ESIE13-02
Troubleshooting
71
Part 4 – Troubleshooting
4
3
4
5
4
1.2.12 The User Interface Does Not Display Certain Screens (RT, LWT, Tank, Ext RT)
Applicable models
EHB*CA, EHV*CA
Error detection
method
Error generating
condition
Supposed causes -
corrective action
Possible causes
Corrective action
The tank-screen is not visible.
Check if there is a tank connected? Then setting
A.2.2.1. should be set to yes.
The RT-screen is not visible.
Check setting A.2.1. to see if unit control method
is set to Room Thermostat control.
The ext RT-screen is not visible.
Check setting A.2.1. to see if unit control method
is set to ext Room Thermostat control.
The LWT-screen is not visible.
1. Check setting A.2.1. to see if unit control
method is set to LWT.
2. Check 7.4.1 (user settings - available home
page if LWT screen is enabled).