EWAQ+EWYQ009~0 EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to
water heatpumps
4PW51588-1
Operation manual
10
[1] Weather dependent set point (heat pump models only)
The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: colder outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C. See the
operation manual for more details on weather dependent operation.
■
[1-00] Low ambient temperature (Lo_A): low outdoor
temperature.
■
[1-01] High ambient temperature (Hi_A): high outdoor
temperature.
■
[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is
required.
■
[1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A).
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.
[3] Auto restart
When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.
Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the
pr
button to enable the schedule timer again.
■
[3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).
[9] Cooling and heating set points
The purpose of this field setting is to prevent the user from selecting
a wrong (i.e., too hot or too cold) leaving water temperature. Thereto
the heating temperature set point range and the cooling temperature
set point range available to the user can be configured.
■
[9-00] Heating set point upper limit: maximum leaving water
temperature for heating operation.
■
[9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.
■
[9-02] Cooling set point upper limit: maximum leaving water
temperature for cooling operation.
■
[9-03] Cooling set point lower limit: minimum leaving water
temperature for cooling operation.
■
[9-04] Overshoot setting: defines how much the water
temperature may rise above the setpoint before the
compressor stops. This function is only applicable in heating
mode.
[A] Quiet mode
This field setting allows to select the desired quiet mode. Two quiet
modes are available: quiet mode A and quiet mode B.
In quiet mode A, priority is given to the unit operating quietly under all
circumstances. Fan and compressor speed (and thus performance)
will be limited to a certain percentage of the speed at normal
operation. In certain cases, this might result in reduced performance.
In quiet mode B, quiet operation might be overridden when higher
performance is required. In certain cases, this might result in less
quiet operation of the unit to meet the requested performance.
■
[A-00] Quiet mode type: defines whether quiet mode A (0) or
quiet mode B (2) is selected.
■
[A-01] Parameter 01: do not change this setting. Leave it set
to its default value.
[C] Alarm output logic of EKRP1HB
■
[C-01] Defines the logic of the alarm output on the EKRP1HB
remote alarm input/output PCB.
If [C-01]=0, the alarm output will be powered when an alarm
occurs (default).
If [C-01]=1, the alarm output will not be powered when an alarm
occurs. This field setting allows for distinction between detection
of an alarm and detection of a power failure to the unit.
T
t
Target water temperature
T
A
Ambient (outdoor) temperature
= Shift value
NOTE
It is therefore recommended to leave the auto restart
function enabled.
NOTE
If the benefit kWh rate power supply is of the type that
power supply is interrupted, then always allow the auto
restart function.
Lo_Ti
Lo_A
Hi_A
T
A
T
t
+ 05
00
– 05
Hi_Ti
Shift value
In case of a floor cooling application, it is important to limit
the minimum leaving water temperature at cooling
operation (field setting of parameter [9-03]) to 16~18°C to
prevent condensation on the floor.
Do not set other values than the ones mentioned.
[C-01]
Alarm
No alarm
No power supply
to unit
0 (default)
Closed output
Open output
Open output
1
Open output
Closed output
Open output
Summary of Contents for EWAQ009ACV3
Page 15: ......
Page 16: ...4PW51588 1 Copyright Daikin ...