Functional Control
ESIE10-01
2–48
Part 2 – Functional Description
3
1
2
4
5
2.3.5
EXV Control
The EXV moves at a rate of 150 steps per second, with a total range of 3810 steps. Positioning should
be determined as described in the following sections, with adjustments made in increments of 0.1% of
the total range.
Preopen operation
The EXV control should include a preopen operation that is used only when the unit has liquid line
solenoids. The unit will be configured for use with or without liquid line solenoids via a set point.
When a circuit start is required, the EXV should be opened before the compressor starts. The preopen
position should be defined by a set point. The time allowed for this preopen operation should be at
least enough time for the EXV to open to the preopen position based on the programmed movement
rate of the EXV.
Startup operation
When the compressor starts if no liquid line solenoid valve is installed, the EXV will start to open to an
initial position that allows a safe start up. The value of LWT will determine if it is possible to enter the
normal operation. If it is higher than 20°C then a pressure control will start to keep the compressor into
the operating range. It goes in normal operation as soon as the suction superheat drops below a value
equal to the suction superheat setpoint.
Normal operation
Normal operation of the EXV can be used when the circuit has completed startup operation of the EXV
and is not in a slide transition conditions.
During normal operation, the EXV should control suction superheat to a target that can vary from 4°C
to 8.5°C.
The EXV should control the suction superheat within 0.8°C during stable operating conditions (stable
water loop, static compressor capacity, and stable condensing temperature).
The target value should be adjusted as needed to maintain discharge superheat within a range from
15°C to 25°C As the discharge superheat approaches 15°C, the suction superheat target should be
adjusted up. As the discharge superheat approaches 25°C, the suction superheat target should be
adjusted down. The control will apply a 0.5°C maximum reset every 5 minutes to the base target.
Maximum operating
pressures
The EXV control must maintain the evaporator pressure in the range defined by the maximum
operating pressure.
If the leaving water temperature is higher than 20°C at startup or if the pressure becomes higher than
3.5 bar during normal operations, then a pressostatic control will be started to keep the compressor
into the envelope.
Maximum operating pressure should be 3.5 bar.
It switches back to normal operation as soon as the suction superheat drops below 4°C suction
superheat setpoint.
Response to
compressor
capacity change
The logic will consider transition from 50% to 60% and from 60% to 50% as special conditions. When
a transition is entered the valve opening will change to adapt to the new capacity, this new calculated
position will be kept for 60 seconds. The valve opening will be increased during 50% to 60% transition
and decreased in 60% to 50% transition. Purpose of this logic is to limit liquid flood back when
changing from 50% to 60% if the capacity increases above 60% due to slides movement.
Summary of Contents for EWAD620-C17C-SS
Page 2: ......
Page 8: ...ESIE10 01 1 2 Part 1 System Outline 3 1 1 5...
Page 111: ...ESIE10 01 General Outline Part 1 System Outline 1 105 3 1 4 5 1 36 1 Power Compressor 1 2...
Page 112: ...General Outline ESIE10 01 1 106 Part 1 System Outline 3 1 1 4 5 1 36 2 Power Compressor 3...
Page 113: ...ESIE10 01 General Outline Part 1 System Outline 1 107 3 1 4 5 1 36 3 Kit Pumps...
Page 122: ...General Outline ESIE10 01 1 116 Part 1 System Outline 3 1 1 4 5 1 36 12 Digital Inputs Board...
Page 123: ...ESIE10 01 General Outline Part 1 System Outline 1 117 3 1 4 5 1 36 13 Digital Outputs Board...
Page 124: ...General Outline ESIE10 01 1 118 Part 1 System Outline 3 1 1 4 5 1 36 14 Digital Outputs Board...
Page 127: ...ESIE10 01 General Outline Part 1 System Outline 1 121 3 1 4 5 1 36 17 Extension Control Fans 4...
Page 131: ...ESIE10 01 General Outline Part 1 System Outline 1 125 3 1 4 5 1 36 21 EEXV Compressor 1...
Page 134: ...General Outline ESIE10 01 1 128 Part 1 System Outline 3 1 1 4 5 1 36 24 EEXV Compressor 2...
Page 137: ...ESIE10 01 General Outline Part 1 System Outline 1 131 3 1 4 5 1 36 27 EEXV Compressor 3...
Page 138: ...General Outline ESIE10 01 1 132 Part 1 System Outline 3 1 1 4 5 1 36 28 Pumps Control...
Page 139: ...ESIE10 01 General Outline Part 1 System Outline 1 133 3 1 4 5 1 36 29 Terminals M1 M2...
Page 140: ...General Outline ESIE10 01 1 134 Part 1 System Outline 3 1 1 4 5 1 36 30 Terminals M3...
Page 141: ...ESIE10 01 General Outline Part 1 System Outline 1 135 3 1 4 5 1 36 31 Terminals M5 MQ...
Page 148: ...General Outline ESIE10 01 1 142 Part 1 System Outline 3 1 1 4 5...
Page 150: ...ESIE10 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 170: ...The Digital Controller ESIE10 01 2 22 Part 2 Functional Description 3 1 2 4 5...
Page 200: ...Functional Control ESIE10 01 2 52 Part 2 Functional Description 3 1 2 4 5...
Page 202: ...ESIE10 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 254: ...Alarms and Events ESIE10 01 3 54 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...Controller Inputs and Outputs ESIE10 01 3 66 Part 3 Troubleshooting 3 1 3 4 5...
Page 280: ...ESIE10 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 286: ...Pre Test Run Checks ESIE10 01 4 8 Part 4 Commissioning and Test Run 3 1 4 5...
Page 289: ...ESIE10 01 Running Data Part 4 Commissioning and Test Run 4 11 3 4 5 1...
Page 290: ...Running Data ESIE10 01 4 12 Part 4 Commissioning and Test Run 3 1 4 5...