9
|
Electrical installation
Installer reference guide
112
EPRA14~W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1A – 2022.07
L N PE
1 2
4
(Optional)
Power saving function
: If you want to use the power saving
function:
▪
Disconnect X804A from X805A.
▪
Connect X804A to X806A.
X806A
X804A
X805A
INFORMATION
Power saving function.
The power saving function is only applicable for V3 models.
For more information about the power saving function ([9.F] or overview field setting
[E‑08]), see
In case of W1 models
1
Power supply cable
:
▪
Route the cable through the frame.
▪
Connect the wires to the terminal block.
▪
Fix the cable with a cable tie.
Wires: 3N+GND
Maximum running current: Refer to name plate on unit.
—