4.  SELECTION OF LOCATION 

 

          The units are designed for indoor installation and should 
           be installed in a location that meets the following  
           requirements:    

1. 

  The foundation is strong enough to support the 

weight of the unit and the floor is flat to prevent 
vibration and noise generation. 

2. 

  The space around the unit is adequate for 

servicing. 

3. 

  There is no danger of fire due to leakage of   

infiammable gas. 

4. 

  Select the location of the unit in such a way that the 

sound generated by to the unit does not disturb 
anyone. 

5. 

  Ensure that water cannot cause any damage to the 

location in case it drips out the unit. 
 

NOTE     

Pull-down operation is restricted to one 

               hour maximum. 
 
 

5.  INSPECTING AND HANDLING THE 

UNIT 

   

At delivery, the unit should be checked and any damage 
should be reported immediately to the carrier claims 
agent. 

               

 

            
          When handling the unit, take into account the following: 
  

1. 

List the unit preferably with a crane and belts in 
accordance with the instructions on the unit. 
The length of the ropes (1) to be used for lifting are  
4 m minimum each. 
 

2. 

The unit is shipped with wooden beams (2) under it,    

these have to be removed before installation. 

 
       

NOTE     

Try to reduce the drilling in the unit to a  

                      

minimum. It drilling is impreventable,  

                      remove the iron filling thoroughly in order  
                      to prevent  surface rust. 
 

          
 
  
 

6.  UNPACKING AND PLACING THE 

UNIT 

 

1.    Remove the wooden beams from the unit. 
 

2.    Install vibration mountings in case of an 

installation where noise and vibration might 
an impediment. 

 

3.    Set the unit on a solid and level foundation. 

 

The unit should be installed on a solid base. It 
is recommended to fix the unit on a concrete 
base with anchor bolts. 

 

 

 

 
       

1. 

Anchor bolt 

2. 

Washer 

3. 

Rubber plate 

4. 

Row cork or rubber sheet 

5. 

Ground 

6. 

Concrete floor 

7. 

Ditch 
 

 

Fix  anchor  bolts into  the  concrete  foundation. 
When  finally  fixing  the  unit  by  means  of 
these  anchor  bolts,  make  sure    that  the 
washers  for  channel  DIN434, and  both  field 
supplied  rubber plates  and  field  supplied  raw 
cork  or  rubber  sheets  for    better  vibration 
protection, are installed as indicated. 

 

The   concrete   foundation   should  
approximately  be   100 mm higher than the 
floor level for ease of plumbing work and 
better drain. 

 
 
 
 
 
 
 
 
 
 

Model 

Anchor bolt 

  Size             Qty 

EWWD120J~180J 
EWLD 110J~165J 
EWWH090J-130J 
EWLH080J-130J 
EWWS120J-180J 
EWLS110J-170J 

300 

M20x200 

EWWD210J~280J 
EWLD 195J~265J 
EWWH150J-200J 
EWLH140J-190J 
EWWS200J-270J 

350 

M20x200 

 

 

Make sure that the foundation surface is even and flat 

NOTE

 

 

The  measurement  tabulated is  based  on  the  fact 
the  base  is  made in the  ground  or  on  a  concrete 
floor. In  case the base is made on a rigid floor, it is 
possible  to  include  thickness  of  concrete  floor  in 
that of the base. 

Summary of Contents for EWWD J Series

Page 1: ... water cooled screw chillers EWLD110J SS EWLD265J SS EWLH 80J SS EWLH190J SS EWLS 110J SS EWLS270J SS Refrigerant R 134a R1234ze R513A English 2 Deutsch 13 Français 25 Nederlands 36 Español 48 Italiano 60 Ελληνικά 72 Português 84 Русский 96 Swedish 107 Norsk 118 Finnish Suomi 129 Polski 140 Čech 152 Hrvat 163 Magyar 174 Român 185 Slovenski 196 Български 207 Slovenský 219 Installation Operation and...

Page 2: ...d to replace such personnel EWWD120J SS 280J SS EWWH090J SS 200J SS EWWS120J SS 270J SS EWLD 110J SS 265J SS EWLH 80J SS 190J SS EWLS 110J SS 270J SS Label Identification 1 Unit nameplate data 5 Manufacturer s logo 2 Lifting instructions 6 Emergency stop 3 Hazardous Voltage warning 7 Non flammable gas symbol 4 Electrical hazard symbol 8 Gas type ...

Page 3: ...R1234ZE 9 8 5 ADDITIONAL GUIDELINES FOR SAFE USE OF R1234ZE E FOR EQUIPMENT LOCATED IN THE OPEN AIR 9 8 6 ADDITIONAL GUIDELINES FOR SAFE USE OF R1234ZE E FOR EQUIPMENT LOCATED IN A MACHINERY ROOM 9 9 MAINTENANCE 10 9 1 ROUTINE MAINTENANCE FOR R1234ZE 10 10 EWLD J EWLH AND EWLS VERSIONS 11 10 1 PRECAUTIONS WHEN HANDLING PIPING 11 10 2 LEAK TEST AND VACUUM DRYING 11 10 3 CHARGING THE UNIT 11 11 PREP...

Page 4: ...OPER INSTALLATION OR ATTACHEMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUIPMENT BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL IF UNSURE OF INSTALLATION PROCEDURES OR USE ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATI...

Page 5: ... 1600 1607 Operation weight Kg 1663 1675 Connections Chilled water inlet outlet 2 inch 3 Condenser water inlet outlet 2 inch 4 2 Victaulic coupling Model EWLD J 110 130 145 165 195 Dimensions HxWxL mm 1020x913x2726 Weight Unit weight Kg 1086 1101 1169 1164 1236 Operation weight Kg 1090 1114 1183 1183 1263 Connections Chilled water inlet outlet 2 inch 3 Liquid line inlet connection 3 inch 1 3 8 Gas...

Page 6: ...tion with Glycol Fixed minimum capacity at 100 2 Operation with Glycol below 4 C Evap LWT 3 Some units could work partialized in this area EWWH J EWLH J 1 Operation with Glycol Fixed minimum capacity at 100 2 Operation with Glycol below 4 C Evap LWT 3 Operation with fixed minimum capacity at 100 EWWS J EWLS J 1 Operation with Glycol below 4 C Evap LWT 2 Some units could work partialized in this ar...

Page 7: ...ling in the unit to a minimum It drilling is impreventable remove the iron filling thoroughly in order to prevent surface rust 6 UNPACKING AND PLACING THE UNIT 1 Remove the wooden beams from the unit 2 Install vibration mountings in case of an installation where noise and vibration might an impediment 3 Set the unit on a solid and level foundation The unit should be installed on a solid base It is...

Page 8: ...21 66 19 33 10 2 01 9 4 01 29 7 27 48 12 53 67 19 78 9 2 09 10 4 15 30 7 48 49 12 85 68 20 23 8 2 17 11 4 29 31 7 70 50 13 18 69 20 69 7 2 26 12 4 43 32 7 92 51 13 51 70 21 16 6 2 34 13 4 58 33 8 15 52 13 85 71 21 64 5 2 43 14 4 73 34 8 39 53 14 20 72 22 13 4 2 53 15 4 88 35 8 63 54 14 55 73 22 62 3 2 62 16 5 04 36 8 87 55 14 91 74 23 12 2 2 72 17 5 20 37 9 12 56 15 28 75 23 63 1 2 82 18 5 37 38 9...

Page 9: ...mity with the directives along with the documentation Before machine installation and commissioning the people involved in this activity must have acquired the information necessary to carry out these tasks applying all the information collected in this book Do not allow unauthorized and or unskilled personnel to access the unit The chiller has to be installed in open air or machinery room locatio...

Page 10: ...be done with due consideration of local airflow patterns accounting for location sources of ventilation and louvers Consideration shall also be given to the possibility of mechanical damage or contamination At least one detector shall be installed in each machinery room or the occupied space being considered and or at the lowest underground room for refrigerants heavier than air and at the highest...

Page 11: ... technicians Before beginning any work on the system the personnel shall assure that all security precautions have been taken Always protect the operating personnel with personal protective equipment appropriate for the tasks to be performed Common individual devices are Helmet goggles gloves caps safety shoes Additional individual and group protective equipment should be adopted after an adequate...

Page 12: ...h the product NOTE Take care for contamination of the remote condenser In order to avoid blocking of the system It is impossible for the manufacturer to control the contamination of the foreign condenser of the installer The unit has a strict contamination level 11 PREPARING CHECKING AND CONNECTING THE WATER CIRCUIT The units are equipped with a water inlet and water outlet for connection to a chi...

Page 13: ...ransmitting vibration and noise 6 For units in double circuit configuration with common leaving water control ELWT be sure to foresee an insertion hole for the additional water temperature sensor Sensor and sensor holder are optional parts The insertion hole shall be 1 4 GAS female thread and should be located in the mixed waterflow of the chillers Make sure that the sensortip is in the waterflow ...

Page 14: ...e relef valve on the condenser and pipe to each pressure relief valve on the evaporator Cross section and length of the discharge line must comply with local codes 15 FIELD WIRING All field wiring and components must be installed by a licensed electrician and must compy with relevant European and national regulations The field wiring must be carried out in accordance with the wiring diagram suppli...

Page 15: ... sent to specific refuse collection centres Oil must be collected and sent to specific refuse collection centres 16 BEFORE STARTING The unit should not be started not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off va...

Page 16: ...mp VFD D L Demand Limit DI Digital Inputs DO Digital Outputs DPS Double Set Point EF Esternal Fault EFS Evaporator Flow Switch EFS 1 Evaporator Flow Switch 1 EFS 2 Evaporator Flow Switch 2 GA General Alarm KPC Condensator Water Pump KPE 1 Evaporator Water Pump 1 KPE 2 Evaporator Water Pump 2 PS Power Supply Q10 Main Switch S O Setpoint Override TW1 Tower 1 Fan Step TW2 Tower 2 Fan Step TW3 Tower 3...

Page 17: ...D EIMWC01006 11EU 17 20 17 FACTORY AND FIELD CHARGED UNITS INSTRUCTIONS Errore Non si possono creare oggetti dalla modifica di codici di campo 18 FIELD CHARGED UNITS INSTRUCTIONS ...

Page 18: ...frigerant charge Factory Field h Greenhouse gas emission of the total refrigerant charge expressed as tonnes of CO2 equivalent m Refrigerant type n GWP Global Warming Potential p Unit serial number 2 The filled out label must be adhered inside the electrical panel Periodical inspections for refrigerant leaks may be required depending on European or local legislation Please contact your local deale...

Page 19: ... of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publication All content is copyrighted by...

Page 20: ...D EIMWC01006 11EU 20 20 ...

Reviews: