background image

 

Installation manual

12

ERX125~250A7W1B

Inverter condensing unit

4PW30064-1D

1.

Remove the cap and turn the valve counterclockwise with the
hexagon wrench.

2.

Turn it until the shaft stops.

3.

Make sure to tighten the cap securely. Refer to the table below

Closing stop valve 

(See figure 21)

1.

Remove the cap and turn the valve clockwise with the hexagon
wrench.

2.

Securely tighten the valve until the shaft contacts the main body
seal.

3.

Make sure to tighten the cap securely.
For the tightening torque, refer to the table above.

11.4. Additional refrigerant charge

Follow the procedures below.

1

Adding additional refrigerant

(See figure 14)

Charge with the outdoor unit at standstill

1.

Calculate how much refrigerant to be added using the formula
explained in the chapter 

"4.2 How to calculate the additional

refrigerant to be charged" on page 6

.

2.

Open valve C (valves A and B and the stop valves must be left
closed) and charge the required amount of refrigerant through
the liquid side stop valve service port.

When the required amount of refrigerant is fully charged,
close valve C. Record, with a permanent marker, the amount
of refrigerant that was added on the wiring diagram attached
on the inside of the switch box. 
Perform the test procedure as described in 

"In case

refrigerant was added at standstill" on page 16

.

When the additional charging is not complete, perform the
procedure explained in the chapter 

"Charge with operating

outdoor unit" on page 12

.

Charge with operating outdoor unit
Charge the refrigerant through valve A.

1.

Start of charging refrigerant manually
-

Open the liquid and gas side stop valves and the service port 
stop valve. (Valves A, B and C must be closed.)

-

Close all front panels except the electric box front panel and 
turn the power ON.

-

Make sure the control box and evaporator unit are operating.

-

If the H2P LED is not flashing (in 12 minutes time after 
turning on the power), make sure it is displayed as shown 
below.
If the H2P LED is flashing, check the malfunction code on the
remote controller 

"3 Remote controller malfunction code

display" on page 13

.

Do not apply excessive force to the stop valve. Doing
so may break the valve body, as the valve is not a
backseat type. Always use the special tool.

Stop valve size

Tightening torque N•m (Turn clockwise to close)

Shaft

Cap (valve lid)

Service port

Valve body

Hexagonal 

wrench

Ø9.5

5.4~6.6

4 mm

13.5~16.5

11.5~13.9

Ø15.9

13.5~16.5

6 mm

23.0~27.0

Ø19.1

27.0~33.0

8 mm

22.5~27.5

Ø25.4

When charging a system, charging over the
permissible quantity can cause liquid hammer.

Always use protective gloves and protect your eyes
when charging refrigerant.

When the refrigerant charging procedure is done or
when pausing, close the valve of the refrigerant tank
immediately. If the tank is left with the valve open, the
amount of refrigerant which is properly charged may
get off point. More refrigerant may be charged by any
remaining pressure after the unit has stopped.

Electric shock warning

Close the electric box lid before turning on the main
power.

Perform the settings on the circuit board (A1P) of the
outdoor unit and check the LED display after the
power is on via the service lid which is in the lid of the
electric box. 
Operate switches with an insulated
stick (such as a ball-point pen) to
avoid touching the life parts. 
Make sure to re-attach the
inspection cover into the switch box cover after the job
is finished.

If the power of some units is turned off, the charging
procedure can not be finished properly.

Make sure to turn ON the power 6 hours before
starting the operation. This is necessary to warm the
crankcase by the electric heater.

If operation is performed within 12 minutes after the
indoor and outdoor units are turned on, the H2P-led
will be lit and the compressor will not operate.

NOTE

See

 

"11.3. Stop valve operation procedure" on

page 11

 for details on how to handle stop valves.

The refrigerant charging port is connected to the
piping inside the unit.
The unit's internal piping is already factory
charged with refrigerant, so be careful when
connecting the charge hose.

After adding the refrigerant, do not forget to close
the lid of the refrigerant charging port.
The tightening torque for the lid is 11.5 to
13.9 N•m. 

In order to ensure uniform refrigerant distribution,
it may take the compressor ±10 minutes to start
up after the unit has started operation. This is not
a malfunction.

1

Measuring instrument

2

Tank (siphon system)

3

Charge hose

4

Liquid line stop valve

5

Gas line stop valve

6

Stop valve service port

7

Valve B

8

Valve C

9

Valve A

10

Outdoor unit

11

Refrigerant charge port

12

To air handling unit

13

Inter-unit piping

14

Refrigerant flow

Summary of Contents for ERX125A7W1B

Page 1: ...INSTALLATION MANUAL ERX125A7W1B ERX200A7W1B ERX250A7W1B Inverter condensing unit ...

Page 2: ... d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 300 mm e 20 mm f 500 mm a 50 mm b 100 mm c 50 mm d 100 mm e 100 mm f 500 mm 3 2 2 4 4 8 14 1 1 1500 500 100 100 11 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 7 13 14 3 5 4 2 1 7 8 9 6 10 11 12 1 2 12 15 1 2 4 5 6 3...

Page 3: ...iitä käytetään ohjeidemme mukaisesti 14 za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům 15 u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint haszná...

Page 4: ...štelę 23 Maksimālais pieļaujamais spiediens PS K bar Minimālā maksimālā pieļaujamā temperatūra TS TSmin Minimālā temperatūra zemā spiediena pusē L C TSmax Piesātinātā temperatūra saskaņā ar maksimālo pieļaujamo spiedienu PS M C Dzesinātājs N Spiediena drošības ierīces iestatīšana P bar Izgatavošanas numurs un izgatavošanas gads skat modeļa izgatavotājuzņēmuma plāksnītie 24 Maximálny povolený tlak ...

Page 5: ...er condensing unit Installation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUIPMENT BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE ...

Page 6: ...tion site where sides A B C D have obstacles the wall heights of sides A C have no impact on service space dimensions Refer to figure 1 for impact of wall heights of sides B D on service space dimensions In case of an installation site where only the sides A B have obstacles the wall heights have no influence on any indicated service space dimensions 3 Make sure that there is no danger of fire due...

Page 7: ...re recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 2 In places with weak reception keep distances of 3 m or more to avoid electromagnetic disturbance of other equipment and use conduit tubes for power and transmission lines In heavy snowfall areas select an installation site where snow will not affect the...

Page 8: ...t infiltration of water coming from under the unit When installed in a corrosive environment use a nut with plastic washer 1 to protect the nut tightening part from rust Do not insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury Use R410A to add refrigerant All field piping must be installed by a licensed refrigeration techn...

Page 9: ...e knock holes wrap the wiring with protective tape to prevent damage Any gas remaining inside the stop valve may blow off the pinched piping causing damage or injury 1 Pinched piping 2 Stop valve 3 Service port 4 Point of melting the brazing metal Precautions when connecting field piping Perform brazing at the gas stop valve before brazing at the liquid stop valve Add brazing material as shown in ...

Page 10: ... the system passes the test If the pressure drops check where the nitrogen leaks from R Total length m of liquid piping size at Ø9 5 x0 059 Outdoor unit type Piping size mm Gas Liquid 125 Ø15 9 Ø9 5 200 Ø19 1 Ø9 5 250 Ø22 2 Ø9 5 Installation period Protection method More than a month Pinch the pipe Less than a month Pinch or tape the pipe Regardless of the period After all the piping has been conn...

Page 11: ...95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S2PH Pressure switch high SD1 Safety devices input T1A Current sensor A6P V1R Power module A4P V1R V2R Power module A3P X1A X4A Connector M1F X1M Terminal strip power supply X1M Terminal strip control A1P Y2E Expansion valve electronic type subcool Y1S Solenoid valve hotgas bypass Y2S Solenoid valve oil return Z...

Page 12: ...and lightning rods dangerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrical charge due to leaked electrical current which will have to be discharged with the grounding Be sure...

Page 13: ... 4 Pipe opening 5 Conduit 6 Power wiring and ground wiring 7 Cut off the shaded zones before use 8 Through cover 1 Knockout hole 2 Burr 3 If there are any possibilities that small animals enter the system through the knockout holes plug the holes with packing materials to be prepared on site 2 3 1 Outside the unit make sure the weak low voltage electric wiring i e for the remote control between un...

Page 14: ...ply cord make sure that the current carrying conductors become taut before the earthing conductor Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firm...

Page 15: ...e specified amount of refrigerant in liquid state to the liquid pipe Since this refrigerant is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not Be sure to use tools exclusively for R410A to ensure required pressure resistance and to preve...

Page 16: ...op valve size Tightening torque N m Turn clockwise to close Shaft Cap valve lid Service port Valve body Hexagonal wrench Ø9 5 5 4 6 6 4 mm 13 5 16 5 11 5 13 9 Ø15 9 13 5 16 5 6 mm 23 0 27 0 Ø19 1 27 0 33 0 8 mm 22 5 27 5 Ø25 4 When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your eyes when charging refrigerant When the r...

Page 17: ...turn to setting mode 1 H1P x OFF Setting mode 1 default system status H1P H2P H3P H4P H5P H6P H7P Default status normal x x w x x x x H1P H2P H3P H4P H5P H6P H7P w w w w w w w When charging in cooling mode the unit will stop operating when the required amount of refrigerant is charged H1P H2P H3P H4P H5P H6P H7P Pressure control for the first minute x c x x x x w Start up control for the next 2 mi...

Page 18: ...dding refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded 12 BEFORE OPERATION 12 1 Service precautions Pay attention to the fan It is dangerous to inspect the unit while the fan is running Be sure to turn off the main switch and to remove the fuses from the control circuit located in the outdoor unit H1P H2P H3P H4P H5P H6P H7P w c...

Page 19: ...tches LEDs and buttons Led state Throughout the manual the state of the LEDs is indicated as follows Setting the DIP switches Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB A1P The figure shows state of the LED indications when the unit is shipped from the factory Check operation procedure 1 Turn the power on for the outdoor unit an...

Page 20: ...ing to the crank case heater 3 Make the field setting as needed using the push buttons on the PCB A1P of the outdoor unit Refer to Field setting on page 15 4 Set the check operation without initial refrigerant decision following setting mode 2 in the field setting and perform the check operation The system operates for 30 minutes and automatically stops the check operation If no malfunction code i...

Page 21: ...nction code displayed on the remote controller In case of a displayed malfunction code perform the following actions to correct the abnormality Error codes on the remote controller when a remote controller is connected After correcting the abnormality press the button and reset the malfunction code Carry out the test operation again and confirm that the abnormality is properly corrected Air handli...

Page 22: ...s or standards The following standards may be applicable if local regulations are not available This unit like other air conditioning systems uses R410A as refrigerant R410A itself is an entirely safe non toxic non combustible refrigerant Nevertheless care must be taken to ensure that air conditioning facilities are installed in a room which is sufficiently large This assures that the maximum conc...

Page 23: ...n a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation NOTES A Where there are no smaller room divisions B Where there is a room division bu...

Page 24: ...NOTES NOTES ...

Page 25: ...21 1 2 3 4 5 19 L1 L2 L3 N 1 3 4 2 6 5 7 8 9 10 11 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 18 2 1 1 3 3 17 16 A A B C D 1 2 1 3 4 25 150 90 20 6 6 5 1 4 3 2 4 5 NOTES 16 17 18 19 20 21 ...

Page 26: ...4PW30064 1D Copyright Daikin ...

Reviews: