7
|
Unit installation
Installer reference guide
62
EPRA14~18D + ET23E
Daikin Altherma 3 H HT F
4P644739-1A – 2022.03
▪
"7.2.7 To lower the switch box on the indoor unit"
▪
"7.4.4 To connect the drain hose to the drain"
▪
When you need access to the high voltage switch box
2×
T25
5
If you need access to the high voltage components, remove the high voltage
switch box cover.
4×
T25
7.2.7 To lower the switch box on the indoor unit
During the installation, you will need access to the inside of the indoor unit. To
have easier front access, put the switch box lower on the unit as follows:
Prerequisite:
The user interface panel and front panel have been removed.
1
Remove the fixing plate at the top of the unit.
2
Tilt the switch box to the front and lift it out of its hinges.