An overview of the fault indications and safeties is given in ‘Overview of Fault Indications and Safeties’
on page 3-7.
High pressure
switch
■
water flow too low in heating
■
water temperature too high in
heating
■
defective condenser fan
operation in cooling
■
dirty or blocked condenser
■
operation out of range
■
pump operation
■
water flow (blocked valves)
■
flow switch operation
■
operation condition
outdoor air temperature < 43 °C
leaving condenser water < 25 °C
■
state of the condenser (clean)
Flow switch or
pump contact
■
damaged flow switch
■
incorrect pump operation
■
incorrect field wiring
■
defective control devices
(pump relay)
■
flow switch
■
pump operation
■
field wiring
■
control devices
Discharge ther-
mal protector
■
Refrigerant shortage
■
Operation out of range
■
Refrigerant leak
■
Operation condition
Fan thermal
protector
■
Blocked fan
■
Blocked condenser
■
State of the fans (free rotation)
■
State of the condenser
Reverse phase
protection
■
Incorrect phase direction
■
One phase missing
■
Swap two phases
■
Connect the loose phase
Problem
Possible causes
Items to be checked
Summary of Contents for EUWA/Y5-30HB/C(Z)
Page 2: ......
Page 8: ...Introduction ESIE98 06A vi 3 1 4 5...
Page 10: ...ESIE98 06A 1 2 Part 1 System Outline 3 1 1 4 5...
Page 28: ...General Outline ESIE98 06A 1 20 Part 1 System Outline 3 1 1 4 5...
Page 36: ...Piping Layout ESIE98 06A 1 28 Part 1 System Outline 3 1 1 4 5...
Page 52: ...ESIE98 06A Wiring Layout Part 1 System Outline 1 44...
Page 58: ...ESIE98 06A 2 2 Part 2 Functional Description 3 1 2 4 5...
Page 100: ...ESIE98 06A 3 2 Part 3 Troubleshooting 3 1 3 4 5...
Page 134: ...Troubleshooting ESIE98 06A 3 36 Part 3 Troubleshooting 3 1 3 4 5...
Page 136: ...ESIE98 06A 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 142: ...Pre Test Run Checks ESIE98 06A 4 8 Part 4 Commissioning and Test Run 3 1 4 5...