ESIE13-02
Error Codes: Outdoor Units
125
Part 4 – Troubleshooting
4
3
4
5
4
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
NO
YES
Request an improvement to
make the power supply voltage
fall within the standard range.
Turn OFF the power supply
once.
Check the resistance value for
the fan motor.
Is the
power supply voltage
between 180 and 220
VAC?
NO
YES
Connect tightly and correctly.
Is the
lead wire for
compressor connected to
PC board and compressor
without becoming
loose?
NO
Replace the fan motor.
Is the
resistance value of the
fan motor normal?
NO
YES
YES
Replace the fuse. Use only
specified fuses.
There is no problem with the unit.
An external factor (noise, etc.) other
than unit failure may be the cause.
Replace the outdoor PC board
(A2P) ERHQ***V3* / ERLQ***V3*
Power ON again.
Does the
fuse F6U have
continuity?
YES
NO
Does "L1"
malfunction reoccur?