EWAQ016~ EWYQ016~064BAW
Packaged air-cooled water chiller
4PW70082-1C – 2013.07
Installation and operation manual
40
A
Option setup
00
Not applicable. Do not change the default value.
0
—
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Not applicable. Do not change the default value.
5
—
—
—
03
Allowable overshoot on leaving water
3
1~5
0.5
°C
04
Ethylene glycol concentration
0
0~1
1
—
b
Settings are not applicable
00
Not applicable. Do not change the default value.
35
—
—
—
01
Not applicable. Do not change the default value.
45
—
—
—
02
Not applicable. Do not change the default value.
1
—
—
—
03
Not applicable. Do not change the default value.
70
—
—
—
04
Not applicable. Do not change the default value.
70
—
—
—
C
Leaving water temperature limits
00
Set point: heating leaving water maximum
temperature
50
37~50
1
°C
01
Set point: heating leaving water minimum
temperature
25
25~37
1
°C
02
Set point: cooling leaving water maximum
temperature
20
18~22
1
°C
03
Set point: cooling leaving water minimum
temperature
5
Q
(a)
~18
1
°C
04
Not applicable. Do not change the default value.
0
—
—
—
d
Settings are not applicable
00
Not applicable. Do not change the default value.
10
—
—
—
01
Not applicable. Do not change the default value.
30
—
—
—
02
Not applicable. Do not change the default value.
15
—
—
—
03
Not applicable. Do not change the default value.
15
—
—
—
04
Not applicable. Do not change the default value.
40
—
—
—
E
Service mode
00
Not applicable. Do not change the default value.
0
—
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Not applicable. Do not change the default value.
1
—
—
—
04
Pump only operation
0
0~25
1
—
F
Settings are not applicable
00
Not applicable. Do not change the default value.
5
—
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Not applicable. Do not change the default value.
1
—
—
—
03
Not applicable. Do not change the default value.
10
—
—
—
04
Not applicable. Do not change the default value.
50
—
—
—
(a) Refer to page 21 where [C-03] is explained.
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
4PWEN70082-1C.book Page 40 Wednesday, September 25, 2013 7:31 AM