Operation manual
19
EWAD120~340MBYNN
Packaged air-cooled water chillers
4PW22683-1
A
NNEX
III
Floating setpoint working
The diagram and table below show the default value and the upper
and lower limits of the floating setpoint parameters on the evaporator.
A
NNEX
IV
Free cooling working
Free cooling on ambient temperature
Free cooling on difference between inlet water evaporator
temperature and ambient temperature
Floating setpoint
Default value
Lower limit
Upper limit
Maximum value
(°C)
3.0
0.0
5.0
D1
(°C)
20.0
20.0
43.0
D2
(a)
(a) rise in floating setpoint value for 10°C drop in ambient
(°C)
5.0
0.0
10.0
0
°
C
5
°
C
D2
D1
Max, value
Ambient
Free cooling
default
minimum
maximum
SP
(°C)
5
-30
25
DI
(°C)
2
1
5
Free cooling
default
minimum
maximum
SP
(°C)
5
1
20
DI
(°C)
2
1
5
DI
SP
°
C
free cooling state
ambient temperature
ON
OFF
DI
SP
°
C
free cooling state
ON
OFF
inlet water evaporator temperature
minus ambient temperature