background image

EWAP400~540MBYNN

Packaged air-cooled water chillers

4PW22678-1B

Installation manual

10

Example 2: Single ring system with separate pumps

Figure 2

  shows the system configuration, field wiring and terminals

for field wiring of this example.

Purpose

Purpose of this system is to deliver a constant water flow at a
constant temperature to a particular load. One unit, slave 3 (S3), is
kept as a standby unit.

Setup

The system is controlled on leaving water temperature. It is
required to install the additional sensor R8T (EKCLWS) in the
mixed water outlet and to connect it to the PCB of the master
unit.

Pump 1, pump 2 and pump 3 keep running as long as the
master unit, slave 1 or slave 2 are ON. Pump 4 only starts
running if slave 3 is switched ON. After switching OFF the units,
the pumps run for a time indicated by the 

 setting.

Slave 3 (S3) is configured to operate when its remote start/stop
switch S6S (S3) is pushed by the operator.

Slave 1 (S1), slave 2 (S2) and the master unit (M) are switched
ON or OFF using the remote start/stop switch S6S (M) which is
connected to the master unit.

The setpoint can be switched from 

  to

  using the dual setpoint selection switch S10S

which is connected to the master unit.

Parameter settings of the units

Usersettings menu:

Changeable inputs/outputs must be defined as follows:

Service setting menu:

Remark

Slave 3 can be configured to start up automatically if:

1 of the other units is in alarm or;

all other units are running on full capacity and the setpoint is not
reached yet.

To have your slave 3 unit act this way, set its mode to 

 

. In this

case, S6S (S3) has no function.

Example 3: Double ring system with several pumps

Figure 3

  shows the system configuration, field wiring and terminals

for field wiring of this example.

Purpose

Purpose of this system is to keep a buffer at a constant temperature
and to feed a load from this buffer. One unit, slave 3 (S3), is kept as a
standby unit.

Setup

The system is controlled on entering water temperature.

The pumps of the slave units only run when their compressor is
running (energy saving). After stopping the compressor, the
pump runs for a time indicated by the 

 setting.

The pump of the master unit must run continuously so as to
sense the correct temperature.

Slave 3 (S3) is configured to operate when its remote start/stop
switch S6S (S3) is pushed by the operator.

Slave 1 (S1), slave 2 (S2) and the master unit (M) are switched
ON or OFF using the remote start/stop switch S6S (M) which is
connected to the master unit.

The setpoint can be switched from 

 to 

using the dual setpoint selection switch S10S which is
connected to the master unit.

Parameter settings of the units

Usersettings menu:

Changeable inputs/outputs must be defined as follows:

Service setting menu:

Remark

Slave 3 can be configured to start up automatically if:

1 of the other units is in alarm or;

all other units are running on full capacity and the setpoint is not
reached yet.

To have your slave 3 unit act this way, set its mode to 

 

. In this

case, S6S (S3) has no function.

NOTE

K*P can also be a 24 V DC or 230 V AC contactor.

The additional sensor R8T (EKCLWS) must be
connected directly to the PCB of the master unit.

Slave 3

Slave 2

Slave 1

Master

 "

  

  "

 

 

 

 

Slave 3

Slave 2

Slave 1

Master

Terminal 76-78 

S10S DI1

  

Terminal 76-79 

S6S DI2

 

 

Terminal 76-85 

DI3

Terminal 76-86 

DI4

Terminal 8T+8T– 

R8T AI1

  

 

NOTE

K*P can also be a 24 V DC or 230 V AC contactor.

Slave 3

Slave 2

Slave 1

Master

 "

  

  "

 

     

Slave 3

Slave 2

Slave 1

Master

Terminal 76-78 

S10S DI1

  

Terminal 76-79 

S6S DI2

 

 

Terminal 76-85 

DI3

Terminal 76-86 

DI4

Terminal 8T+8T– 

R8T AI1

Summary of Contents for EWAP400MBYNN

Page 1: ...INSTALLATION MANUAL EWAP400MBYNN EWAP460MBYNN EWAP540MBYNN Packaged air cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...nderung 03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med...

Page 4: ...grills BMS Connection MODBUS J BUS BACNET LON Inverter fans Heat recovery High ESP fans Features Stepless capacity control 15 100 Evaporator heater tape Glycol application for leaving evaporator wate...

Page 5: ...the unit and the floor is flat to prevent vibration and noise generation 2 The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet refer to the operatio...

Page 6: ...or I beam frame to support the unit on the roof or it can be installed on a concrete base Ground level mounted The unit must be installed on a solid base It is recommended to fix the unit on a concret...

Page 7: ...To assure proper operation of the unit the water flow through the evaporator must be within the operation range as specified in the table below and a minimum water volume is required in the system Th...

Page 8: ...note the following Switch for remote on off Units with status or will be controlled by the remote on off switch connected to the chiller defined as Units with status are controlled by the switch conne...

Page 9: ...not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for...

Page 10: ...s to comply Defining of the changeable digital analog inputs and outputs Besides locked inputs and outputs there are a number of changeable inputs and outputs of which the function can be chosen from...

Page 11: ...from a supervisory system If set to no the supervisory system can only read out values but cannot modify them used to address the PCB indicates the communication protocol If the optional gateway is us...

Page 12: ...ll units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master u...

Page 13: ...em configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this buffer One unit s...

Page 14: ...Installation manual 11 EWAP400 540MBYNN Packaged air cooled water chillers 4PW22678 1B NOTES...

Page 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergenc...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22678 1B...

Reviews: