10
|
Configuration
Installer reference guide
169
EPRA14~18D + ET23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
NOTICE
If there are 2 zones and the emitter types are wrongly configured, water of high
temperature can be sent towards a low temperature emitter (underfloor heating). To
avoid this:
▪
Install an aquastat/thermostatic valve to avoid too high temperatures towards a
low temperature emitter.
▪
Make sure you set the emitter types for the main zone [2.7] and for the
additional zone [3.7] correctly in accordance with the connected emitter.
Pump operation mode
When the space heating/cooling operation is OFF, the pump is always OFF. When
space heating/cooling operation is ON, you have the choice between these
operation modes:
#
Code
Description
[4.5]
[F–0D]
Pump operation mode
:
▪
0
Continuous
: Continuous pump operation,
regardless of thermo ON or OFF condition.
Remark:
Continuous pump operation requires
more energy than sample or request pump
operation.
a
b
c
d
b
c
a
Space heating/cooling control
b
Off
c
On
d
Pump operation