D
–EIMAC00708-16EN - 17/76
Operating limits
Storing
The environment conditions have to be in the following limits:
Minimum ambient temperature : -20°C
Maximum ambient temperature
:
57°C
Maximum R.H.
:
95% not condensing
ATTENTION
Storing below the minimum temperature above mentioned may cause damage to components such as the electronic
controller and its LCD display.
WARNING
Storing above the maximum temperature cause opening of the safety valves on the compressors
’ suction line.
ATTENTION
Storing in condensing atmosphere may damage the electronic components.
Operation
Operation is allowed within the limits mentioned in the following diagrams.
ATTENTION
Operation out of the mentioned limits may damage the unit.
For any doubts contact the factory.