Error Codes: Outdoor Units
ESIE13-02
Part 4 – Troubleshooting
112
3
1
4
5
Troubleshooting
(*) See also "Check No.10 - Outdoor Unit: Fan Speed Pulse" on page 159.
Remove the foreign
matter.
Replace the fan motor.
NO
YES
Ask repair so that the
supply voltage will be within
the normal range.
Turn OFF the power again (and
wait for 10 minutes).
Remove the fan motor connector.
Is the supply
voltage within the range 180
to 220 VAC ?
NO
YES
Properly connect the
connector.
-
NO
YES
Is there any
foreign matter around the
fan?
NO
YES
Is the fan
rotatable easily
by hand?
A
Check 10
check the fan motor.
-
Is
the fan
motor connector
correctly connected to
the outdoor PC board?
Is the connector X191A of
reactor coil (L4R) correctly
connected?