background image

EUWAC5~10FZ

Packaged air-cooled water chillers

4PW14037-1D

Installation and operation manual

10

ei

,

e0

: indicates that the supply voltage is exceedingly low (

EU

) or

exceedingly high (

EO

). In these cases contact a licensed

electrician,

fl

: indicates that there was no water flow either during the

period of 15 seconds after the pump was started or for 5
seconds while the compressor is active,

h1

: indicates that a high pressure switch, the discharge

thermal protection or the overcurrent protection of the
compressor motor is activated, 

l1

: indicates that the low pressure switch is activated. 

To reset an alarm, proceed as follows:

1

Press the 

key to acknowledge the alarm.

The buzzer is de-activated.

2

Find the cause of shutdown and correct.

Refer to the chapter 

"Troubleshooting" on page 13

.

3

If the alarm codes 

a1

f l

h1

 or 

l1

 appear on the display, reset

the alarm manually by pressing the 

and 

key

simultaneously for approximately 5 seconds.

In all other cases the alarm is reset automatically.
Once the alarm is reset, the error code no longer appears on the
display. The controller continues its normal operation, displaying
the inlet water temperature.

Resetting warnings

During normal operation, the display of the controller may start flash-
ing, alternately showing the inlet water temperature and the following
warning code:

n1

: indicates that the compressor requires maintenance: the

total running hours of the compressor (direct parameter

c9

) has exceeded the setting of the timer threshold for

maintenance warning (user parameter 

cb

).

To reset the maintenance warning 

n1

, proceed as follows:

1

Enter the list of direct parameters by pressing the 

key for

approximately 5 seconds.

The parameter code 

r1

 appears on the display.

2

Select parameter code 

c9

 using the 

and/or 

key.

3

Press the 

key to switch to the parameter value.

4

Press the 

and 

keys simultaneously for approximately

5 seconds.

The timer's value becomes 

0

5

Press the 

key to return to parameter code 

c9

.

6

Press the 

key to return to normal operation. 

Advanced features of the digital controller

This chapter gives an overview of the direct parameters and user
parameters provided by the controller. In the following chapter, you
will learn how you can set up and configure the EUWAC unit using
these parameters.

Overview of the direct parameters

The list of direct parameters is accessible by pressing the 

key for

approximately 5 seconds.

When scrolling through the list of direct parameters using the 

and/

or 

key, the parameters appear in the following order:

r1

: to define the cooling temperature setpoint,

r2

: to define the cooling temperature difference,

r6

: to check the outlet water temperature,

c9

: to check the total running hours of the compressor,

cv

: to check the total running hours of the pump.

Overview of the user parameters

The list of user parameters is only accessible by means of the user
password. When scrolling through the list of parameters using the 

A

and/or 

key, you see the direct parameters and user parameters.

The user parameters appear in the following order:

:d

: to define the measurement unit (°C or °F),

c7

: to define the time delay between the pump startup and

the compressor startup,

c8

: to define the time delay between the unit shutdown and

the pump shutdown,

cb

: to define the timer threshold for maintenance warning,

p4

: to disable the buzzer or to define the activation period of

the buzzer in case of an alarm,

h7

: to activate or de-activate the remote on/off control,

h9

: to lock or unlock the controller keyboard,

ha

: to define the unit's serial address,

hb

,

c6

: not used.

Tasks carried out using direct parameters

Entering the list of direct parameters

1

Press the 

key for approximately 5 seconds.

The controller enters the list of direct parameters, displaying
parameter code 

r1

.

Defining the cooling temperature difference

To  control the cooling load, the unit is equipped with a single-step
thermostat. The thermostat's “cooling temperature difference” can be
modified by means of direct parameter 

r2

. The default, limit and step

values are:

Default value

3

.

0

°C

Limit values

0

.

3

 to 

19

.

9

°C

Step value

0

.

1

°C

NOTE

If the alarm codes 

fl 

 and 

h1

  are flashing alternately,

the alarm is most probably caused by the reverse
phase protector.

NOTE

Do not forget to carry out the required maintenance
activities after resetting the timers.

Besides resetting timer 

c9

 (running hours of the com-

pressor), it is also possible to reset timer 

cv

  which

defines the total running hours of the pump. To do this,
consult the timer's value (refer to paragraph

"Consulting actual operational information" on page 9

)

and press the 

and 

keys simultaneously for

approximately 5 seconds while the timer's value is dis-
played. The timer's value becomes 

0

.  Then succes-

sively press the 

key  and the 

key  to return to

normal operation.

12

°C

15

°C

compressor

inlet water temperature

ON

OFF

Summary of Contents for EUWAC8FZW1

Page 1: ...INSTALLATION AND OPERATION MANUAL EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1 Packaged air cooled water chillers...

Page 2: ...D E F G H I J K L M N O P Q R EUWAC5FZ mm 243 311 243 1345 343 125 765 71 58 629 108 25 796 605 735 578 600 795 EUWAC8FZ mm 163 800 162 1290 267 98 815 71 60 951 111 25 1125 605 288 975 600 1122 EUWAC...

Page 3: ...en i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob u...

Page 4: ...and used for cooling applications only The units are available in 3 standard sizes with nominal cooling capacities ranging from 11 2 to 22 6 kW The EUWAC packaged air cooled water chillers can be comb...

Page 5: ...dboard box and attached on a wooden pallet At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account...

Page 6: ...the water circuit 1 Use clean pipes only 2 Hold the pipe end downwards when removing burrs 3 Cover the pipe end when inserting it through a wall so that no dust and dirt enter WATER CHARGE FLOW AND Q...

Page 7: ...d that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the public sys tem It is the responsibility of the installer or user of the equip me...

Page 8: ...lter installed behind the condenser removes small particles from the refrigerant to prevent blockage of the expansion valve and tubes Thermostatic expansion valve The liquid refrigerant coming from th...

Page 9: ...ter becomes too low in order to prevent freezing of the water during operation When the outlet water temperature returns to normal the protector resets automatically but the controller needs to be res...

Page 10: ...er operation of the drain Pour some water into the drain pan and check whether the water evacuates freely through the drain Water supply Fill the water piping taking into account the minimum water vol...

Page 11: ...9 Consulting actual operational information on page 9 Resetting alarms on page 9 Resetting warnings on page 10 Switching the EUWAC unit on To switch the EUWAC unit on proceed as follows 1 When the on...

Page 12: ...er temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of direct parameters without saving the modified parameter The inlet water t...

Page 13: ...t of direct parameters is accessible by pressing the R key for approximately 5 seconds When scrolling through the list of direct parameters using the A and or Z key the parameters appear in the follow...

Page 14: ...aying the inlet water temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of user parameters without saving the modifications The i...

Page 15: ...t other user parameters before saving the modifications select another user parameter using the A and or Z key and then repeat from instruction 3 onwards 7 To save the modifications press the E key To...

Page 16: ...without saving the modifications The inlet water temperature reappears on the display TROUBLESHOOTING This section provides useful information for diagnosing and correct ing certain troubles which may...

Page 17: ...freely Air flow in the unit too low or outdoor temperature too high Clean the air heat exchanger properly RESET After temperature decrease the thermal protector is reset automatically If the protecto...

Page 18: ...leak is detected call your local Daikin dealer Check the working pressure of the unit Refer to paragraph Working pressure on page 8 in the chapter Switching the EUWAC unit on 6 Compressor Check on oi...

Page 19: ...5 10 5 15 20 15 30 25 40 35 50 C 45 5 Hp 8 Hp 10 Hp General specifications IN OUT IN OUT IN OUT Nominal air flow m3 min 70 70 100 100 125 125 long side W mm 763 341 952 802 1102 938 short side P mm 6...

Page 20: ...ESP External static pressure AF Air flow 1 ESP with pulley closed factory setting 2 ESP with pulley 1 turn open 3 ESP with pulley 2 turns open 4 ESP with pulley 3 turns open 5 ESP with pulley 4 turns...

Page 21: ...4 4 6 7 16 11 10 12 13 6 7 16 11 10 12 13 2 15 4 5 2 15 3 9 8 1 14 9 8 1 14 5 5 M1C P S4LP 6 P S1HP 7 1 3 9 8 5 4 2 10 10 R3T R4T M11F M11F EUWAC5 EUWAC8 10...

Page 22: ...4PW14037 1D Copyright Daikin...

Reviews: