Installation manual

2

ERX125~250A7W1B

Inverter condensing unit

4PW30064-1D

1.

I

NTRODUCTION

1.1.

Combination

The air conditioning unit can be installed in the following range.

Always use appropriate units compatible with R410A.
To learn which models of air handling units are compatible with
R410A, refer to the product catalogs.

The manufacturer of this outdoor unit has limited responsibility
for total capacity of the system because performance is
determined by the total system. The discharge air may fluctuate
depending on selected air handling unit and depending on the
installation configuration.

Both air handling unit (evaporator) and digital controller software
and hardware are field supply and are to be selected by the
installer. Refer to the manual "Option kit for combination of
Daikin condensing units with field supplied evaporators" for
more details.
Recommended temperature setting on the field supplied
controller is between 16°C and 25°C.

Refer to the installation and operation manual of the control box
or to the Technical Data for allowed heat exchanger
combinations.

1.2.

Standard supplied accessories

See location 1 in 

figure 6

  for reference to where following

accessories are supplied with the unit.

See location 2 in 

figure 6

  for reference to where following

accessories are supplied with the unit.

1.3.

Technical and Electrical specifications

Refer to the Engineering Data Book for the complete list of
specifications.

2.

M

AIN

 

COMPONENTS

For main components and function of the main components, refer to
the Engineering Data Book.

3.

S

ELECTING

 

INSTALLATION

 

SITE

Obtain the customer's permission before installing.

The inverter units should be installed in a location that meets the
following requirements:

1

The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.

2

The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available. (Refer to

figure 1

 and choose one of the possibilities).

In case of an installation site where sides A+B+C+D  have
obstacles, the wall heights of sides A+C have no impact on
service space dimensions. Refer to 

figure 1

 for impact of wall

heights of sides B+D on service space dimensions.

In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any
indicated service space dimensions.

3

Make sure that there is no danger of fire due to leakage of
inflammable gas.

4

Ensure that water cannot cause any damage to the location in
case it drips out the unit (e.g. in case of a blocked drain pipe).

5

The piping length may not exceed the allowable piping length
(see 

"4 Piping length restrictions" on page 5

).

6

Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturbs
anyone.

7

Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction. Frontal wind will
disturb the operation of the unit. If necessary, use a windscreen
to block the wind.

8

Do not install or operate the unit on locations where air contains
high levels of salt, like e.g. in the vicinity of oceans. (Refer for
further information to the engineering databook).

9

During installation, avoid the possibility that anybody can climb
on the unit or place objects on the unit.

Falls may result in injury.

10

When installing the unit in a small room, take measures in order
to keep the refrigerant concentration from exceeding allowable
safety limits in the event of a refrigerant leak.

Installation manual 

1

Operation manual 

1

Item

Quantity

Gas side accessory pipe

1

Gas side accessory pipe

1

Liquid side accessory pipe

1

Liquid side accessory pipe

1

Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

If not, the unit may fall over and cause damage or
injury.

A B C D

Sides along the installation site with obstacles

Suction side

NOTE

The service space dimensions in 

figure 1

  are

based on cooling operation at 35°C.

Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.

Summary of Contents for ERX125A7W1B

Page 1: ...INSTALLATION MANUAL ERX125A7W1B ERX200A7W1B ERX250A7W1B Inverter condensing unit ...

Page 2: ... d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 300 mm e 20 mm f 500 mm a 50 mm b 100 mm c 50 mm d 100 mm e 100 mm f 500 mm 3 2 2 4 4 8 14 1 1 1500 500 100 100 11 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 7 13 14 3 5 4 2 1 7 8 9 6 10 11 12 1 2 12 15 1 2 4 5 6 3...

Page 3: ...iitä käytetään ohjeidemme mukaisesti 14 za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům 15 u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint haszná...

Page 4: ...štelę 23 Maksimālais pieļaujamais spiediens PS K bar Minimālā maksimālā pieļaujamā temperatūra TS TSmin Minimālā temperatūra zemā spiediena pusē L C TSmax Piesātinātā temperatūra saskaņā ar maksimālo pieļaujamo spiedienu PS M C Dzesinātājs N Spiediena drošības ierīces iestatīšana P bar Izgatavošanas numurs un izgatavošanas gads skat modeļa izgatavotājuzņēmuma plāksnītie 24 Maximálny povolený tlak ...

Page 5: ...er condensing unit Installation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUIPMENT BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE ...

Page 6: ...tion site where sides A B C D have obstacles the wall heights of sides A C have no impact on service space dimensions Refer to figure 1 for impact of wall heights of sides B D on service space dimensions In case of an installation site where only the sides A B have obstacles the wall heights have no influence on any indicated service space dimensions 3 Make sure that there is no danger of fire due...

Page 7: ...re recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 2 In places with weak reception keep distances of 3 m or more to avoid electromagnetic disturbance of other equipment and use conduit tubes for power and transmission lines In heavy snowfall areas select an installation site where snow will not affect the...

Page 8: ...t infiltration of water coming from under the unit When installed in a corrosive environment use a nut with plastic washer 1 to protect the nut tightening part from rust Do not insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury Use R410A to add refrigerant All field piping must be installed by a licensed refrigeration techn...

Page 9: ...e knock holes wrap the wiring with protective tape to prevent damage Any gas remaining inside the stop valve may blow off the pinched piping causing damage or injury 1 Pinched piping 2 Stop valve 3 Service port 4 Point of melting the brazing metal Precautions when connecting field piping Perform brazing at the gas stop valve before brazing at the liquid stop valve Add brazing material as shown in ...

Page 10: ... the system passes the test If the pressure drops check where the nitrogen leaks from R Total length m of liquid piping size at Ø9 5 x0 059 Outdoor unit type Piping size mm Gas Liquid 125 Ø15 9 Ø9 5 200 Ø19 1 Ø9 5 250 Ø22 2 Ø9 5 Installation period Protection method More than a month Pinch the pipe Less than a month Pinch or tape the pipe Regardless of the period After all the piping has been conn...

Page 11: ...95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S2PH Pressure switch high SD1 Safety devices input T1A Current sensor A6P V1R Power module A4P V1R V2R Power module A3P X1A X4A Connector M1F X1M Terminal strip power supply X1M Terminal strip control A1P Y2E Expansion valve electronic type subcool Y1S Solenoid valve hotgas bypass Y2S Solenoid valve oil return Z...

Page 12: ...and lightning rods dangerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrical charge due to leaked electrical current which will have to be discharged with the grounding Be sure...

Page 13: ... 4 Pipe opening 5 Conduit 6 Power wiring and ground wiring 7 Cut off the shaded zones before use 8 Through cover 1 Knockout hole 2 Burr 3 If there are any possibilities that small animals enter the system through the knockout holes plug the holes with packing materials to be prepared on site 2 3 1 Outside the unit make sure the weak low voltage electric wiring i e for the remote control between un...

Page 14: ...ply cord make sure that the current carrying conductors become taut before the earthing conductor Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firm...

Page 15: ...e specified amount of refrigerant in liquid state to the liquid pipe Since this refrigerant is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not Be sure to use tools exclusively for R410A to ensure required pressure resistance and to preve...

Page 16: ...op valve size Tightening torque N m Turn clockwise to close Shaft Cap valve lid Service port Valve body Hexagonal wrench Ø9 5 5 4 6 6 4 mm 13 5 16 5 11 5 13 9 Ø15 9 13 5 16 5 6 mm 23 0 27 0 Ø19 1 27 0 33 0 8 mm 22 5 27 5 Ø25 4 When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your eyes when charging refrigerant When the r...

Page 17: ...turn to setting mode 1 H1P x OFF Setting mode 1 default system status H1P H2P H3P H4P H5P H6P H7P Default status normal x x w x x x x H1P H2P H3P H4P H5P H6P H7P w w w w w w w When charging in cooling mode the unit will stop operating when the required amount of refrigerant is charged H1P H2P H3P H4P H5P H6P H7P Pressure control for the first minute x c x x x x w Start up control for the next 2 mi...

Page 18: ...dding refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded 12 BEFORE OPERATION 12 1 Service precautions Pay attention to the fan It is dangerous to inspect the unit while the fan is running Be sure to turn off the main switch and to remove the fuses from the control circuit located in the outdoor unit H1P H2P H3P H4P H5P H6P H7P w c...

Page 19: ...tches LEDs and buttons Led state Throughout the manual the state of the LEDs is indicated as follows Setting the DIP switches Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB A1P The figure shows state of the LED indications when the unit is shipped from the factory Check operation procedure 1 Turn the power on for the outdoor unit an...

Page 20: ...ing to the crank case heater 3 Make the field setting as needed using the push buttons on the PCB A1P of the outdoor unit Refer to Field setting on page 15 4 Set the check operation without initial refrigerant decision following setting mode 2 in the field setting and perform the check operation The system operates for 30 minutes and automatically stops the check operation If no malfunction code i...

Page 21: ...nction code displayed on the remote controller In case of a displayed malfunction code perform the following actions to correct the abnormality Error codes on the remote controller when a remote controller is connected After correcting the abnormality press the button and reset the malfunction code Carry out the test operation again and confirm that the abnormality is properly corrected Air handli...

Page 22: ...s or standards The following standards may be applicable if local regulations are not available This unit like other air conditioning systems uses R410A as refrigerant R410A itself is an entirely safe non toxic non combustible refrigerant Nevertheless care must be taken to ensure that air conditioning facilities are installed in a room which is sufficiently large This assures that the maximum conc...

Page 23: ...n a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation NOTES A Where there are no smaller room divisions B Where there is a room division bu...

Page 24: ...NOTES NOTES ...

Page 25: ...21 1 2 3 4 5 19 L1 L2 L3 N 1 3 4 2 6 5 7 8 9 10 11 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 18 2 1 1 3 3 17 16 A A B C D 1 2 1 3 4 25 150 90 20 6 6 5 1 4 3 2 4 5 NOTES 16 17 18 19 20 21 ...

Page 26: ...4PW30064 1D Copyright Daikin ...

Reviews: