole by penetrating the center area around the knockout hole using a Ø6 mm drill See figure 5 Cutting out the two slits makes it possible to install as shown in figure 5 Use a metal saw to cut out the slits After knocking out the knock out it is recommended to apply repair paint to the edge and the surrounding end sur...

Page 11: ... flare nut may cause refrigerant leak 9 3 How to use the stop valve Use hexagonal wrenches 4 mm and 6 mm Opening the valve 1 Place the hex wrench on the valve bar and turn counter clockwise 2 Stop when the valve bar no longer turns It is now open Closing the valve 1 Place the hex wrench on the valve bar and turn clockwise 2 Stop when the valve bar no longer turns It is now closed 9 4 Cautions for ...

Page 12: ...se a vacuum pump which can evacuate to 100 7 kPa 5 Torr 755 mm Hg 1 Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2 hours and bring the system to 100 7 kPa After keeping the system under that condition for more than 1 hour check if the vacuum gauge rises or not If it rises the system may either contain moisture inside or have leaks 2 Following should be exe...

Page 13: ...ated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please fill in with indelible ink the factory refrigerant charge of the product the additional refrigerant amount charged in the field and the total refrigerant charge on the fluorinated greenhouse gases label supplied with the product The...

Page 14: ...initial start up Setting the mode on page 16 set the required function A additional refrigerant charging operation to ON Then operation starts The blinking H2P led indicates test operation and the remote controller indicates test operation and external control 6 When the specified amount of refrigerant is charged push the button Then operation stops The operation automatically stops within 30 minu...

Page 15: ...ircuits must be interrupted Use only copper wires Do not turn on the main switch until all the wiring is completed Make sure that the main switch has a contact separation of at least 3 mm in all poles Never squeeze bundled cables into a unit Secure the electrical wiring with clamping material as shown in figure 9 so that it does not come in contact with the piping particularly on the high pressure...

Page 16: ...oper distance between power cable and control wiring 4 Clamp field supply 5 Stop valve mounting plate 6 Power cable 7 Ground cable yellow green 8 Fix the control wiring with the clamp 9 Control terminal block X2M 1 Knockout hole 2 Burr 3 Packing materials 2 3 1 Use a power wire pipe for the power wiring Outside the unit make sure the low voltage electric wiring i e for the remote control between u...

Page 17: ...rminals for connections to the power terminal block When none are available follow the instructions below Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firmly then secure to prevent out...

Page 18: ...ording to the instructions described in this manual according to the wiring diagrams and according to local and national regulations 4 Pipe sizes and pipe insulation Make sure that correct pipe sizes are installed and that the insulation work is properly executed 5 Additional refrigerant charge The amount of refrigerant to be added to the unit should be written on the included Added Refrigerant pl...

Page 19: ... 1 Led H1P H8P 2 Push button switches BS1 BS5 3 DIP switches 2 DS1 1 DS1 2 x OFF w ON c blinking For changing the set mode For field setting For field setting For test operation For resetting the address when the wiring is changed or when an additional air handling unit is installed NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P ...

Page 20: ...the sound of a magnetic solenoid valve may rise during this operation The following items are automatically checked Check for incorrect wiring Check if stop valves are open Check of refrigerant charge Automatic judgement of piping length 4 After the test operation maximum 30 minutes the unit automatically stops Check the operation results by the outdoor unit led indication H1P H2P H3P H4P H5P H6P ...

Page 21: ...e H1P led is on and the remote controller indicates test operation and external control and the operation will be prohibited 2 Recover the refrigerant using a refrigerant reclaimer For details see the operation manual delivered with the refrigerant reclaimer 3 Press the button and reset the setting mode 2 Installation error Malfunction code Remedial action The stop valve of an outdoor unit is left...

Page 22: ...steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately 2 Calculate the smallest room volume m3 In a case such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above If the result of t...

Page 23: ...1 2 3 4 D E E E E E 9 A B C 2 2 3 2 4 7 2 9 3 2 3 5 6 1 4 8 3 2 3 16 V 1 2 3 4 230 V 6 5 TO IN D UNIT F1 F2 TO OUT D UNIT F1 F2 DS1 1 2 F1 F2 OUT IN ON OFF A2P X2M A1P A2P A4P X2M F1 F1 F2 F2 TO IN D UNIT C H SELECTOR X2M A C B A4P TO OUT D UNIT 4 A B C 1 3 2 5 F1 F2 1 2 3 4 5 8 11 12 9 10 13 14 ...

Page 24: ...4PW51321 1 Copyright Daikin ...

Reviews: