10
|
Configuration
Installer reference guide
146
EPRA14~W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02
6
Press the left dial to confirm the new setting.
7
Press the center button to go back to the home screen.
INFORMATION
When you change the overview settings and you go back to the home screen, the
user interface will show a popup screen and request to restart the system.
When confirmed, the system will restart and recent changes will be applied.
10.1.2 To connect the PC cable to the switch box
Prerequisite:
The EKPCCAB4 kit is required.
1
Connect the USB connector of the cable to your PC.
2
Connect the plug of the cable to X10A on A1P of the switch box of the indoor
unit.
A1P
X10A
3
Pay special attention to the position of the plug!
2
3
4
5
H J
ST
10.2 Configuration wizard
After first power ON of the system, the user interface starts a configuration wizard.
Use this wizard to set the most important initial settings for the unit to run
properly. If required, you can afterwards configure more settings. You can change
all these settings via the menu structure.
You can find a short overview of the settings in the configuration here. All the
settings can also be adjusted in the settings menu (use the breadcrumbs).
For the setting…
Refer to…
Language
[7.1]
Time/date
[7.2]