background image

Installation and operation manual

15

EUWAC5~10FZ

Packaged air-cooled water chillers

4PW14037-1D

M

AINTENANCE

In order to ensure optimal availability of the unit, a number of checks
and inspections on the unit and the field wiring have to be carried out
at regular intervals.

If the unit is used for air conditioning application, the described
checks should be executed at least once a year. In case the unit is
used for other applications, the checks should be executed every 4
months.  

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.

Refrigerant type:

R407C

GWP

(1)

 value:

1652.5

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

Maintenance activities  

1

Condenser coil

Remove dust and any other contaminant from the coil fins using
a brush and a blower. Blow from the inside of the unit. Take care
not to bend or damage the fins.

2

Field wiring and power supply

Check the power supply voltage on the local supply panel.
The voltage should correspond to the voltage marked on the
identification label of the unit.

Check the connections and make sure they are properly
fixed.

Check the proper operation of the circuit breaker and the
earth leak detector provided on the local supply panel.

3

Internal wiring of the unit

Visually check the switch box on loose connections (terminals
and components). Make sure that the electrical components are
not damaged or loose.

4

Earth connection

Make sure that the earth wires are still connected properly and
that the earth terminals are tightened.

5

Refrigerant circuit

Check for leaks inside the unit. In case a leak is detected, call
your local Daikin dealer.

Check the working pressure of the unit. Refer to paragraph

"Working pressure" on page 8

  in the chapter “

Switching the

EUWAC unit on

”.

6

Compressor

Check on oil leaks. If there is an oil leak, call your local Daikin
dealer. 

Check for abnormal noises and vibrations. If the compressor
is damaged, call your local Daikin dealer.

7

Condenser fan motor 

Clean the cooling ribs and the cooling grid of the motor.

Check on abnormal noises. If the fan or motor are damaged,
call your local Daikin dealer.

8

Air in/outlet ducts of unit

Clean the inside of the ducting (use a vacuum cleaner, avoid
dirt and dust from entering the condenser coil).

Check if the ducts are properly fixed and do not make contact
with the unit (may cause abnormal noises or vibrations).

Make sure that the flexible connection between the ducts and
the unit is not damaged or perforated. Replace it if
necessary.

9

V-belt transmission of condenser fan motor 
(for 10 units only)

Check that the V-belt is not worn
out. Replace if necessary.

Check the tension of the V-belt.
When the belt is slightly
pressed with the  fingers, the
relaxation of the belt may not
exceed 10 mm. 

10

Water supply

Check if the water connection is still well fixed.

Check the water quality (refer to the chapter “

Installing the

unit

” for specifications of the water quality).

11

Drain disposal

Check the proper functioning of the drain. Make sure that
water evacuates freely. Clean the drain pan and piping
thoroughly.

Disposal requirements

Dismantling of the unit and treatment of the refrigerant, oil and even-
tual other parts, should be done in accordance with the relevant local
and national regulations. 

Before carrying out any maintenance or repair activity,
always switch off the circuit breaker on the supply panel,
remove the fuses or open the protection devices of the
unit. 

Do never clean the unit with water under pressure.

The wiring and power supply must be checked by a
licensed electrician.

Summary of Contents for EUWAC8FZW1

Page 1: ...INSTALLATION AND OPERATION MANUAL EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1 Packaged air cooled water chillers...

Page 2: ...D E F G H I J K L M N O P Q R EUWAC5FZ mm 243 311 243 1345 343 125 765 71 58 629 108 25 796 605 735 578 600 795 EUWAC8FZ mm 163 800 162 1290 267 98 815 71 60 951 111 25 1125 605 288 975 600 1122 EUWAC...

Page 3: ...en i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob u...

Page 4: ...and used for cooling applications only The units are available in 3 standard sizes with nominal cooling capacities ranging from 11 2 to 22 6 kW The EUWAC packaged air cooled water chillers can be comb...

Page 5: ...dboard box and attached on a wooden pallet At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account...

Page 6: ...the water circuit 1 Use clean pipes only 2 Hold the pipe end downwards when removing burrs 3 Cover the pipe end when inserting it through a wall so that no dust and dirt enter WATER CHARGE FLOW AND Q...

Page 7: ...d that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the public sys tem It is the responsibility of the installer or user of the equip me...

Page 8: ...lter installed behind the condenser removes small particles from the refrigerant to prevent blockage of the expansion valve and tubes Thermostatic expansion valve The liquid refrigerant coming from th...

Page 9: ...ter becomes too low in order to prevent freezing of the water during operation When the outlet water temperature returns to normal the protector resets automatically but the controller needs to be res...

Page 10: ...er operation of the drain Pour some water into the drain pan and check whether the water evacuates freely through the drain Water supply Fill the water piping taking into account the minimum water vol...

Page 11: ...9 Consulting actual operational information on page 9 Resetting alarms on page 9 Resetting warnings on page 10 Switching the EUWAC unit on To switch the EUWAC unit on proceed as follows 1 When the on...

Page 12: ...er temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of direct parameters without saving the modified parameter The inlet water t...

Page 13: ...t of direct parameters is accessible by pressing the R key for approximately 5 seconds When scrolling through the list of direct parameters using the A and or Z key the parameters appear in the follow...

Page 14: ...aying the inlet water temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of user parameters without saving the modifications The i...

Page 15: ...t other user parameters before saving the modifications select another user parameter using the A and or Z key and then repeat from instruction 3 onwards 7 To save the modifications press the E key To...

Page 16: ...without saving the modifications The inlet water temperature reappears on the display TROUBLESHOOTING This section provides useful information for diagnosing and correct ing certain troubles which may...

Page 17: ...freely Air flow in the unit too low or outdoor temperature too high Clean the air heat exchanger properly RESET After temperature decrease the thermal protector is reset automatically If the protecto...

Page 18: ...leak is detected call your local Daikin dealer Check the working pressure of the unit Refer to paragraph Working pressure on page 8 in the chapter Switching the EUWAC unit on 6 Compressor Check on oi...

Page 19: ...5 10 5 15 20 15 30 25 40 35 50 C 45 5 Hp 8 Hp 10 Hp General specifications IN OUT IN OUT IN OUT Nominal air flow m3 min 70 70 100 100 125 125 long side W mm 763 341 952 802 1102 938 short side P mm 6...

Page 20: ...ESP External static pressure AF Air flow 1 ESP with pulley closed factory setting 2 ESP with pulley 1 turn open 3 ESP with pulley 2 turns open 4 ESP with pulley 3 turns open 5 ESP with pulley 4 turns...

Page 21: ...4 4 6 7 16 11 10 12 13 6 7 16 11 10 12 13 2 15 4 5 2 15 3 9 8 1 14 9 8 1 14 5 5 M1C P S4LP 6 P S1HP 7 1 3 9 8 5 4 2 10 10 R3T R4T M11F M11F EUWAC5 EUWAC8 10...

Page 22: ...4PW14037 1D Copyright Daikin...

Reviews: