10
|
Configuration
Installer reference guide
206
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1C – 2023.07
Backup heater type
#
Code
Description
[9.3.1]
[E‑03]
▪
0:
None
▪
2:
3V
▪
3:
6V
▪
4:
9W
Voltage
▪
For a
3V
and
6V
model, this is fixed to
230V, 1ph
.
▪
For a
9W
model, this is fixed to
400V, 3ph
.
#
Code
Description
[9.3.2]
[5‑0D]
▪
0:
230V, 1ph
▪
2:
400V, 3ph
Configuration
The backup heater can be configured in different ways. For the
3V
model, the
system variably choses from 3 available capacity steps the adequate capacity for
the given operating conditions. For the
6V
and
9W
model, it can be chosen to have
a 1-step only backup heater or a backup heater with 2 steps. If 2 steps, the capacity
of the second step depends on this setting. It can also be chosen to have a higher
capacity of the second step in emergency.
#
Code
Description
[9.3.3]
[4‑0A]
▪
0: Relay 1
▪
1: Relay 1 / Relay 1+2
▪
2: Relay 1 / Relay 2
▪
3: Relay 1 / Relay 2
Emergency
Relay 1+2
INFORMATION
Settings [9.3.3] and [9.3.5] are linked. Changing one setting influences the other. If
you change one, check if the other is still as expected.
INFORMATION
During normal operation, the capacity of the second step of the backup heater at
nominal voltage is equal to [6‑03]+[6‑04].
INFORMATION
If [4‑0A]=3 and emergency mode is active, the power usage of the backup heater is
maximal and equal to 2×[6‑03]+[6‑04].
INFORMATION
If the storage temperature setpoint is higher than 50°C and no auxiliary boiler is
installed, Daikin recommends NOT to disable the backup heater second step because
it will have a big impact on the required time for the unit to heat up the storage tank.
INFORMATION
The capacities displayed in the selection menu for [4-0A] are only correctly displayed
for correct selection of the capacity steps [6-03] and [6-04].
Summary of Contents for ETSXB16E
Page 313: ......
Page 314: ......
Page 315: ......
Page 316: ...4P679467 1C 2023 07 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...