ESIE11-02
General Outline
1–31
3
1
4
5
1.11
Electrical Specifications: EUWA*5-8KBZW1
Electrical
specifications
The table below contains the electrical specifications
(1)
.
Model
EUWAN5KBZW1 EUWAP5KBZW1 EUWAB5KBZW1 EUWAN8KBZW1 EUWAP8KBZW1 EUWAB8KBZW1
Power supply
Phase
3N~
Frequency
50 Hz
Voltage
400 V
Voltage tolerance
± 10 %
Unit
Starting current
62.2 A
63.5 A
97.9 A
99.2 A
Nominal running
current
7.7 A
9.0 A
13.6 A
14.9 A
Max. running
current
11.2 A
12.5 A
16.9 A
18.2 A
Recommended
fuses
3 x 20 gL/gG
3 x 20 gL/gG
3 x 25 gL/gG
3 x 25 gL/gG
Fans
Phase
1~
Voltage
230 V
Max. running
current
2.2 A
2.9 A
Compressor
Phase
3~
Voltage
400 V
Starting current
60.0 A
95 A
Nom. running
current
5.5 A
10.7 A
Max. running
current
9.0 A
14 A
Starting method
Direct on line
Control circuit
Phase
1~
Voltage
230 V
Recommended
fuses
Factory installed
Pump
Phase
__
3~
__
3~
Voltage
__
400.0 V
__
400.0 V
Max. running
current
__
1.3 A
__
1.3 A
Summary of Contents for EUWY 24KBZW1 Series
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...