background image

D-EIMWC01008-16_03EN - 6/35 

30.  the machinery must be installed in structures protected against atmospheric discharge according to the applicable 

laws and technical standards 

31.  do not bend or hit pipes containing pressurised fluids 
32.  it is not permitted to walk or rest other objects on the machines 
33.  the user is responsible for overall evaluation of the risk of fire in the place of installation (for example, calculation 

of the fire load) 

34.  during transport, always secure the unit to the bed of the vehicle to prevent it from moving about and overturning 
35.  the machine must be transported according to the regulations in force taking into account the characteristics of 

the fluids in the machine and the description of these on the safety data sheet 

36.  inappropriate transport can cause damage to the machine and even leaking of the refrigerant fluid. Before start -

up, the machine must be checked for leaks and repaired accordingly.  

37.  the accidental discharge of  refrigerant in a closed area can cause a lack of oxygen and, therefore, the  risk of 

asphyxiation:  install  the  machinery  in  a  well  ventilated  environment  according  to  EN  378 -3  and  the  local 
regulations in force. 

38.  the installation must comply with the requirements of EN 378-3 and the local regulations in force; in the case of 

installations  indoors,  good  ventilation  must  be  guaranteed  and  refrigerant  detectors  must  be  fitted  when 
necessary. 

 
 

1.2 

Description 

The unit purchased is a Heat Pump, that is a machine designed to cool/heat the water (or  a water-glycol mixture) within 
certain limits which will be listed below. The unit operates based on the compression, condensation and evaporation of the 
coolant gas as per the Carnot cycle, and is composed mainly of the following parts depending on the Mo de of Operation. 
 

Cooling or Conditioning Mode: 

 

Screw compressors which increase the pressure of the refrigerant gas from evaporation pressure to condensation 
pressure. 

 

A water-cooled condenser where the refrigerant gas condenses under high pressure and transfers heat to the 
water. 

 

An expansion valve which allows the pressure of condensed liquid refrigerant to be reduced from condensation 
pressure to evaporation pressure. 

 

A water-cooled evaporator, where the low-pressure liquid refrigerant evaporates and chills the water. 

 
Heating Mode or Heat Pump: 

 

Screw compressors compressors which increase the pressure of the refrigerant gas from evaporation pressure 
to condensation pressure. 

 

A condenser where the refrigerant gas condenses under high pressure and transfers heat to the water. 

 

An expansion valve which allows the pressure of condensed liquid refrigerant to be reduced from condensation 
pressure to evaporation pressure. 

 

An evaporator, where the low-pressure liquid refrigerant evaporates and chills the water. 

 

The  operation  of  the  heat  exchangers  can  be  inverted  connecting  the  user  piping  to  the  Brazed  Plate  Heat 
exchanger (chilled water) or to the shell&tube heat exchanger (heated water).  

 
All standard units are fully assembled in Daikin Applied Europe factory and tested before shipping, only the condenserless 
untis can not be tested. 
The EWWD(H/S)-J range consists of models with a single refrigerant circuit (from 90 to 120 kW).  
The machine uses three type of refrigerant fluids: R134a, R1234ze, R513A with different envelopes. 
The  controller  is  pre-wired,  set  up  and  tested  at  the  factory.  Only  normal  field  connections  such  as  piping,  electrical 
connections and pump interlocks are required, simplifying installation and increasing reliability. All safety an d operation 
control systems are installed at the factory in the control panel.  
The instructions in this manual are applicable to all models in this series unless otherwise specified.  
 

1.3 

Information about the refrigerants used 

This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere. 
 

Models 

EWWD J  
EWLD J 

EWWH J 
EWLH J 

EWWS J 
EWLS J 

Refrigerant type 

R134a 

R1234ze 

R513A 

GWP

(1)

 value 

1430 

572 

 
 
For the EWWD J, EWWH J and EWWS J unit versions the quantity is indicated on the unit name plate. 
 
For the EWLD J, EWLH J and EWLS J  unit versions, please fill the total refrigerant charge in with indelible ink on the 
refrigerant charge label supplied with the product.  

 

(

1

)  GWP = global warming potential

 

Summary of Contents for EWLD-J

Page 1: ...structions REV 03 Date 04 2021 Supersedes D EIMWC01008 16_02EU Installation Operation and Maintenance Manual EWWD EWLD J EWWH EWLH J EWWS EWLS J Installation Operation and Maintenance Manual D EIMWC01...

Page 2: ...GUIDELINES FOR REMOTE CONDENSER APPLICATION EWLD J EWLH and EWLS versions 22 6 1 Installation information for condenserless units 22 6 1 1 Precautions when handling piping 22 6 1 2 Leak test and vacu...

Page 3: ...alve Condenser Shut off valve Filter drier Shut off valve charge valve Solenoid valve Liquid indicator 1 2 3 4 5 6 7 8 Control equipment High Pressure Switch 21 0bar Pressure Transducer Temperature Tr...

Page 4: ...EWLH80J SS 190J SS EWLS110J SS 270J SS Label Identification Figure 2 Description of the labels applied to the electrical panel 1 Unit nameplate data 5 Manufacturer s logo 2 Lifting instructions 6 Eme...

Page 5: ...el 14 check that the unit has been grounded correctly before starting it 15 install the machine in a suitable area in particular do not install it outdoors if it is intended for use indoors 16 do not...

Page 6: ...sfers heat to the water An expansion valve which allows the pressure of condensed liquid refrigerant to be reduced from condensation pressure to evaporation pressure A water cooled evaporator where th...

Page 7: ...9 31 7 70 50 13 18 69 20 69 7 2 26 12 4 43 32 7 92 51 13 51 70 21 16 6 2 34 13 4 58 33 8 15 52 13 85 71 21 64 5 2 43 14 4 73 34 8 39 53 14 20 72 22 13 4 2 53 15 4 88 35 8 63 54 14 55 73 22 62 3 2 62 1...

Page 8: ...a and R513A According to the standard EN 378 1 2016 any refrigerant system that contains R134a or R513A can be installed without any restriction in open air or machinery rooms Anyway the building owne...

Page 9: ...and including the charge and safety classification of the refrigerant used shall be conducted to determine whether it is necessary to place the refrigerating system in a separate refrigeration machine...

Page 10: ...gerants heavier than air and at the highest point for refrigerants lighter than air Detectors shall be continuously monitored for functioning In the case of a detector failure the emergency sequence s...

Page 11: ...ndensing atmosphere may damage electronic components 4 2 Operation The Daikin EWWD J EWLD J EWWH J EWLH J EWWS J EWLS J packaged water cooled water chillers are designed for indoor installation and us...

Page 12: ...D EIMWC01008 16_03EN 12 35 4 2 2 Operation range EWWD J 1 Operation with Glycol below 4 C Evap LWT EWLD J 1 Operation with Glycol below 4 C Evap LWT...

Page 13: ...vap LWT 2 Option111 and operation with Glycol below 4 C Evap LWT 3 Option111 4 Option 111 Option 189 5 Option 189 EWLH J 1 Operation with Glycol below 4 C Evap LWT 2 Option111 and operation with Glyco...

Page 14: ...D EIMWC01008 16_03EN 14 35 EWWS J 1 Operation with Glycol below 4 C Evap LWT EWLS J 1 Operation with Glycol below 4 C Evap LWT...

Page 15: ...re 3 Lifting When handling the unit take into account the following 1 List the unit preferably with a crane and belts in accordance with the instructions on the unit The length of the ropes 1 to be us...

Page 16: ...x the unit on a concrete base with anchor bolts 1 Anchor bolt 2 Washer 3 Rubber plate 4 Row cork or rubber sheet 5 Ground 6 Concrete floor 7 Ditch Figure 4 Unit Levelling Fix anchor bolts into the con...

Page 17: ...antee the cleaning of the water pipes between the water filter and the BPHE Recommended maximum opening for strainer mesh is 0 87 mm DX S T 1 0 mm BPHE 1 2 mm Flooded Precautions for correct use 9 BPH...

Page 18: ...ection pipes prior the operation see figure Connecting the filter The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied Victaulic coup...

Page 19: ...nge as specified in the table below and a minimum water volume is required in the system Model Minimum water flow l min Maximum water flow l min EWWD120J EWLD110J EWWH090J EWLH080J EWWS120J EWLS110J 1...

Page 20: ...anti freeze electrical resistance which provides adequate anti freeze protection at temperatures as low as 18 C However unless the heat exchangers are completely empty and cleaned with anti freeze so...

Page 21: ...gram terminals L1 L2 and L3 5 Supply water to the evaporator and verify if waterflow is within the limits as given in the table under Water charge flow and quality 6 The piping must be completely purg...

Page 22: ...e used For copper to copper joints use a phos copper solder with 6 to 8 silver content A high silver content brazing rod must be used for copper to brass or copper to steel joints Only use oxy acetyle...

Page 23: ...must be between 3 and 8 K c Verify the oil sight glass Level must be within the sight glass d Verify the liquid line sight glass It should be sealed and not indicate moisture in the refrigerant e As l...

Page 24: ...D EIMWC01008 16_03EN 24 35 Figure 5 Condenser located with no elevation difference Figure 6 Condenser located above the unit...

Page 25: ...alves etc Table 2 shows the equivalent length of pipe for various nonferrous valves and fittings Follow these steps when calculating line size 1 Start with an initial approximation of equivalent lengt...

Page 26: ...oling may be affected In these situations insulate the liquid lines Reference for liquid line sizing is shown in Table 3 It has to be used for reference only for circuit working with condensing temper...

Page 27: ...234ze R513A 6 2 4 Oil charge In remote condenser application the oil charge into the compressor has to take into account that a percentage of oil around 1 is usually mixed into the refrigerant so some...

Page 28: ...dards for industrial environments Therefore it is not intended for use in residential areas e g installations where the product is connected to a low voltage public distribution system Should this pro...

Page 29: ...al areas e g installations where the product is connected to a low voltage public distribution system Should this product need to be connected to a low voltage public distribution system specific addi...

Page 30: ...operating manual and the wiring diagram in order to understand start up sequence operation shutdown sequence and operation of all the safety devices During the unit s initial start up phase a technici...

Page 31: ...sure that the work area is properly ventilated before working on the refrigerant circuit or before welding brazing or soldering work ensure that the leak detection equipment being used is non sparking...

Page 32: ...be read on a daily basis thus keeping high observation standards 4 Replace the oil filter when the pressure drop across it reaches 2 0 bar 5 Check for any dissolved metals TAN Total Acid Number 0 10...

Page 33: ...unbalance between phases exceeding 3 The unit must stay turned off until the electrical problem has been solved 4 No safety device either mechanical electrical or electronic must be disabled or overri...

Page 34: ...ed inside the electrical panel Fill in with indelible ink the refrigerant charge label supplied with the product as following instructions Any refrigerant charge for each circuit 1 2 3 added during co...

Page 35: ...e of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe...

Reviews: