background image

D-EIMWC01206-15EN - 9/20 

 

EWWQ180L 

5.38 

11.21 

EWWQ205L 

6.17 

12.86 

EWWQ230L 

7.01 

14.61 

EWWQ260L 

7.82 

16.30 

EWWQ290L 

8.70 

18.13 

EWWQ330L 

9.89 

20.60 

EWWQ380L 

11.11 

23.14 

EWWQ430L 

12.35 

25.73 

EWWQ480L 

13.66 

28.46 

EWWQ540L 

15.77 

32.86 

EWWQ600L 

17.56 

36.58 

EWWQ660L 

19.06 

39.71 

EWWQ720L 

20.74 

43.21 

EWLQ Model  

Minimum water 

flow 

l/s

 

Maximum 

water flow 

l/s

 

EWLQ090G 

2.50 

5.21 

EWLQ100G 

2.85 

5.94 

EWLQ120G 

3.19 

6.65 

EWLQ130G 

3.61 

7.53 

EWLQ150G 

4.02 

8.38 

EWLQ170G 

4.61 

9.61 

EWLQ190G 

5.24 

10.91 

EWLQ210G 

5.90 

12.30 

EWLQ240G 

6.61 

13.76 

EWLQ300G 

8.39 

17.48 

EWLQ360G 

10.00 

20.83 

EWLQ180L 

4.97 

10.36 

EWLQ205L 

5.67 

11.81 

EWLQ230L 

6.42 

13.38 

EWLQ260L 

7.13 

14.86 

EWLQ290L 

8.00 

16.68 

EWLQ330L 

9.09 

18.94 

EWLQ380L 

10.37 

21.60 

EWLQ430L 

11.75 

24.48 

EWLQ480L 

13.16 

27.43 

EWLQ540L 

14.69 

30.60 

EWLQ600L 

16.40 

34.16 

EWLQ660L 

17.92 

37.33 

EWLQ720L 

19.43 

40.49 

EWHQ Model 

Minimum water 

flow 

l/s

 

Maximum 

water flow 

l/s

 

EWHQ100G 

3.80 

7.91 

EWHQ120G 

4.19 

8.74 

EWHQ130G 

4.77 

9.94 

EWHQ150G 

5.41 

11.26 

EWHQ160G 

5.98 

12.45 

EWHQ190G 

6.83 

14.24 

EWHQ210G 

7.80 

16.25 

EWHQ240G 

8.95 

18.64 

EWHQ270G 

9.94 

20.71 

EWHQ340G 

12.51 

26.06 

EWHQ400G 

14.82 

30.88 

 

To ensure the correct operation of the unit, the flow of 
water in the evaporator must fall within the operating 
sphere specified in the preceding table and there must 
be a minimum volume of water in the system. 
The distribution circuits of the cold water should have a 
minimum content of water to avoid an excessive 
number of start-up and shut-downs of the compressor. 
In fact, every time the compressor goes into operation, 
an excessive amount of oil from the compressor starts 
circulating in the refrigerant circuit and at the same time 
there is an increase of the temperature of the 
compressor stator, generated by the inrush current of 
the start-up.  Therefore to avoid damages to the 
compressors, the application of a device has been 
planned to limit frequent shut-downs and start-ups: in 

one hour, there will only be 6 start-ups of the 
compressor.                
The system where the unit is installed must therefore 
ensure that the overall content of water allows the unit t 
operate continuously and therefore greater 
environmental comfort. The minimum water content per 
unit must be calculated with a certain approximation 
using the following formula: 
 

For units with 2 compressors: 
 

M(litres) = (12.153 x DT (°C) 

– 22.168) x P(kW) 

 

For units with 4 compressors: 
 

M(litres) = (0.32 x DT (°C) +1,36) x P(kW) 
 
Where: 
M = minimum content of water per unit expressed in 
litres 
P = refrigerating capacity of the unit express in kW 
ΔT = difference in temperature of the incoming and 
outgoing water, expressed in °C. 
 
This formula is valid with the standard parameters of 
the microprocessor. To determine most accurately the 
quantity of water, we recommend contacting the 
designer of the system. 
 

Anti-freeze protection for evaporators and recovery 
exchangers  

When the entire system of the cooling or heating 
installation is being designed, two or more of the 
following anti-freeze protection methods should be 
considered at the same time: 
1.  Continuous circulation of the flow of water inside the 

exchangers 

2.  Additional heat insulation and heating of exposed 

piping 

3.  Emptying and cleaning of the heat exchanger during 

the winter and its maintenance with anti-oxidant 
atmosphere (nitrogen). 

 
As an alternative, it is possible to add an appropriate 
amount of glycol (antifreeze) to the water circuit. 
 
The installer and/or the local personnel assigned to 
maintenance must make sure that anti-freeze protection 
methods are in use and ensure that the appropriate 
maintenance operations of the antifreeze protection 
devices are always carried out. Failing to follow the 
instructions above could result in unit damage. Damage 
caused by freezing is not covered by the warranty.  
 

Electrical system General Specifications 

The units must be connected to a TN power supply 
system. 
If the units must be connected to a different type of 
power system, for example the IT system, please 
contact the factory. 

 

All the electrical connections to the unit must 
be carried out in compliance with national laws 
and European directives and regulations in 
force. 
 

All installation, management and maintenance activities 
must be carried out by qualified personnel. 

Summary of Contents for EWLQ Series

Page 1: ...manual EWWQ090G EWWQ720L Water cooled scroll chillers EWLQ090G EWLQ720L Condenserless EWHQ100G EWHQ400G Heat pump scroll chillers Refrigerant R410A D EIMWC01206 15EN REV 00 Date Supersedes EWLQ G L C...

Page 2: ...unit can be seasonally inverted General Information All the units are delivered together withwiring diagrams certifieddrawings nameplateandDoC DeclarationofConformity Thesedocumentslistallthe technica...

Page 3: ...t Identification of the labels 1 Manufacturer s logo 5 Hazardous voltage warning 2 Type of coolant in the circuit s 6 Non flammable gas symbol 3 Electrical hazard symbol 7 Identification data of the u...

Page 4: ...ency Service wait without leaving the injured person alone until the rescue operators come Give all necessary information to the rescue operators Positioning and assembly The unit must be installed on...

Page 5: ...he unit very slowly keeping it perfectly level Avoid bumping and or shaking the unit during the handling and loading unloading operations from the transportation vehicle push or pull the unit only usi...

Page 6: ...re 4 Handling of the double circuit unit Alternative handling method 1 Remove before installation 2 Use lifting hooks with closing device exclusively The hooks must be safely fastened before performin...

Page 7: ...es not exceed the design pressure of the water side heat exchangers and install a safety valve on the pipe of the water 12 Install a suitable expansion CAUTION To avoid damages install a filter that c...

Page 8: ...onsible for any damages or malfunctions of the equipment The quality of the water must comply with the specifications listed in the following table Circulating water Water supply Possible problems Ele...

Page 9: ...installed must therefore ensure that the overall content of water allows the unit t operate continuously and therefore greater environmental comfort The minimum water content per unit must be calculat...

Page 10: ...other components of the system or other appliances in general 2 Plan an electrical circuit for the connection of the unit This circuit must be protected with the necessary safety devices that is a ma...

Page 11: ...quence and operation of all the safety devices The user must keep a log system booklet of the operating data of the unit installed and of all the periodic maintenance and service activities If the ope...

Page 12: ...ranty All the units are tested at the factory and guaranteed for a specific period of time These units have been developed and constructed according to high quality standards ensuring years of failure...

Page 13: ...stalled in an aggressive environment perform this activity monthly The following are considered aggressive environments place with high concentration of industrial exhaust gas in the air Place close t...

Page 14: ...collection centres This manual is a technical aid and does not represent a binding offer We cannot guarantee explicitly or implicitly the completeness accuracy or reliability of its contents All data...

Page 15: ...requency Drive condenser pump VFD 3 Way Valve VFD 3 Way Valve VFD Fans D L Limit of charge DI Digital Inputs DO Digital Outputs DPS Digital Setpoint EF External Fault EFS Evaporator Flow Switch GA Gen...

Page 16: ...e A Typical single refrigerant circuit The input and output of the water of the condenser and the evaporator are approximate Consult the dimensional drawings of the unit for the exact hydraulic connec...

Page 17: ...Figure B Typical single refrigerant circuit of the moto evaporating version The input and output of the water of the evaporator are approximate Consult the dimensional drawings of the unit for the exa...

Page 18: ...Figure C Typical single refrigerant circuit for Heat Pump The input and output of the water of the condenser and the evaporator are approximate Consult the dimensional drawings of the unit for the exa...

Page 19: ...r 17 Refrigerant inlet connection from the remote condenser 18 Condenser leaving water connection 19 Condenser entering water connection 20 Evaporator leaving water connection 21 Evaporator entering w...

Page 20: ...cy reliability or fitness for particular purpose of its content and the products and services presented therein Specifications are subject to change without prior notice Daikin Europe N V explicitly r...

Reviews: