background image

EWAD120~340MBYNN

Packaged air-cooled water chillers

4PW22683-1

Operation manual

4

Fan motor thermal protector (part safety devices)
The condenser fan motors are equipped with thermal protectors
(Q*F). The protectors are activated when the temperature
becomes too high. When temperature returns to normal, the
protectors reset automatically.

Flowswitch (general safety devices)
The unit is protected by a flowswitch (S8L).
When the water flow becomes lower than the minimum allowed
water flow, the flowswitch shuts down the unit. When the water
flow becomes normal, the protection resets automatically but the
controller still needs to be reset manually.

Discharge thermal protectors (circuit safety devices)
The unit is equipped with discharge thermal protectors (S*T).
The protectors are activated when the temperature of the
refrigerant leaving the compressor becomes too high. When the
temperature returns to normal the protector resets automatically
and the controller needs to be reset manually.

Freeze-up protection (general safety devices)
The freeze-up protection  prevents the water in the evaporator
from freezing during operation. When the outlet water
temperature is too low, the controller shuts down the unit.  When
the outlet water temperature returns to normal, the controller
needs to be reset manually.

Low pressure safety (circuit safety devices)
When the suction pressure of a circuit is too low, the circuit
controller shuts down the circuit. When the pressure returns to
normal, the safety device can be reset on the controller.

Pressure relief safety valve (general safety devices)
The safety valve is activated when the pressure in the refrigerant
circuit becomes too high. If this occurs, shut down the unit and
contact your local dealer.

High pressure switch (circuit safety devices)
Each circuit is protected by two high pressure switches (S*PH)
which measure the condenser pressure (pressure at the outlet
of the compressor). They are installed in the compressor
housing of the circuit. When the pressure becomes too high, the
pressure switches are activated and the circuit stops. 
The switches are factory-set and may not be adjusted. When
activated, they must be reset by means of a screwdriver. The
controller still needs to be reset.

Reverse phase protector (circuit safety devices)
The reverse phase protectors (R*P) prevent the screw
compressors from running in the wrong direction. If the
compressors do not start, two phases of the power supply must
be inverted.

Internal wiring - Parts table

Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:

A1,A2..........** ....... Current transfo/A-meter for circuit 1, circuit 2

A1P........................ PCB controller

A11P...................... Expansion board controller 

(only for EWAD240~340)

B1P,B4P................. Low pressure transmitter for circuit 1, circuit 2

B2P,B5P................. High pressure transmitter for circuit 1, circuit 2

C1~C3 ................... Capacitor

E1HC,E2HC .......... Crankcase heater compressor circuit 1, circuit 2

E3H,E4H................ Evaporator heater circuit 1, circuit 2

F1U~F3U

.......# ........ Main fuses

F4U,F5U .....# ........ Fuses for evaporator heater

F6B ........................ Fuse for primary of TR1

F7B ........................ Fuse for secondary of TR1

F8U........................ Surge proof fuse of TR1

F9B ........................ Fuse for secondary of TR2

F10S,F11S ............ Circuit breakers with fuses for circuit 1, circuit 2

(only for EWAD240~340)

F12B,F13B ............ Autofuse for fanmotors circuit 1, circuit 2

H1P ............ * ......... Indication lamp general operation

H2P ............ * ......... Indication lamp alarm

H3P,H4P..... * ......... Indication lamp operation compressor 1, 

compressor 2

H5P ............ * ......... Changeable output

J1 ........................... Power supply

J2,J3,J6.................. Analog input

J4 ........................... Analog output

J5,J7,J8,J19........... Digital input

J11,J23 .................. RS485 connection

J12~J18,J21,J22.... Digital output

K1A,K4A ................ Auxiliary relay for safeties circuit 1, circuit 2

K2A,K5A ................ Auxiliary relay compressor thermal protector 

circuit 1, circuit 2

K3A,K6A ................ Auxiliary relay for discharge thermal protector 

circuit 1, circuit 2

K7A,K8A ................ Auxiliary relay for safety high pressure circuit 1, 

circuit 2

K1M,K4M ............... Linecontactor for circuit 1, circuit 2

K2M,K5M ............... Deltacontactor for circuit 1, circuit 2

K3M,K6M ............... Starcontactor for circuit 1, circuit 2

K7F,K10F ............... Fancontactor for circuit 1, circuit 2

K8F,K11F ............... Fancontactor for circuit 1, circuit 2

K9F,K12F ............... Fancontactor for circuit 1, circuit 2

K17S,K18S ............ Overcurrent relay for circuit 1, circuit 2

L1,L2,L3 ................. Main supply terminals

M1C,M2C ............... Compressor motors circuit 1, circuit 2

M1S,M2S ............... Stepless capacity control for compressor 

circuit 1, circuit 2

M11F-M14F ........... Fan motors circuit 1

M21F-M24F ........... Fan motors circuit 2

PE .......................... Main earth terminal

Q1M,Q2M .............. Thermal protector compressor motor circuit 1, 

circuit 2

Q11F-Q14F............ Thermal protectors fan motors circuit 1

Q21F-Q24F............ Thermal protectors fan motors circuit 2

R1,R2..................... Auxiliary resistance for feedback

R1F,R2F ................. Feedback resistance fot circuit 1, circuit 2

R1P,R2P................. Reverse phase protector circuit 1, circuit 2

R3T ........................ Sensor for evaporator inlet water temperature

R4T ........................ Sensor for evaporator outlet water temperature

(only for EWAD120~170)

R5T ........................ Sensor for ambient temperature

R7T ........................ Sensor for mixed outlet water temperature 

(only for EWAD240~340)

R8T ........................ Sensor for common leaving water in a DICN 

system

S1PH,S2PH ........... High pressure switch circuit 1, circuit 2

S3T,S4T ................. Discharge thermal protector circuit 1, circuit 2

S5E ........................ Emergency stop push button

S6S ............ * ......... Changeable switch for remote function 

(e.g. remote start/stop)

S8L......................... Flowswitch

S9L............. #......... Contact that closes if the pump is working

S10S .......... * ......... Changeable switch for remote function 

(e.g. dual setpoint)

S11S .......... * ......... Changeable switch for remote function

(e.g. enable/disable capacity limitation 1)

S12S .......... * ......... Changeable switch for remote function

(e.g. enable/disable capacity limitation 2)

S13S .......... ##....... Main isolator switch

Summary of Contents for EWAD120MBYNN1

Page 1: ...OPERATION MANUAL EWAD120MBYNN1 EWAD150MBYNN1 EWAD170MBYNN1 EWAD240MBYNN1 EWAD300MBYNN1 EWAD340MBYNN1 Packaged air cooled water chillers...

Page 2: ...e that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start up on pag...

Page 3: ...rge evaporator 19 Field wiring intake 2 Condenser 11 Leaving water temperature sensor R4T 20 Main isolator switch optional S13S 3 Compressor 1 M1C 12 Entering water temperature sensor R3T 21 Compresso...

Page 4: ...the evaporator of the unit against freezing when there is no waterflow or when the waterflow is too low Safety devices The unit is equipped with three kinds of safety device 1 General safety devices...

Page 5: ...ntroller A11P Expansion board controller only for EWAD240 340 B1P B4P Low pressure transmitter for circuit 1 circuit 2 B2P B5P High pressure transmitter for circuit 1 circuit 2 C1 C3 Capacitor E1HC E2...

Page 6: ...ted by paper sheets cardboard or any other material 12 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification...

Page 7: ...with the everyday usage of the unit Here you will find how to perform routine tasks such as Setting the language on page 6 Switching the unit on on page 7 Consulting actual operational information on...

Page 8: ...rs menu on page 9 the circuit is ready to start up when extra cooling load is needed The preceding OFF messages are written down in order of priority If one of the timers is busy and one of the safeti...

Page 9: ...ll function as stand alone units If a slave unit can not be found by the network the red light inside the p key of the master lights up and the buzzer inside the control is activated If the master can...

Page 10: ...atus To consult information about the pressures of circuit 1 To consult information about the pressures of circuit 2 only for EWAD240 340 To consult actual operational informa tion about the ambient t...

Page 11: ...f the compressors at the moment of shutdown To check which were the pressures of the circuit 1 at the moment of shutdown To check which were the pressures of the circuit 2 at the moment of shutdown on...

Page 12: ...e cooling capacity However the thermostat parameters are not fixed and can be modified via the screen of the user settings menu The default limit and step values for the thermostat parameters are show...

Page 13: ...ating setpoint is altered based on the ambient temperature 4 used to define maximum value that can be added to the active setpoint used to define the ambient source at which the floating setpoint valu...

Page 14: ...tep change has occurred During the countdown the unit will not be able to go to a lower thermo stat step FLOWSTART 15 sec counts down when the waterflow through the evaporator is continuous and the un...

Page 15: ...to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the next screen This screen contains information about the controller s...

Page 16: ...devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer Symptom 1 The unit does not start but the ON LED lights...

Page 17: ...sed electrician RESET After pressure decrease push the button on the high pressure switch and reset the controller Symptom 5 4 Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION Mech...

Page 18: ...ck the water quality refer to the installation manual of the unit for specifications of the water quality Waterfilters Make sure to clean the waterfilter in front of the evaporator water inlet once ev...

Page 19: ...ngs in group 1 all Wednesdays will work according to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settin...

Page 20: ...tween inlet water evaporator temperature and ambient temperature Floating setpoint Default value Lower limit Upper limit Maximum value C 3 0 0 0 5 0 D1 C 20 0 20 0 43 0 D2 a a rise in floating setpoin...

Page 21: ...h h g h g h 0 1 2 0 1 g h g h g h g h g h g h g h g h g h g g h g h g h g h g h h g g 5 f 2 7 7 g h 7 7 5 7 7 7 7 7 7 7 7 7 7 3 7 7 7 7 g h g h g h 5 0 1 2 0 1 5 5 5 0 1 2 0 1 5 5 q h h g q h g h g h...

Page 22: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22683 1...

Reviews: