9/12
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[3-0B]
--
1
9.I
[3-0C]
--
1
9.I
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
9.I
[4-01]
R/W
0: None
1: BSH
2: BUH
9.I
[4-02]
R/W
14~35°C, step: 1°C
35°C
9.I
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
9.I
[4-04]
R/W
0: Intermittent
1: Continuous
2: Off
9.I
[4-05]
0
9.I
[4-06]
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.I
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
9.I
[4-09]
R/W
0: Current
1: Power
9.I
[4-0A]
R/W
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.I
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C(*3)
9.I
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C(*3)
9.I
[4-0E]
6
9.I
[5-00]
R/W
0: No (*5)
1: Yes (*4)
9.I
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-02]
R/W
0: Disabled
1: Enabled
9.I
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.I
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0D]
R/W (*1)
R/O (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
9.I
[5-0E]
1
9.I
[6-00]
R/W
2~40°C, step: 1°C
8°C
9.I
[6-01]
R/W
0~10°C, step: 1°C
2°C
9.I
[6-02]
R/W
0~10kW, step: 0,2kW
0
kW
9.I
[6-03]
R/W
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
9.I
[6-04]
R/W
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
9.I
[6-07]
0
9.I
[6-08]
R/W
2~20°C, step: 1°C
10°C
9.I
[6-09]
0
9.I
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.I
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.I
[6-0E]
R/W
40~65°C, step: 1°C
65°C
9.I
[7-00]
R/W
0~4°C, step: 1°C
0°C
9.I
[7-01]
R/W
2~40°C, step: 1°C
2°C
Domestic hot water booster heater hysteresis.
What is the desired comfort storage temperature?
What is the desired eco storage temperature?
What is the desired reheat temperature?
What is the desired DHW production type?
What is the maximum temperature setpoint?
Domestic hot water booster heater overshoot temperature.
What is the capacity of the booster heater?
What is the capacity of the backup heater step 1?
What is the capacity of the backup heater step 2?
--
What is the hysteresis to be used in reheat mode?
--
What is the requested limit for DI3?
What is the requested limit for DI4?
Backup heater voltage
--
The temperature difference determining the heat pump ON temperature.
The temperature difference determining the heat pump OFF temperature.
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the requested limit for DI1?
What is the requested limit for DI2?
--
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
What is the equilibrium temperature for the building?
Space heating priority.
Space heating priority temperature.
Set point correction for domestic hot water temperature.
Emergency
Which power limitation mode is required on the system?
Which power limitation type is required?
Backup heater configuration
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
What is the BUH operation mode?
Which electric heater has priority?
Below which outdoor temperature is heating allowed?
Operation permission of the booster heater.
Water pipe freeze prevention
--
(*1) *6V*_(*2) *9W*_
(*3) Only applicable for models where cooling is possible_
(*4) E_(*5) E7
4P644735-1A - 2022.03