ESIE98–06A
Troubleshooting
Part 3 – Troubleshooting
3–27
3
3
4
5
1
To exit the factory
menu
When you have changed all parameters, proceed as follows to exit:
FC
triac pulse length
factory
2
0
A2
antifreeze-alarm hysteresis
factory
5
5
A3
bypass-time for antifreeze-alarm
factory
0
0
A5
antifreeze-heater differential
factory
1
3
A6
supporting heaters probe
factory
0
0
A7
limit antifreeze-alarm set
factory
- 40
- 15
P1
flow start timer
factory
20
20
P2
flow stop timer
factory
5
5
P3
LP bypass timer
factory
40
60
P4
buzzer on time
user
1
1
P5
reset of alarms
factory
0
0
P8
selection of digital input ID1
factory
0
1
PA
low pressure alarm when the compressor is
OFF
factory
0
0
Pb
high temperature alarm set
user
90
90
PC
high temperature alarm delayed at start-up
user
30
30
H5
pump functional logic
factory
1
1
H6
cooling/heating input
user
0
0
H7
on/off input
user
0
0
H8
number of terminals
factory
0
0
H9
keyboard lock-up
user
1
1
HA
serial address
user
1
1
Hb
infrared remote control password
user
0
1
HC
second set of parameters
factory
0
1
Hd
logic inversion cooling/heating
factory
0
1
HE
inversion valve status cooling/heating
factory
0
1
HF
alarm relay state without alarm
factory
1
0
HG
software release version
factory
1.3
1.3
FC
triac pulse length
factory
2
0
A7
limit antifreeze alarm set
factory
-40
-15
Name
Function
Parameter
CAREL
(default)
EUWA/Y5-10HB
Step
Action
1
Press
p
.
2
Put off the power supply.
Summary of Contents for EUWA/Y5-30HB/C(Z)
Page 2: ......
Page 8: ...Introduction ESIE98 06A vi 3 1 4 5...
Page 10: ...ESIE98 06A 1 2 Part 1 System Outline 3 1 1 4 5...
Page 28: ...General Outline ESIE98 06A 1 20 Part 1 System Outline 3 1 1 4 5...
Page 36: ...Piping Layout ESIE98 06A 1 28 Part 1 System Outline 3 1 1 4 5...
Page 52: ...ESIE98 06A Wiring Layout Part 1 System Outline 1 44...
Page 58: ...ESIE98 06A 2 2 Part 2 Functional Description 3 1 2 4 5...
Page 100: ...ESIE98 06A 3 2 Part 3 Troubleshooting 3 1 3 4 5...
Page 134: ...Troubleshooting ESIE98 06A 3 36 Part 3 Troubleshooting 3 1 3 4 5...
Page 136: ...ESIE98 06A 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 142: ...Pre Test Run Checks ESIE98 06A 4 8 Part 4 Commissioning and Test Run 3 1 4 5...