15
|
Disposal
Installer reference guide
267
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1C – 2023.07
15.1.2 Recovery mode — In case of EPRA-DAV3* and EPRA-DAW1* models (7-LEDs display)
Components
To activate/deactivate the recovery mode, you need the following components:
SET
BS1
MODE
BS2
BS3
BS4
RETURN
PUMP DOWN
H1P
H2P
H3P
H4P
H5P
H6P
H7P
DEMAND
L.N.O.P.
HWL
MODE
TEST
EPRA-DAV3*
EPRA-DAW1*
H1P~H7P
7‑LEDs display
BS1~BS4
Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
To activate the recovery mode
INFORMATION
If you get confused in the middle of the process, press BS1 to return to the default
situation.
Before recovering refrigerant, activate the recovery mode as follows:
#
Action
7-LEDs display
(a)
H1P H2P H3P H4P H5P H6P H7P
1
Start from the default situation.
2
Press and hold
BS1
for 5 seconds.
3
Press
BS2
9 times.
4
Press
BS3
once.
5
Press
BS2
once.
6
Press
BS3
once.
7
Press
BS3
once.
The flashing H1P indicates the
recovery mode has been correctly
selected and is activated.
8
Press
BS1
once.
H1P keeps flashing, indicating that
you are in a mode that does not
allow compressor operation.
(a)
= OFF, = ON, and = flashing.
Summary of Contents for ETSXB16E
Page 313: ......
Page 314: ......
Page 315: ......
Page 316: ...4P679467 1C 2023 07 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...