background image

Operation manual

5

EWAD120~340MBYNN

Packaged air-cooled water chillers

4PW22683-1

S14PH,S15PH .......High pressure switch circuit 1, circuit 2

TC01~TC04............Optocoupler (analog to digital signal)

TR1 ........................Transfo control circuit

TR2 ........................Transfo supply cont digital inputs

V1............... ** ........V-meter for circuit 1 (and for circuit 2)

Y11S,Y21S.............12% capacity step for compressor circuit 1, 

circuit 2

Y15S,Y25S.............Liquid injection valve of the compressor circuit 1, 

circuit 2

Y16S,Y26S.............Liquid line solenoid valve circuit 1, circuit 2

B

EFORE

 

OPERATION

Checks before initial start-up

After the installation of the unit, check the following before switching
on the circuit breaker:

1

Field wiring

Make sure that the field wiring between the local supply panel
and the unit has been carried out according to the instructions
described in the installation manual, according to the wiring
diagrams and according to European and national regulations.

2

Additional pump interlock contact

Additional interlock contacts (S*L) should be provided (e.g.
flowswitch, contact of pump motor contactor). Make sure that
they have been installed between the appropriate terminals
(refer to the wiring diagram supplied with the unit). They should
be  normal open contacts.

3

Fuses or protection devices

Check that the fuses or the locally installed protection devices
are of the size and type specified in the installation manual.
Make sure that neither a fuse nor a protection device has been
bypassed.

4

Earth wiring

Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.

5

Internal wiring

Visually check the switch box on loose connections or damaged
electrical components.

6

Fixation

Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.

7

Damaged equipment

Check the inside of the unit on damaged components or
squeezed pipes.

8

Refrigerant leak

Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local dealer.

9

Oil leak

Check the compressor on oil leakage. If there is an oil leak, call
your local dealer.

10

Stop valves

Open the liquid line, discharge and suction (if provided)
stopvalves completely.

11

Air inlet/outlet

Check that the air inlet and outlet of the unit is not obstructed by
paper sheets, cardboard, or any other material.

12

Power supply voltage

Check the power supply voltage on the local supply panel. The
voltage should correspond to the voltage on the identification
label of the unit.

13

Water connection

Check water piping system and circulating pumps.
Check if a water filter is installed correctly in front of the
evaporator water inlet.

Water supply

Fill the water piping, taking into account the minimum water volume
required by the unit. Refer to the "installation manual".

Make sure that the water is of the quality as mentioned in the
installation manual.

Purge the air at the high points of the system and check the operation
of the circulation pump and the flowswitch.

Power supply connection and crankcase heating

To switch on the crankcase heater proceed as follows:

1

Switch on the circuit breaker on the local supply panel. Make
sure that the unit is 

"

OFF

"

.

2

The crankcase heater is switched on automatically.

3

Check the supply voltage on the supply terminals L1, L2, L3,  by
means of a voltmeter. The voltage must correspond to the
voltage indicated on the identification label of the unit. If the
voltmeter reads values which are not within the ranges specified
in the technical data, check the field wiring and replace the
supply cables if necessary.

4

Check the LED on the reverse phase protectors. If it lights up,
the phase order is correct. If not, switch off the circuit breaker
and call a licensed electrician to connect the wires of the power
supply cable in the correct phase order.

5

Check if the crankcaseheaters are warming up.

After 8 hours, the unit is ready for operation.

General recommendations

Before switching on the unit, read following recommendations:

1

When the complete installation and all necessary settings have
been carried out, close all front panels of the unit.

2

The service panels of the switch boxes may only be opened by a
licensed electrician for maintenance purposes.

3

To prevent the evaporator from freezing and to avoid damage to
the LCD displays of the digital controller, never switch off the
power supply during winter.

Not included with standard unit

Not possible as option

Possible as option

Obligatory

#

##

Not obligatory

*

**

Make sure that the circuit breaker on the power supply
panel of the unit is switched off.

In order to avoid compressor damage, it is necessary to
switch on the crankcase heater for at least 8 hours before
starting the compressor after a long period of standstill.

Summary of Contents for EWAD120MBYNN1

Page 1: ...OPERATION MANUAL EWAD120MBYNN1 EWAD150MBYNN1 EWAD170MBYNN1 EWAD240MBYNN1 EWAD300MBYNN1 EWAD340MBYNN1 Packaged air cooled water chillers...

Page 2: ...e that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start up on pag...

Page 3: ...rge evaporator 19 Field wiring intake 2 Condenser 11 Leaving water temperature sensor R4T 20 Main isolator switch optional S13S 3 Compressor 1 M1C 12 Entering water temperature sensor R3T 21 Compresso...

Page 4: ...the evaporator of the unit against freezing when there is no waterflow or when the waterflow is too low Safety devices The unit is equipped with three kinds of safety device 1 General safety devices...

Page 5: ...ntroller A11P Expansion board controller only for EWAD240 340 B1P B4P Low pressure transmitter for circuit 1 circuit 2 B2P B5P High pressure transmitter for circuit 1 circuit 2 C1 C3 Capacitor E1HC E2...

Page 6: ...ted by paper sheets cardboard or any other material 12 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification...

Page 7: ...with the everyday usage of the unit Here you will find how to perform routine tasks such as Setting the language on page 6 Switching the unit on on page 7 Consulting actual operational information on...

Page 8: ...rs menu on page 9 the circuit is ready to start up when extra cooling load is needed The preceding OFF messages are written down in order of priority If one of the timers is busy and one of the safeti...

Page 9: ...ll function as stand alone units If a slave unit can not be found by the network the red light inside the p key of the master lights up and the buzzer inside the control is activated If the master can...

Page 10: ...atus To consult information about the pressures of circuit 1 To consult information about the pressures of circuit 2 only for EWAD240 340 To consult actual operational informa tion about the ambient t...

Page 11: ...f the compressors at the moment of shutdown To check which were the pressures of the circuit 1 at the moment of shutdown To check which were the pressures of the circuit 2 at the moment of shutdown on...

Page 12: ...e cooling capacity However the thermostat parameters are not fixed and can be modified via the screen of the user settings menu The default limit and step values for the thermostat parameters are show...

Page 13: ...ating setpoint is altered based on the ambient temperature 4 used to define maximum value that can be added to the active setpoint used to define the ambient source at which the floating setpoint valu...

Page 14: ...tep change has occurred During the countdown the unit will not be able to go to a lower thermo stat step FLOWSTART 15 sec counts down when the waterflow through the evaporator is continuous and the un...

Page 15: ...to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the next screen This screen contains information about the controller s...

Page 16: ...devices may be bridged or changed to a value other than the factory setting If the cause of the problem cannot be found call your local dealer Symptom 1 The unit does not start but the ON LED lights...

Page 17: ...sed electrician RESET After pressure decrease push the button on the high pressure switch and reset the controller Symptom 5 4 Fan thermal protector is activated POSSIBLE CAUSES CORRECTIVE ACTION Mech...

Page 18: ...ck the water quality refer to the installation manual of the unit for specifications of the water quality Waterfilters Make sure to clean the waterfilter in front of the evaporator water inlet once ev...

Page 19: ...ngs in group 1 all Wednesdays will work according to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settin...

Page 20: ...tween inlet water evaporator temperature and ambient temperature Floating setpoint Default value Lower limit Upper limit Maximum value C 3 0 0 0 5 0 D1 C 20 0 20 0 43 0 D2 a a rise in floating setpoin...

Page 21: ...h h g h g h 0 1 2 0 1 g h g h g h g h g h g h g h g h g h g g h g h g h g h g h h g g 5 f 2 7 7 g h 7 7 5 7 7 7 7 7 7 7 7 7 7 3 7 7 7 7 g h g h g h 5 0 1 2 0 1 5 5 5 0 1 2 0 1 5 5 q h h g q h g h g h...

Page 22: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22683 1...

Reviews: