Check No.5 - Resistance Conversion Table (Discharge Pipe Sensor)
Temperature –
resistance
The table below is the discharge pipe thermistor temperature – resistance conversion table
.
Temp.
(°C)
Resist.
(k
Ω
)
Temp.
(°C)
Resist.
(k
Ω
)
Temp.
(°C)
Resist.
(k
Ω
)
—
—
60.0
52.8
130.0
5.4
—
-6.0
-4.0
-2.0
—
1120.0
1002.5
898.6
62.0
64.0
66.0
68.0
48.9
45.3
42.0
39.0
132.0
134.0
136.0
138.0
5.4
4.8
4.6
4.3
0.0
806.5
70.0
36.3
140.0
4.1
2.0
4.0
6.0
8.0
724.8
652.2
587.6
530.1
72.0
74.0
76.0
78.0
33.7
31.4
29.2
27.2
142.0
144.0
146.0
148.0
3.9
3.7
3.5
3.3
10.0
478.8
80.0
25.4
150.0
3.2
12.0
14.0
16.0
18.0
432.9
392.0
355.3
322.4
82.0
—
—
—
23.7
—
—
—
152.0
154.0
156.0
158.0
3.0
2.9
2.7
2.6
20.0
292.9
—
—
160.0
2.5
22.0
24.0
26.0
28.0
266.3
242.5
221.0
201.6
92.0
94.0
96.0
98.0
16.9
15.8
14.8
13.9
162.0
164.0
166.0
168.0
2.3
2.5
2.1
2.0
30.0
184.1
100.0
13.1
170.0
1.9
32.0
34.0
36.0
38.0
168.3
154.0
141.0
129.3
102.0
104.0
106.0
108.0
12.3
11.5
10.8
10.2
172.0
174.0
176.0
178.0
1.9
1.8
1.7
1.6
40.0
118.7
110.0
9.6
180.0
1.5
42.0
44.0
46.0
48.0
109.0
100.2
92.2
84.9
112.0
114.0
116.0
118.0
9.0
8.5
8.0
7.6
—
50.0
78.3
120.0
7.1
52.0
54.0
56.0
58.0
72.2
66.7
61.6
57.0
122.0
124.0
126.0
128.0
6.7
6.4
6.0
5.7