Troubleshooting
ESIE13-02
Part 4 – Troubleshooting
58
3
1
4
5
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Output
from
PC
board
Is the power
switch OFF or the fuse for
power switch
blown?
Is the heating
switch turned on at outdoor
temperature
>35°C
YES
1
Is rated
voltage applied at the
compressor
terminals?
2
Is rated
voltage output from the
magnetic switch or power
transistor?
3
Is rated
voltage output from the
PC board?
YES
YES
·
Hydro-box pump runs at set flow rate.
Hydro-box
PC board
Outdoor unit
PC board
Relay
1
Output from
magnetic
switch or
U,V,W of
power
transistor
2
Output from
magnetic
switch or SW
circuit of
power
transistor
3
Output from
relay or
microcomputer
Input
to PC
board
Input
to PC
board
NO
NO
YES
NO
NO
YES
NO
Sensor
Magnetic
switch
COMP
Turn on the power
switch or replace fuse.
Normal.
(Thermostat OFF by
outdoor temperature)
Replace the compressor.
Replace the magnetic
switch or power transistor.
Replace the PC board.
Check the thermistor.
Is setting A.2.1.9
pump operation mode set to
(0) = continuous pump
operation?
YES
NO
Normal operation.