Outdoor Unit
ESIE13-02
Part 2 – Specifications
48
3
1
2
5
Operation
range
(1)
Heating (heat
pump)
Min
°CDB
-25
Max
°CDB
25
Cooling
Min
°CWB
10
Max
°CWB
43
Sound level
(nominal)
Heating (heat
pump)
Sound power
(4/6/8)
dBA
61 / 61 / 62
Sound pressure
(4/6/8)
(2)
dBA
48 / 48 / 49
Cooling
Sound power
dBA
63 / 63 / 63
Sound pressure
(4/6/8)
(2)
dBA
48 / 49 / 50
Refrigerant
Type
<R-410A>
Charge EHYRLQ005 / EHYRLQ008
kg
1.45 / 1.60
Control
<Expansion valve (electronic type)>
N° of circuits
1
Refrigerant oil
Type
<FVC50K>
Charged volume
l
0,75
Piping connec-
tions
Liquid
Type
<Flare connection>
Diameter (OD)
mm
<6,35>
Gas
Type
<Flare connection>
Diameter (OD)
mm
<15,9>
Drain
Quantity
2
Type
Hole
Diameter (OD)
mm
1xØ15 + 1xØ20
Piping length
Minimum
m
3
Maximum
m
30
Additional refrigerant charge
kg/m
0,02 IF > 10 m
Height difference
between outdoor
unit and indoor
unit
Maximum
m
20
Defrost method
<Reverse cycle>
Defrost control
<Sensor for outdoor heat exchanger temperature>
Capacity control method
<Inverter controlled>
Standard acces-
sories
Item
<Installation manual>
Quantity
1