Error Codes: Outdoor Units
ESIE13-02
Part 4 – Troubleshooting
128
3
1
4
5
4.13
“L5”
DC Output Overcurrent (Instantaneous)
Remote controller
display
L5
Method of
malfunction
detection
Malfunction is detected by converting the current flowing to power transistor into voltage with CT1 (DC
current sensor).
Malfunction
decision conditions
When overcurrent has run to power transistor.
(Actuated even by instantaneous overcurrent)
Supposed causes
Faulty compressor coil (disconnection, poor insulation)
Compressor startup malfunction (mechanical lock)
Faulty inverter PC board
Instantaneous fluctuation of power supply voltage
Faulty compressor (if bearing is scratched)
The stop valve is left in closed.