Additional Checks for Troubleshooting
ESIE13-02
Part 4 – Troubleshooting
154
3
1
4
5
Be careful when ordering spare part sensor for tank thermistor.
Thermistor
resistance check
Remove the connectors of the thermistors on the PCB, and measure the resistance of each thermistor
using tester.
The tank thermistor is for EKHWS-B and EKHWE domestic hot water tanks.
The relationship between normal temperature and resistance is shown in the graph and the table
below:
Tank thermistor for EHV*CA* domestic hot water tanks.
NTC-curve tank thermistor
Hydro-box
3SA48002
R25°C=20k
Ω
B=3990
-20
197.8 k
Ω
-15
148.2 k
Ω
-10
112.0 k
Ω
-5
85.52 k
Ω
0
65.84 k
Ω
5
51.05 k
Ω
10
39.91 k
Ω
15
31.44 k
Ω
20
24.95 k
Ω
25
19.94 k
Ω
30
16.04 k
Ω
35
12.99 k
Ω
40
10.58 k
Ω
45
8.669 k
Ω
50
7.143 k
Ω
T°C
Resistance value
-20
197.81 k
Ω
0
65.84 k
Ω
25
20 k
Ω