Maintenance
ESIE10-01
5–10
3
1
55
1.3
Standard Checks
Temperature and
pressure sensors
The unit comes factory-equipped with all the sensors listed below. Periodically check that their
measurements are correct by means of reference instruments (manometers, thermometers) and
correct any wrong readings as necessary, using the microprocessor keypad. Well-calibrated sensors
guarantee greater machine efficiency and a longer life.
N.B.:
refer to the microprocessor use and maintenance manual for a complete description of the
applications, settings and adjustments.
All sensors are preassembled and connected to the microprocessor. The descriptions of each sensor
are listed below:
■
Outlet water temperature sensor
– This sensor is located on the evaporator outlet water
connection and is used by the microprocessor to control the machine load depending on the
system's thermal load. It also helps control the evaporator's antifreeze protection.
■
Inlet water temperature sensor
– This sensor is located on the evaporator inlet water connection
and is used for monitoring the return water temperature.
■
External air temperature sensor
– Optional. This sensor allows for the monitoring of the external
air temperature on the microprocessor display. It is also used to carry out the 'OAT setpoint
override'.
■
Compressor discharge pressure compressor
– This is installed on every compressor and
allows to monitor the discharge pressure and to control the fans. Should the condensation pressure
increase, the microprocessor will control the compressor load in order to allow it to function even
if split. It also contributes to the oil control logic.
■
Oil pressure transducer
– This is installed on every compressor and allows you to monitor the oil
pressure. The microprocessor uses this sensor to inform the operator on the conditions of the oil
filter and on how the lubrication system is functioning. By working together with the high and low
pressure transducers, it protects the compressor from problems deriving from poor lubrication.
■
Low pressure compressor
– This is installed on every compressor and allows to monitor the
compressor suction pressure along with the low pressure alarms. It also contributes to the oil
control logic.
■
Suction sensor
– This is installed optionally (if the electronic expansion valve has been
requested) on every compressor, and allows for the monitoring of suction temperature. The
microprocessor uses the signal from this sensor to control the electronic expansion valve.
■
Compressor discharge temperature sensor
– This is installed on every compressor and allows
to monitor the compressor discharge pressure along with the oil temperature. The microprocessor
uses the signal from this sensor to control liquid injection and shut down the compressor should
discharge temperature reach 110°C. It also protects the compressor from pumping liquid at
start-up.
Summary of Contents for EWAD620-C17C-SS
Page 2: ......
Page 8: ...ESIE10 01 1 2 Part 1 System Outline 3 1 1 5...
Page 111: ...ESIE10 01 General Outline Part 1 System Outline 1 105 3 1 4 5 1 36 1 Power Compressor 1 2...
Page 112: ...General Outline ESIE10 01 1 106 Part 1 System Outline 3 1 1 4 5 1 36 2 Power Compressor 3...
Page 113: ...ESIE10 01 General Outline Part 1 System Outline 1 107 3 1 4 5 1 36 3 Kit Pumps...
Page 122: ...General Outline ESIE10 01 1 116 Part 1 System Outline 3 1 1 4 5 1 36 12 Digital Inputs Board...
Page 123: ...ESIE10 01 General Outline Part 1 System Outline 1 117 3 1 4 5 1 36 13 Digital Outputs Board...
Page 124: ...General Outline ESIE10 01 1 118 Part 1 System Outline 3 1 1 4 5 1 36 14 Digital Outputs Board...
Page 127: ...ESIE10 01 General Outline Part 1 System Outline 1 121 3 1 4 5 1 36 17 Extension Control Fans 4...
Page 131: ...ESIE10 01 General Outline Part 1 System Outline 1 125 3 1 4 5 1 36 21 EEXV Compressor 1...
Page 134: ...General Outline ESIE10 01 1 128 Part 1 System Outline 3 1 1 4 5 1 36 24 EEXV Compressor 2...
Page 137: ...ESIE10 01 General Outline Part 1 System Outline 1 131 3 1 4 5 1 36 27 EEXV Compressor 3...
Page 138: ...General Outline ESIE10 01 1 132 Part 1 System Outline 3 1 1 4 5 1 36 28 Pumps Control...
Page 139: ...ESIE10 01 General Outline Part 1 System Outline 1 133 3 1 4 5 1 36 29 Terminals M1 M2...
Page 140: ...General Outline ESIE10 01 1 134 Part 1 System Outline 3 1 1 4 5 1 36 30 Terminals M3...
Page 141: ...ESIE10 01 General Outline Part 1 System Outline 1 135 3 1 4 5 1 36 31 Terminals M5 MQ...
Page 148: ...General Outline ESIE10 01 1 142 Part 1 System Outline 3 1 1 4 5...
Page 150: ...ESIE10 01 2 2 Part 2 Functional Description 3 1 2 5...
Page 170: ...The Digital Controller ESIE10 01 2 22 Part 2 Functional Description 3 1 2 4 5...
Page 200: ...Functional Control ESIE10 01 2 52 Part 2 Functional Description 3 1 2 4 5...
Page 202: ...ESIE10 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 254: ...Alarms and Events ESIE10 01 3 54 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...Controller Inputs and Outputs ESIE10 01 3 66 Part 3 Troubleshooting 3 1 3 4 5...
Page 280: ...ESIE10 01 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 286: ...Pre Test Run Checks ESIE10 01 4 8 Part 4 Commissioning and Test Run 3 1 4 5...
Page 289: ...ESIE10 01 Running Data Part 4 Commissioning and Test Run 4 11 3 4 5 1...
Page 290: ...Running Data ESIE10 01 4 12 Part 4 Commissioning and Test Run 3 1 4 5...