D-EIMAC00208-16EU - 18/192
Periodic obligatory checks and starting up of
appliances under pressure
The units are included in category IV of the classification
established by the European Directive PED 2014/68/EU.
For chillers belonging to this category, some local regulations
require a periodic inspection by an authorized agency. Please
check with your local requirements.
Table 2 - Routine maintenance programme
List of Activities
Weekly
Monthly
(Note 1)
Yearly/Seas
onal
(Note 2)
General:
Reading of operating data (Note 3)
X
Visual inspection of unit for any damage and/or loosening
X
Verification of thermal insulation integrity
X
Clean and paint where necessary
X
Analysis of water (6)
X
Check of flow switch operation
X
Electrical:
Verification of control sequence
X
Verify contactor wear
– Replace if necessary
X
Verify that all electrical terminals are tight
– Tighten if necessary
X
Clean inside the electrical control board
X
Visual inspection of components for any signs of overheating
X
Verify operation of compressor and electrical resistance
X
Measure compressor motor insulation using the Megger
X
Refrigeration circuit:
Check for any refrigerant leakage
X
Verify refrigerant flow using the liquid sight glass
– Sight glass full
X
Verify filter dryer pressure drop
X
Verify oil filter pressure drop (Note 5)
X
Analyse compressor vibrations
X
Analyse compressor oil acidity (7)
X
Condenser section:
Clean condenser banks (Note 4)
X
Verify that fans are well tightened
X
Verify condenser bank fins
– Comb if necessary
X
Notes:
1.
Monthly activities include all the weekly ones.
2.
The annual (or early season) activities include all weekly and monthly activities.
3.
Unit operating values should be read on a daily basis thus keeping high observation standards.
4.
In environments with a high concentration of air-borne particles, it might be necessary to clean the condenser bank more often.
5.
Replace the oil filter when the pressure drop across it reaches 2.0 bar.
6.
Check for any dissolved metals.
7.
TAN (Total Acid Number) :
0,10 : No action
Between 0.10 and 0.19 : Replace anti-acid filters and re-check after 1000 running hours. Continue to replace filters
until the TAN is lower than 0.10.
0,19 : Replace oil, oil filter and filter dryer. Verify at regular intervals.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases
. Do not vent gases into the atmosphere.
Refrigerant type:
R134a
GWP(1) value:
1430
(1)GWP =
Global Warming Potential
The refrigerant quantity necessary for standard operation is indicated on the unit name plate.
Real refrigerant quantity charged in the unit is listed on a silver sticker inside the electrical panel.
Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
Please contact your local dealer for more information.
Summary of Contents for EWAD-D-H 200
Page 3: ...D EIMAC00208 16EU 3 192 A B...
Page 8: ...D EIMAC00208 16EU 8 192 A B...
Page 66: ...D EIMAC00208 16EU 66 192 chiller chiller Carnot DOC 20 57 95 1 1 6 2 7 3 8 4 9 5...
Page 67: ...D EIMAC00208 16EU 67 152 2 chiller chiller 3Figure 3 C C Speedtroll 10 C 18 C 3 10 C 3 ICE 4 C...
Page 69: ...D EIMAC00208 16EU 69 192 4 7 8 25 C 9 10...
Page 74: ...EIMAC00208 16EU 74 192...
Page 84: ...D EIMAC00208 16EU 84 192 20 C 57 95 1 1 6 2 7 3 8 4 9 5...
Page 85: ...D EIMAC00208 16EU 85 192 2 3Figure 3 C C Speedtroll 10 C 18 C 3 10 C 3 ICE 4 C...
Page 86: ...D EIMAC00208 16EU 86 192 3 250 2500 3000 3600 1 2 3 4 5 6 2355 4 0 0 0 2400 2234 L...
Page 87: ...D EIMAC00208 16EU 87 192 4 7 8 25 C 9 10 11 12...
Page 91: ...EIMAC00208 16EU 91 192 1 1 2 3 1 2 3 x 1000 a b c d e f g h CO2 m n GWP p 2 CO2 x 1000...
Page 92: ...EIMAC00208 16EU 92 192 4 3...
Page 174: ...D EIMAC00208 16EU 174 192 DOC 20 C 57 C 95 1 1 6 2 7 3 8 4 9 5...
Page 175: ...D EIMAC00208 16EU 175 162 2 3Figure3 C Temperatura ambiente C 10 C 18 C 3 10 C 3 ICE 4 C...
Page 176: ...D EIMAC00208 16EU 176 192 3 250 2500 3000 3600 1 2 3 4 5 6 2355 4 0 0 0 2400 2234 L...
Page 177: ...D EIMAC00208 16EU 177 192 4 7 8 25 C 9 10 11 12...
Page 181: ...EIMAC00208 16EU 181 192 1 1 2 3 1 2 3 1000 CO2 2 CO2 1000...
Page 182: ...EIMAC00208 16EU 182 192 Intergovernmental Panel on Climate Change IPCC IPCC...