D-EIMAC00208-16EU - 13/192
Figure 2 - Operating limits
Safety
The unit must be firmly secured to the soil.
It is essential to observe the following instructions:
The unit can only be lifted using the lifting points marked
in yellow fixed to its base.
It is forbidden to access the electrical components without
having opened the unit main switch and switched off the
power supply.
It is forbidden to access the electrical components without
using an insulating platform. Do not access the electrical
components if water and/or moisture are present.
Sharp edges and the surface of the condenser section
could cause injury. Avoid direct contact and use adeguate
protection device
Switch off power supply, by opening the main switch,
before servicing the cooling fans and/or compressors.
Failure to observe this rule could result in serious
personal injury.
Do not introduce solid objects into the water pipes while
the unit is connected to the system.
A mechanical filter must be installed on the water pipe
connected to the heat exchanger inlet.
The unit is supplied with safety valves, that are installed
both on the high-pressure and on the low-pressure sides
of the refrigerant circuit.
It is absolutely forbidden to remove all protections of
moving parts.
In case of sudden stop of the unit, follow the instructions on the
Control Panel Operating Manual
which is part of the on-
board documentation delivered to the end user.
It is strongly recommended to perform installation and
maintenance with other people. In case of accidental injury or
unease, it is necessary to:
-
keep calm
-
press the alarm button if present in the installation site
-
move the injured person in a warm place far from the unit
and in rest position
-
contact immediately emergency rescue personnel of the
building or the Health Emergency Service
-
wait without leaving the injured person alone until the
rescue operators come
-
give all necessary information to the the rescue operators
Avoid installing the chiller in areas that could be
dangerous during maintenance operations, such as
platforms without parapets or railings or areas not
complying with the clearance requirements around the
chiller.
Noise
The unit is a source of noise mainly due to rotation of
compressors and fans.
The noise level for each model size is listed in sales
documentation.
If the unit is correctly installed, operated and manteined the
noise emission level do not require any special protection
device to operate continuosly close to the unit without any risk.
In case of installation with special noise requirements it could
be necessary to install additional sound attenuation devices.
Moving and lifting
Avoid bumping and/or jolting during loading/unloading unit
from the truck and moving it. Do not push or pull the unit from
any part other than the base frame. Secure the unit inside the
truck to prevent it from moving and causing damages. Do not
allow any part of the unit to fall during transportation or
loading/unloading.
All units of the are supplied with lifting points marked in yellow.
Only these points may be used for lifting the unit, as shown in
the following Figure 3.
Both the lifting ropes and the spacing bars must be
strong enough to support the unit safely. Please check
the unit’s weight on the unit nameplate.
The unit must be lifted with the utmost attention and care
following lifting label instructions; lift unit very slowly, keeping it
perfectly level..
Positioning and assembly
All units are designed for installation outdoors, either on
balconies or on the ground, provided that the installation area
is free of obstacles that could reduce air flow to the
condensers coil.
Evap Leaving Water Temperature (°C)
A
m
b
ie
n
t
T
e
m
p
e
ra
tu
re
(
°C
)
Speedtroll required
(below -10°C Amb.)
Fan Speed Modulation
required
(below 18°C Amb. Temp
for less than 3 fans units,
below 10°C for 3 or more
fans units)
COMP FULL LOAD ONLY
Above this line
(ICE Mode)
Operation with Glycol
(below 4°C Evap LWT)
Summary of Contents for EWAD-D-H 200
Page 3: ...D EIMAC00208 16EU 3 192 A B...
Page 8: ...D EIMAC00208 16EU 8 192 A B...
Page 66: ...D EIMAC00208 16EU 66 192 chiller chiller Carnot DOC 20 57 95 1 1 6 2 7 3 8 4 9 5...
Page 67: ...D EIMAC00208 16EU 67 152 2 chiller chiller 3Figure 3 C C Speedtroll 10 C 18 C 3 10 C 3 ICE 4 C...
Page 69: ...D EIMAC00208 16EU 69 192 4 7 8 25 C 9 10...
Page 74: ...EIMAC00208 16EU 74 192...
Page 84: ...D EIMAC00208 16EU 84 192 20 C 57 95 1 1 6 2 7 3 8 4 9 5...
Page 85: ...D EIMAC00208 16EU 85 192 2 3Figure 3 C C Speedtroll 10 C 18 C 3 10 C 3 ICE 4 C...
Page 86: ...D EIMAC00208 16EU 86 192 3 250 2500 3000 3600 1 2 3 4 5 6 2355 4 0 0 0 2400 2234 L...
Page 87: ...D EIMAC00208 16EU 87 192 4 7 8 25 C 9 10 11 12...
Page 91: ...EIMAC00208 16EU 91 192 1 1 2 3 1 2 3 x 1000 a b c d e f g h CO2 m n GWP p 2 CO2 x 1000...
Page 92: ...EIMAC00208 16EU 92 192 4 3...
Page 174: ...D EIMAC00208 16EU 174 192 DOC 20 C 57 C 95 1 1 6 2 7 3 8 4 9 5...
Page 175: ...D EIMAC00208 16EU 175 162 2 3Figure3 C Temperatura ambiente C 10 C 18 C 3 10 C 3 ICE 4 C...
Page 176: ...D EIMAC00208 16EU 176 192 3 250 2500 3000 3600 1 2 3 4 5 6 2355 4 0 0 0 2400 2234 L...
Page 177: ...D EIMAC00208 16EU 177 192 4 7 8 25 C 9 10 11 12...
Page 181: ...EIMAC00208 16EU 181 192 1 1 2 3 1 2 3 1000 CO2 2 CO2 1000...
Page 182: ...EIMAC00208 16EU 182 192 Intergovernmental Panel on Climate Change IPCC IPCC...