background image

4 Installation

Installation manual

8

EWAQ+008BAVP

Packaged air-cooled water chillers and packaged air to water heat

pumps

4P478610-1 – 2017.02

1

Drill (a, 4×) and remove the knockout hole (b).

b

        

a b

4× Ø6 mm

2

Remove  the  burrs,  and  paint  the  edges  and  areas  around  the
edges using repair paint to prevent rusting.

4.2.4

To prevent the outdoor unit from falling
over

1

Prepare  2  cables  as  indicated  in  the  following  illustration  (field
supply).

2

Place the 2 cables over the outdoor unit.

3

Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit
to prevent the cable from scratching the paint (field supply).

4

Attach the cable’s ends. Tighten those ends.

4.3

Connecting the water piping

4.3.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.  Make  sure  that  the  tightening  torque  does  NOT
exceed 30 N•m.

To facilitate service and maintenance, 2 shut-off valves are provided.
Mount  the  valves  on  the  water  inlet  and  on  the  water  outlet.  Mind
their  position:  the  integrated  drain  valves  will  only  drain  the  side  of
the  circuit  on  which  they  are  located.  To  be  able  to  only  drain  the
unit, make sure the drain valves are positioned between the shut‑off
valves and the unit.

a

b

a

Water inlet

b

Water outlet

1

Screw the outdoor unit nuts on the shut-off valves.

2

Connect the field piping on the shut-off valves.

NOTICE

Install a manometer in the system.

NOTICE

Install air purge valves at all local high points.

4.3.2

To protect the water circuit against
freezing

If  negative  outdoor  temperatures  are  expected,  add  glycol  to  the
water  circuit.  The  required  concentration  depends  on  the  lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from  freezing,  more  glycol  is  required.  Add  glycol  according  to  the
table below.

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

▪ The  addition  of  glycol  applies  to  BOTH  cooling‑only

models (008BAVP) AND reversible models
(008BAVP),  and  is  independent  of  cooling
or  heating  operation.  ALWAYS  add  glycol  if  negative
outdoor temperatures are expected.

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ In  case  of  a  power  supply  failure  or  pump  failure,  and

NO glycol was added to the system, drain the system.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

The following types of glycol are allowed:

Ethylene glycol

;

Propylene glycol

, including the necessary inhibitors, classified as

Category III according to EN1717.

WARNING

Ethylene glycol is toxic.

Summary of Contents for EWAQ006BAVP

Page 1: ...Packaged air cooled water chillers and packaged air to water heat pumps English Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAQ006BAVP EWAQ008BAVP EWYQ...

Page 2: ...C 100 250 100 A B C E 150 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a...

Page 3: ...valt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sek...

Page 4: ...ut 18 7 Hand over to the user 18 7 1 About locking and unlocking 19 To activate or deactivate a function lock 19 To activate or deactivate button lock 19 8 Technical data 20 8 1 Piping diagram Outdoor...

Page 5: ...ivered with the outdoor unit 3 Preparation 3 1 Preparing installation site 3 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See figure 1 on the inside of the front...

Page 6: ...electrical connections for external and internal actuators Item Description Wires Maximum running current Outdoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Normal kWh rate power supp...

Page 7: ...properly When the unit is in cooling mode condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold cli...

Page 8: ...peratures are expected add glycol to the water circuit The required concentration depends on the lowest expected outdoor temperature and on whether you want to protect the system from bursting or from...

Page 9: ...me of the system For more information refer to the chapter To check the water volume and flow rate in the installer reference guide 4 3 3 To fill the water circuit 1 Connect the water supply hose to t...

Page 10: ...that the cable does NOT come in contact with sharp edges 5 Install the switch box cover INFORMATION When installing field supply or option cables foresee sufficient cable length This will make it poss...

Page 11: ...b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 4 4 4 T...

Page 12: ...more than 4 seconds Result is displayed on the home pages 4 If you do NOT press any button for more than 1 hour or press again for more than 4 seconds the installer permission level switches back to E...

Page 13: ...Description A 2 2 E 1 E 03 Backup heater steps 0 default 1 2 Code Description A 2 2 E 2 5 0D BUH type 1 1P 1 1 2 6 kW 1 230 V default 4 3PN 1 2 6 kW 3N 400 V 9W 5 3PN 1 1 2 9 kW 3N 400 V 9W The syste...

Page 14: ...d Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for leaving water temperature control 3 WD scheduled Weather dependent scheduled only for leaving water temperature...

Page 15: ...eaving water setpoint By setting the weather dependent curve to a higher position it cannot drop below the minimum setpoint Refer to the illustration below a 8 06 8 06 b Ta Tt a Weather dependent curv...

Page 16: ...pe Indoor software type Unit control method Pump operation mode Power saving possible User interface location Options External sensor Control box Option box Leaving water Main Delta T source Room ther...

Page 17: ...pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 5 If glycol was added to th...

Page 18: ...ettings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually p...

Page 19: ...er to be able to change setpoint temperatures the simplified user interface or an external room thermostat is then required You can use the following locking modes Function lock Locks a specific funct...

Page 20: ...heat exchanger 9 Safety valve 10 Water filter 11 Expansion vessel 12 R1T Outlet water heat exchanger thermistor 13 R3T Refrigerant liquid side thermistor 14 R4T Inlet water thermistor 15 Gas stop val...

Page 21: ...1P Signal transmission circuit V1D V3D A1P Diode V1R A1P IGBT power module V2R A1P Diode module V1T V2T A1P Insulated gate bipolar transistor IGBT X1M Terminal strip Y1E Electronic expansion valve Y1S...

Page 22: ...power circuit A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat K1A Relay for heating K2A Relay for cooling M2S Shut OFF valve M4S Valve kit English...

Page 23: ...eter inputs 5 V DC pulse detection voltage supplied by PCB Electric pulse meter inputs 5 V DC pulse detection voltage supplied by PCB 2 Legend 2 Legend A4P Extension PCB control optional R6T External...

Page 24: ...for KRUCB A5P P1 P2 user interface A5P P1 P2 user interface Power supply 3 core control box power supply 230 V earth signal signal signal 2 or 3 core 2 core 2 core F1B L1 L2 L3 N earth or L N earth b...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4P478610 1 2017 02 Copyright 2017 Daikin...

Reviews: