10
|
Configuration
Installer reference guide
202
EPRA14~18D + ET23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
#
Code
Description
[9.A.1]
[D‑08]
Electricity meter 1
:
▪
0
None
: NOT installed
▪
1
1/10kWh
: Installed
▪
2
1/kWh
: Installed
▪
3
10/kWh
: Installed
▪
4
100/kWh
: Installed
▪
5
1000/kWh
: Installed
[9.A.2]
[D‑09]
Electricity meter 2
:
▪
0
None
: NOT installed
▪
1
1/10kWh
: Installed
▪
2
1/kWh
: Installed
▪
3
10/kWh
: Installed
▪
4
100/kWh
: Installed
▪
5
1000/kWh
: Installed
In case of pulse meter for photovoltaic panels:
▪
6
100/kWh for PV panel
: Installed
▪
7
1000/kWh for PV panel
: Installed
Sensors
External sensor
#
Code
Description
[9.B.1]
[C–08]
External sensor
: When an optional external
ambient sensor is connected, the type of the
sensor must be set.
▪
0
None
: NOT installed. The thermistor in the
dedicated Human Comfort Interface and in the
outdoor unit are used for measurement.
▪
1
Outdoor
: Connected to PCB of the indoor
unit measuring the
outdoor temperature
.
Remark:
For
some
functionality,
the
temperature sensor in the outdoor unit is still
used.
▪
2
Room
: Connected to PCB of the indoor unit
measuring the
indoor temperature
. The
temperature sensor in the dedicated Human
Comfort Interface is NOT used anymore.
Remark:
This value has only meaning in room
thermostat control.
Ext. amb. sensor offset
ONLY applicable in case an external outdoor ambient sensor is connected and
configured.
Summary of Contents for ETVZ16E6V7
Page 281: ......
Page 282: ......
Page 283: ......
Page 284: ...4P644739 1A 2022 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...