D – 508 C – 07/02 D – EN pag. 12/36
Electrical data EWAP-AJYNN with option OPRN/OPLN R-407C
Unit size
800
900
950
C10
C11
C12
Standard voltage (1)
400 V – 3f – 50 Hz
Nominal unit current (2)
A
566 615 705 766 823 842
Max compressor current (3)
A
620 675 726 782 842 921
Fans current
A
28 30 32 34 37 41
Max unit current (3)
A
648 705 758 816 879 962
Max unit inrush current (4)
A
1048 1050 1104 1106 1154 1270
Max unit current for wires sizing (5)
A
648 706 764 822 881 971
32
Unit size
C13
C14
C15
C16
C17
C18
Standard voltage (1)
400 V – 3f – 50 Hz
Nominal unit current (2)
A
902 947 1053 1125 1182 1238
Max compressor current (3)
A
978 1040 1069 1147 1207 1266
Fans current
A
44 46 51 51 53 55
Max unit current (3)
A
1022 1086 1120 1198 1260 1316
Max unit inrush current (4)
A
1265 1354 1386 1393 1484 1482
Max unit current for wires sizing (5)
A
1030 1088 1149 1205 1263 1321
Notes: (1)
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2)
Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3)
Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 38°C ambient temp.
(4)
Inrush current of biggest comp 75 % of nominal absorbed current of the other comp fans current.
(5)
Compressor FLA + fans current.