background image

EWAQ+EWYQ009~0 EWAQ+EWYQ009~013ACW1

Packaged air-cooled water chillers and packaged reversible air to 
water heatpumps

4PW51588-1

Operation manual

8

10

Press the 

<

  button for 5 seconds to store the programmed

actions.

If the 

<

  button is pressed when action number 3 is displayed,

actions 1, 2 and 3 are stored but 4 and 5 are deleted.

You automatically return to step 

4

.  By pressing the 

pr

  button

several times, you return to previous steps in this procedure and
finally return to normal operation.

Consulting programmed actions

Consulting cooling or heating actions

Consulting cooling or heating is carried out as follows.

1

Use the 

=

  button to select the operation mode (cooling or

heating) you want to consult.

2

Press the 

<

 button.

The actual mode is blinking.

3

Press the 

<

 button to confirm the selected mode.

The actual day is blinking.

4

Select the day you would like to consult by means of the 

pi

and 

pj

 buttons.

The selected day is blinking.

5

Press the 

<

 button to confirm the selected day.

The first programmed action of the selected day appears.

6

Use the 

pi

  and 

pj

  buttons to consult the other

programmed actions of that day.

This is called the readout mode. Empty program actions (e.g. 4
and 5) are not displayed.

By pressing the 

pr

 button several times, you return to previous

steps in this procedure and finally return to normal operation.

Consulting quiet mode

Consulting quiet mode is carried out as follows.

1

Press the 

<

 button.

The actual mode is blinking.

2

Use the 

pi

  and 

pj

  buttons to select the quiet mode

(quiet mode 

s

).

The selected mode is blinking.

3

Press the 

<

 button to confirm the selected mode.

The first programmed action is displayed.

4

Use the 

pi

  and 

pj

  buttons to consult the programmed

actions.

This is called the readout mode. Empty program actions (e.g. 4
and 5) are not displayed.

By pressing the 

pr

 button several times, you return to previous

steps in this procedure and finally return to normal operation.

Tips and tricks

Programming the next day(s)

After confirming the programmed actions of a specific day (i.e. after
pressing the 

<

 button for 5 seconds), press the 

pr

 button once. You

can now select another day by using the 

pi

 and 

pj

 buttons

and restart consulting and programming.

Copying programmed actions to next day

In heating/cooling program it is possible to copy all programmed
actions of a specific day to the next day (e.g. copy all programmed
actions from "

1

" to "

2

").

To copy programmed actions to the next day, proceed as follows:

1

Press the 

<

 button.

The actual mode is blinking.

2

Use the 

pi

 and 

pj

 buttons to select the mode you want

to program.

The selected mode is blinking.

You can leave programming by pressing the 

pr

 button.

3

Press the 

<

 button to confirm the selected mode.

The actual day is blinking.

4

Select the day you would like to copy to the next day by means
of the 

pi

 and 

pj

 buttons.

The selected day is blinking.

You can return to step 

2

 by pressing the 

pr

 button.

5

Press the 

<

 and 

pr

 buttons simultaneously for 5 seconds.

After 5 seconds the display will show the next day (e.g. "

2

" if

"

1

" was selected first). This indicates that the day has been

copied.

You can return to step 

2

 by pressing the 

pr

 button.

Deleting one or more programmed actions

Deleting one or more programmed actions is done at the same time
as storing the programmed actions.

When all actions for one day have been programmed, make sure that
the display shows the highest action number you would like to save.
By pressing the 

<

 button for 5 seconds, you store all actions except

those with a higher action number than the one that is displayed.

E.g. when the 

<

  button is pressed when action number 3 is

displayed, actions 1, 2 and 3 are stored but 4 and 5 are deleted.

Deleting a mode

1

Press the 

<

 button.

The actual mode is blinking.

2

Use the 

pi

 and 

pj

 buttons to select the mode you want

to delete (quiet mode 

or current mode).

The selected mode is blinking.

3

Press the 

<

  and 

ba

  button simultaneously for 5 seconds to

delete the selected mode.

Deleting a day of the week (cooling or heating mode)

1

Use the 

=

  button to select the operation mode (cooling or

heating) you want to delete.

2

Press the 

<

 button.

The actual mode is blinking.

3

Press the 

<

 button to confirm the selected mode.

The actual day is blinking.

4

Select the day you would like to delete by means of the 

pi

and 

pj

 buttons.

The selected day is blinking.

5

Press the 

<

  and 

ba

  button simultaneously for 5 seconds to

delete the selected day.

NOTE

Consulting cooling or heating is done in the same way.
At the start of the consulting procedure cooling or
heating is selected. After that, you have to return to the
start of the consulting procedure to consult the other
operation mode.

NOTE

Returning to previous steps in this procedure is done
by pressing the 

pr

 button.

NOTE

Returning to previous steps in this procedure is done
by pressing the 

pr

 button.

Summary of Contents for EWAQ009ACV3

Page 1: ...Q009ACV3 EWAQ010ACV3 EWAQ011ACV3 EWYQ009ACV3 EWYQ010ACV3 EWYQ011ACV3 EWAQ009ACW1 EWAQ011ACW1 EWAQ013ACW1 EWYQ009ACW1 EWYQ011ACW1 EWYQ013ACW1 Packaged air cooled water chillers and packaged reversible air to water heatpumps ...

Page 2: ...erter chiller THIS MANUAL This manual describes how to start up and switch off the unit set parameters and configure the schedule timer by means of the controller maintain the unit and solve operational problems THIS UNIT This unit is designed for outdoor installation and used for both heating and cooling applications The unit is designed to be combined with fan coil units or air handling units fo...

Page 3: ...eration The LED blinks if a malfunction occurs When the LED is OFF cooling or heating are inactive 3 OPERATION MODE ICONS hcs These icons indicate the current operation mode s heating h cooling c or quiet mode s Quiet mode is a feature of the cooling or heating operation mode When quiet mode is activated the quiet mode icon and the heating or cooling mode icon will be displayed simultaneously In a...

Page 4: ...This multi purpose button is used to program the controller The function of the button depends on the actual status of the controller or on previous actions carried out by the operator 30 SCHEDULE TIMER BUTTON r p The main function of this multi purpose button is to enable disable the schedule timer The button is also used to program the controller The function of the button depends on the actual ...

Page 5: ...utton The operation LED 0 lights up Selecting quiet mode operation s 1 Use the s button to activate quiet mode operation s Icon s appears on the display If the controller is set in permission level 2 or 3 refer to Field settings on page 9 the s button will not be operable Selecting weather dependent set point operation heat pump models only 1 Press the ba button to select weather dependent set poi...

Page 6: ... the actual setting one should consult the last programmed command It is clear that the last programmed command may date from the day before Refer to Consulting programmed actions on page 8 NOTE Only use the pr button to enable or disable the schedule timer The schedule timer overrules the y button The y button only overrules the schedule timer until the next programmed action If the auto restart ...

Page 7: ... setpoint heating actions are added automatically at the same time but with the default heating set point The set points of these automatically added actions can be adjusted by programming the corresponding mode This means that after programming heating you should also program the corresponding cooling set points and vice versa Programming Programming cooling or heating Due to the fact that the sc...

Page 8: ...y shows the highest action number you would like to save 12 Press the button for 5 seconds to store the programmed actions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted You automatically return to step 6 By pressing the pr button several times you return to previous steps in this procedure and finally return to normal operation Prog...

Page 9: ...mmed actions of a specific day to the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to select the mode you want to program The selected mode is blinking You can leave programming by pressing the pr button 3 Press the button to confirm the selected mode The...

Page 10: ... code is indicated 2 with the set value displayed to the right 1 2 Press the bgi button to select the appropriate field setting first code 3 Press the bgj button to select the appropriate field setting second code 4 Press the pfi button and pfj button to change the set value of the select field setting 5 Save the new value by pressing the pr button 6 Repeat step 2 through 4 to change other field s...

Page 11: ...9 00 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set point upper limit maximum leaving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation 9 04 Overshoot setting defines how m...

Page 12: ...electricity company that contact will close and the unit will go in forced off mode 2 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature D 00 Compressor 0 default Forced off 1 Fo...

Page 13: ...lable 6 Not available 7 Not available 8 Not available 9 Cooling and heating set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 15 15 37 1 C 02 Cooling set point upper limit 22 18 22 1 C 03 Cooling set point lower limit 5 5 18 1 C 04 Overshoot setting 2 1 4 1 C A Quiet mode 00 Quiet mode type 0 0 2 01 Parameter 01 3 C Alarm output logic of EKRP1HB 00 Not...

Page 14: ...ong time e g 1 hour too late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Your product is marked with this symbol This means that electrical and electronic products shall not be...

Page 15: ......

Page 16: ...4PW51588 1 Copyright Daikin ...

Reviews: