background image

4 Installation

Installation manual

9

EWAQ+008BAVP
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P478610-1 – 2017.02

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

NOTICE

▪ If overpressure occurs, the system will release some of

the liquid through the pressure relief valve. If glycol was
added to the system, take adequate measures so as to
safely recover it.

▪ In  any  case,  make  sure  that  the  flexible  hose  of  the

pressure  relief  valve  is  ALWAYS  free  to  release
pressure.  Prevent  water  from  staying  and/or  freezing
up inside the hose.

WARNING

Due  to  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

Adding  glycol  to  the  water  circuit  reduces  the  maximum  allowed
water  volume  of  the  system.  For  more  information,  refer  to  the
chapter  "To  check  the  water  volume  and  flow  rate"  in  the  installer
reference guide.

4.3.3

To fill the water circuit

1

Connect the water supply hose to the drain and fill valve.

2

Open the drain and fill valve.

3

If  an  automatic  air  purge  valve  was  installed,  make  sure  it  is
open.

4

Fill  the  circuit  with  water  until  the  manometer  (field  supply)
indicates a pressure of ±2.0 bar.

5

Purge  as  much  air  as  possible  from  the  water  circuit.  For
instructions, see 

"6 Commissioning" on page 17

.

6

Refill the circuit until the pressure is ±2.0 bar.

7

Repeat steps 5 and 6 until no more air is purged and there are
no more pressure drops.

8

Close the drain and fill valve.

9

Disconnect the water supply hose from the drain and fill valve.

4.3.4

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

To  prevent  the  freezing  of  the  outdoor  water  piping  during  winter
time, the thickness of the sealing material MUST be at least 13 mm
(with λ=0.039 W/mK).

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

During  winter,  protect  the  water  piping  and  shut‑off  valves  against
freezing  by  adding  heat  tape  (field  supply).  If  the  outdoor
temperature  can  drop  below  –20°C  and  no  heat  tape  is  used,  it  is
recommended to install the shut‑off valves indoors.

4.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.4.1

To connect the electrical wiring on the
outdoor unit

1

Remove the switch box cover. See 

"4.1.1 To open the outdoor

unit" on page 6

.

2

Insert the wiring from the back of the unit:

a

b
c

≥25 mm

a

Low voltage cable

b

High voltage cable

c

Power supply cable

NOTICE

The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 25 mm.

Summary of Contents for EWAQ006BAVP

Page 1: ...Packaged air cooled water chillers and packaged air to water heat pumps English Installation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAQ006BAVP EWAQ008BAVP EWYQ...

Page 2: ...C 100 250 100 A B C E 150 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a...

Page 3: ...valt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sek...

Page 4: ...ut 18 7 Hand over to the user 18 7 1 About locking and unlocking 19 To activate or deactivate a function lock 19 To activate or deactivate button lock 19 8 Technical data 20 8 1 Piping diagram Outdoor...

Page 5: ...ivered with the outdoor unit 3 Preparation 3 1 Preparing installation site 3 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See figure 1 on the inside of the front...

Page 6: ...electrical connections for external and internal actuators Item Description Wires Maximum running current Outdoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Normal kWh rate power supp...

Page 7: ...properly When the unit is in cooling mode condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold cli...

Page 8: ...peratures are expected add glycol to the water circuit The required concentration depends on the lowest expected outdoor temperature and on whether you want to protect the system from bursting or from...

Page 9: ...me of the system For more information refer to the chapter To check the water volume and flow rate in the installer reference guide 4 3 3 To fill the water circuit 1 Connect the water supply hose to t...

Page 10: ...that the cable does NOT come in contact with sharp edges 5 Install the switch box cover INFORMATION When installing field supply or option cables foresee sufficient cable length This will make it poss...

Page 11: ...b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 4 4 4 T...

Page 12: ...more than 4 seconds Result is displayed on the home pages 4 If you do NOT press any button for more than 1 hour or press again for more than 4 seconds the installer permission level switches back to E...

Page 13: ...Description A 2 2 E 1 E 03 Backup heater steps 0 default 1 2 Code Description A 2 2 E 2 5 0D BUH type 1 1P 1 1 2 6 kW 1 230 V default 4 3PN 1 2 6 kW 3N 400 V 9W 5 3PN 1 1 2 9 kW 3N 400 V 9W The syste...

Page 14: ...d Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for leaving water temperature control 3 WD scheduled Weather dependent scheduled only for leaving water temperature...

Page 15: ...eaving water setpoint By setting the weather dependent curve to a higher position it cannot drop below the minimum setpoint Refer to the illustration below a 8 06 8 06 b Ta Tt a Weather dependent curv...

Page 16: ...pe Indoor software type Unit control method Pump operation mode Power saving possible User interface location Options External sensor Control box Option box Leaving water Main Delta T source Room ther...

Page 17: ...pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 5 If glycol was added to th...

Page 18: ...ettings Commissioning Actuator test run 4 Select an actuator and press Example Pump 5 Select OK and press Result The actuator test run starts It automatically stops when finished To stop it manually p...

Page 19: ...er to be able to change setpoint temperatures the simplified user interface or an external room thermostat is then required You can use the following locking modes Function lock Locks a specific funct...

Page 20: ...heat exchanger 9 Safety valve 10 Water filter 11 Expansion vessel 12 R1T Outlet water heat exchanger thermistor 13 R3T Refrigerant liquid side thermistor 14 R4T Inlet water thermistor 15 Gas stop val...

Page 21: ...1P Signal transmission circuit V1D V3D A1P Diode V1R A1P IGBT power module V2R A1P Diode module V1T V2T A1P Insulated gate bipolar transistor IGBT X1M Terminal strip Y1E Electronic expansion valve Y1S...

Page 22: ...power circuit A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat K1A Relay for heating K2A Relay for cooling M2S Shut OFF valve M4S Valve kit English...

Page 23: ...eter inputs 5 V DC pulse detection voltage supplied by PCB Electric pulse meter inputs 5 V DC pulse detection voltage supplied by PCB 2 Legend 2 Legend A4P Extension PCB control optional R6T External...

Page 24: ...for KRUCB A5P P1 P2 user interface A5P P1 P2 user interface Power supply 3 core control box power supply 230 V earth signal signal signal 2 or 3 core 2 core 2 core F1B L1 L2 L3 N earth or L N earth b...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4P478610 1 2017 02 Copyright 2017 Daikin...

Reviews: