ERX125~250A7W1B
Inverter condensing unit
4PW30064-1D
Installation manual
17
Test operation procedure
1
Close all front panels except the front panel of the electric box.
2
Turn ON the power to all outdoor units and the connected units.
Be sure to turn on the power 6 hours before operation in order to
have power running to the crank case heater and to protect the
compressor.
3
Make the field setting as described in the paragraph
.
4
Press the
button once, and set to the SETTING
MODE (H1P LED = OFF).
5
Press and hold the
button down for 5 seconds or
more. The unit will start the test operation.
■
The test operation is automatically carried out in cooling
mode, the H2P LED will light up and the messages "Test
operation" and "Under centralized control" will display on the
remote controller.
■
It may take 10 minutes to bring the state of the refrigerant
uniform before the compressor starts.
■
During the test operation, the refrigerant running sound or
the magnetic sound of a solenoid valve may become loud
and the LED display may change, but these are not mal-
functions.
■
During the test operation, it is not possible to stop the unit
operation from a remote controller. To abort the operation,
press the
button. The unit will stop after
±30 seconds.
6
Close the front panel in order to let it not be the cause of
misjudgement.
7
Check the test operation results by the LED display on the
outdoor unit.
8
When the test operation is fully completed, normal operation will
be possible after 5 minutes.
Otherwise, refer to
"Correcting after abnormal completion of the
to take actions for correcting the
abnormality.
Correcting after abnormal completion of the test operation
The test operation is only completed if there is no malfunction code
displayed on the remote controller. In case of a displayed malfunction
code, perform the following actions to correct the abnormality:
■
Error codes on the remote controller when a remote controller is
connected
■
After correcting the abnormality, press the
button
and reset the malfunction code.
■
Carry out the test operation again and confirm that the
abnormality is properly corrected.
Air handling units are not checked by the outdoor unit
during test operation. After the test operation is finished,
check the air handling unit separately with its controller.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Normal completion
x
x w x
x
x
x
Abnormal completion
x w w x
x
x
x
BS1 MODE
BS4 TEST
BS3 RETURN
Installation error
Error code
Remedial action
The stop valve of an
outdoor unit is
remained closed.
E3
E4
F3
UF
Check referring to the table in
"Additional refrigerant charge"
The phases of the
power to the outdoor
units are reversed.
U1
Switch two of the three phases (L1,
L2, L3) to make a positive phase
connection.
No power is supplied
to an outdoor or any
other unit (including
phase interruption).
U1
U4
Check if the power wiring for the
outdoor units are connected
correctly.
(If the power wire is not connected
to L2 phase, no malfunction display
will appear and the compressor will
not work.)
Incorrect
interconnections
between units
UF
Check if the refrigerant line piping
and the unit wiring are consistent
with each other.
Refrigerant
overcharge
E3
F6
UF
Recalculate the required amount of
refrigerant from the piping length
and correct the refrigerant charge
level by recovering any excessive
refrigerant with a refrigerant
recovery machine.
The wiring is
connected to the
Q1/Q2 (Out Multi)
U7
UF
Remove the wiring from the Q1/Q2
(Out Multi).
Insufficient refrigerant
E4
F3
Check if the additional refrigerant
charge has been finished correctly.
Recalculate the required amount of
refrigerant from the piping length
and add an adequate amount of
refrigerant.
BS3 RETURN