10
|
Configuration
Installer reference guide
150
EPRA14~18D + ET23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
Setpoint mode
Define the setpoint mode:
▪
Fixed
: the desired leaving water temperature does not depend on the outdoor
ambient temperature.
▪
In
WD heating, fixed cooling
mode, the desired leaving water
temperature:
-
depends on the outdoor ambient temperature for heating
-
does NOT depend on the outdoor ambient temperature for cooling
▪
In
Weather dependent
mode, the desired leaving water temperature depends
on the outdoor ambient temperature.
#
Code
Description
[2.4]
N/A
Setpoint mode
:
▪
Fixed
▪
WD heating, fixed cooling
▪
Weather dependent
When weather dependent operation is active, low outdoor temperatures will result
in warmer water and vice versa. During weather dependent operation, the user
can shift the water temperature up or down by a maximum of 10°C.
Heating WD curve
Set weather-dependent heating for the main zone (if [2.4]=1 or 2):
Summary of Contents for ETVZ16E6V7
Page 281: ......
Page 282: ......
Page 283: ......
Page 284: ...4P644739 1A 2022 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...