In  case  a  base  is  made  on  concrete  floor,  make 
sure to provide a ditch as shown. It  is important to 
extract  drainage  regardless of  whether  a  base  is 
made in the ground or on the concrete floor (ditch- 
sewerage). 

 

 

Ingredient ratio of the concrete is: cement 1, sand 
2  and  gravel  3.  Insert  iron  bars  of  Ø10  at  every 
interval  of  300 mm.  The  edge  of  the  concrete 
base should be planed. 
 
 

 

7.  IMPORTANT INFORMATION 

REGARDING THE REFRIGERANTS  
USED 

 

This  product  contains  fluorinated  greenhouse  gases.  Do  not 
vent gases into the atmosphere. 
 

Model 

EWWD J 

EWLD J 

EWWH J 

EWLH J 

EWWS J 
 EWLS J 

Refrigerant type 

R134a 

R1234ze 

R513A 

GWP(1) value 

1430 

572 

 

 

(1) GWP = global warming potential 
 
For  the 

EWWD  J,  EWWH  J  and  EWWS  J

  unit  versions  the 

quantity is indicated on the unit name plate. 
 
For the 

EWLD J, EWLH J and EWLS J

 unit versions, please 

fill  the  total  refrigerant  charge  in  with  indelible  ink  on  the 
refrigerant charge label supplied with the product. 
The  filled  out  label  must  be  adhered  inside  the  electric  panel 
door. 
 
Refrigerants  R134a,  R1234ze(E) and  R513A  are  classified  by 
European  Directive  2014/68/EU  as  Group  2  (non-dangerous) 
substances  as  it  is  nonflammable  at  standard  ambient 
temperature and non-toxic. Due to this, no special precautions 
are required for storage, transport and handling.  
Daikin Applied  Europe S.p.A.  products comply  with  applicable 
European  Directives  and  refer  for  unit  design  to  product 
Standard EN378:2016 and industrial Standard ISO5149. Local 
authorities  approval  should  be  verified  referring  to  European 
Standard  EN378  and/or  ISO  5149  (where  R134a  and  R513A 
are  classified  A1,  and  R1234ze(E)  is  classified  A2L 

–  Mildly 

flammable gas). 
 
 
 
 
 
 
 

7.1.  Pressure/temperature table 
 

 R134a 

 

R134a Pressure/ Temperature conversion table 

°C 

bar 

°C 

bar 

°C 

bar 

°C 

bar 

°C 

bar 

-15 

1,64 

3,38 

23 

6,27 

43 

11,01 

62 

17,62 

-14 

1,71 

3,50 

25 

6,46 

44 

11,30 

63 

18,04 

-13 

1,78 

3,62 

26 

6,65 

45 

11,60 

64 

18,46 

-12 

1,85 

3,75 

27 

6,85 

46 

11,90 

65 

18,89 

-11 

1,93 

3,88 

28 

7,06 

47 

12,21 

66 

19,33 

-10 

2,01 

4,01 

29 

7,27 

48 

12,53 

67 

19,78 

-9 

2,09 

10 

4,15 

30 

7,48 

49 

12,85 

68 

20,23 

-8 

2,17 

11 

4,29 

31 

7,70 

50 

13,18 

69 

20,69 

-7 

2,26 

12 

4,43 

32 

7,92 

51 

13,51 

70 

21,16 

-6 

2,34 

13 

4,58 

33 

8,15 

52 

13,85 

71 

21,64 

-5 

2,43 

14 

4,73 

34 

8,39 

53 

14,20 

72 

22,13 

-4 

2,53 

15 

4,88 

35 

8,63 

54 

14,55 

73 

22,62 

-3 

2,62 

16 

5,04 

36 

8,87 

55 

14,91 

74 

23,12 

-2 

2,72 

17 

5,20 

37 

9,12 

56 

15,28 

75 

23,63 

-1 

2,82 

18 

5,37 

38 

9,37 

57 

15,65 

76 

24,15 

2,93 

19 

5,54 

39 

9,63 

58 

16,03 

77 

24,68 

3,04 

20 

5,72 

40 

9,89 

59 

16,42 

78 

25,22 

3,15 

21 

5,90 

41 

10,16 

60 

16,81 

79 

25,77 

3,26 

22 

6,08 

42 

10,44 

61 

17,22 

80 

26,32 

 

R513A 

 

R513A Pressure/ Temperature conversion table 

°C 

bar 

°C 

bar 

°C 

bar 

°C 

bar 

°C 

bar 

-
15 

1,87 

3,73 

23 

6,74 

43 

11,58 

62 

18,25 

-
14 

1,94 

3,85 

25 

6,93 

44 

11,88 

63 

18,66 

-
13 

2,02 

3,98 

26 

7,13 

45 

12,18 

64 

19,09 

-
12 

2,10 

4,11 

27 

7,34 

46 

12,49 

65 

19,52 

-
11 

2,18 

4,25 

28 

7,55 

47 

12,80 

66 

19,96 

-
10 

2,27 

4,39 

29 

7,77 

48 

13,12 

67 

20,40 

-9 

2,35 

10 

4,53 

30 

7,99 

49 

13,44 

68 

20,86 

-8 

2,44 

11 

4,68 

31 

8,21 

50 

13,77 

69 

21,32 

-7 

2,53 

12 

4,83 

32 

8,44 

51 

14,11 

70 

21,79 

-6 

2,63 

13 

4,98 

33 

8,67 

52 

14,46 

71 

22,27 

-5 

2,72 

14 

5,14 

34 

8,91 

53 

14,81 

72 

22,75 

-4 

2,82 

15 

5,30 

35 

9,16 

54 

15,16 

73 

23,24 

-3 

2,93 

16 

5,47 

36 

9,41 

55 

15,52 

74 

23,75 

-2 

3,03 

17 

5,64 

37 

9,66 

56 

15,89 

75 

24,26 

-1 

3,14 

18 

5,81 

38 

9,92 

57 

16,27 

76 

24,78 

3,25 

19 

5,99 

39 

10,18 

58 

16,65 

77 

25,30 

3,36 

20 

6,17 

40 

10,45 

59 

17,04 

78 

25,84 

3,48 

21 

6,35 

41 

10,72 

60 

17,43 

79 

26,38 

3,60 

22 

6,54 

42 

11,00 

61 

17,84 

80 

26,94 

 
 
 
 
 
 
 
 
 
 
 
 

R1234ze (E) 

 

HFO-R1234ze(E) Pressure/ Temperature conversion table 

°C 

bar  

°C 

bar 

°C 

bar 

°C 

bar 

°C 

bar 

-15 

1,20 

2,50 

23 

4,69 

43 

8,31 

62 

13,39 

-14 

1,25 

2,59 

25 

4,84 

44 

8,53 

63 

13,71 

-13 

1,30 

2,69 

26 

4,98 

45 

8,76 

64 

14,03 

-12 

1,36 

2,78 

27 

5,14 

46 

8,99 

65 

14,36 

-11 

1,42 

2,88 

28 

5,29 

47 

9,23 

66 

14,70 

-10 

1,47 

2,98 

29 

5,45 

48 

9,47 

67 

15,04 

-9 

1,53 

10 

3,08 

30 

5,62 

49 

9,72 

68 

15,39 

-8 

1,60 

11 

3,19 

31 

5,78 

50 

9,97 

69 

15,75 

-7 

1,66 

12 

3,30 

32 

5,95 

51 

10,23 

70 

16,11 

-6 

1,73 

13 

3,41 

33 

6,13 

52 

10,49 

71 

16,48 

-5 

1,79 

14 

3,52 

34 

6,31 

53 

10,76 

72 

16,85 

-4 

1,86 

15 

3,64 

35 

6,49 

54 

11,03 

73 

17,23 

-3 

1,94 

16 

3,76 

36 

6,67 

55 

11,30 

74 

17,62 

-2 

2,01 

17 

3,88 

37 

6,86 

56 

11,58 

75 

18,01 

-1 

2,09 

18 

4,01 

38 

7,06 

57 

11,87 

76 

18,41 

Summary of Contents for EWWD J Series

Page 1: ... water cooled screw chillers EWLD110J SS EWLD265J SS EWLH 80J SS EWLH190J SS EWLS 110J SS EWLS270J SS Refrigerant R 134a R1234ze R513A English 2 Deutsch 13 Français 25 Nederlands 36 Español 48 Italiano 60 Ελληνικά 72 Português 84 Русский 96 Swedish 107 Norsk 118 Finnish Suomi 129 Polski 140 Čech 152 Hrvat 163 Magyar 174 Român 185 Slovenski 196 Български 207 Slovenský 219 Installation Operation and...

Page 2: ...d to replace such personnel EWWD120J SS 280J SS EWWH090J SS 200J SS EWWS120J SS 270J SS EWLD 110J SS 265J SS EWLH 80J SS 190J SS EWLS 110J SS 270J SS Label Identification 1 Unit nameplate data 5 Manufacturer s logo 2 Lifting instructions 6 Emergency stop 3 Hazardous Voltage warning 7 Non flammable gas symbol 4 Electrical hazard symbol 8 Gas type ...

Page 3: ...R1234ZE 9 8 5 ADDITIONAL GUIDELINES FOR SAFE USE OF R1234ZE E FOR EQUIPMENT LOCATED IN THE OPEN AIR 9 8 6 ADDITIONAL GUIDELINES FOR SAFE USE OF R1234ZE E FOR EQUIPMENT LOCATED IN A MACHINERY ROOM 9 9 MAINTENANCE 10 9 1 ROUTINE MAINTENANCE FOR R1234ZE 10 10 EWLD J EWLH AND EWLS VERSIONS 11 10 1 PRECAUTIONS WHEN HANDLING PIPING 11 10 2 LEAK TEST AND VACUUM DRYING 11 10 3 CHARGING THE UNIT 11 11 PREP...

Page 4: ...OPER INSTALLATION OR ATTACHEMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUIPMENT BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL IF UNSURE OF INSTALLATION PROCEDURES OR USE ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATI...

Page 5: ... 1600 1607 Operation weight Kg 1663 1675 Connections Chilled water inlet outlet 2 inch 3 Condenser water inlet outlet 2 inch 4 2 Victaulic coupling Model EWLD J 110 130 145 165 195 Dimensions HxWxL mm 1020x913x2726 Weight Unit weight Kg 1086 1101 1169 1164 1236 Operation weight Kg 1090 1114 1183 1183 1263 Connections Chilled water inlet outlet 2 inch 3 Liquid line inlet connection 3 inch 1 3 8 Gas...

Page 6: ...tion with Glycol Fixed minimum capacity at 100 2 Operation with Glycol below 4 C Evap LWT 3 Some units could work partialized in this area EWWH J EWLH J 1 Operation with Glycol Fixed minimum capacity at 100 2 Operation with Glycol below 4 C Evap LWT 3 Operation with fixed minimum capacity at 100 EWWS J EWLS J 1 Operation with Glycol below 4 C Evap LWT 2 Some units could work partialized in this ar...

Page 7: ...ling in the unit to a minimum It drilling is impreventable remove the iron filling thoroughly in order to prevent surface rust 6 UNPACKING AND PLACING THE UNIT 1 Remove the wooden beams from the unit 2 Install vibration mountings in case of an installation where noise and vibration might an impediment 3 Set the unit on a solid and level foundation The unit should be installed on a solid base It is...

Page 8: ...21 66 19 33 10 2 01 9 4 01 29 7 27 48 12 53 67 19 78 9 2 09 10 4 15 30 7 48 49 12 85 68 20 23 8 2 17 11 4 29 31 7 70 50 13 18 69 20 69 7 2 26 12 4 43 32 7 92 51 13 51 70 21 16 6 2 34 13 4 58 33 8 15 52 13 85 71 21 64 5 2 43 14 4 73 34 8 39 53 14 20 72 22 13 4 2 53 15 4 88 35 8 63 54 14 55 73 22 62 3 2 62 16 5 04 36 8 87 55 14 91 74 23 12 2 2 72 17 5 20 37 9 12 56 15 28 75 23 63 1 2 82 18 5 37 38 9...

Page 9: ...mity with the directives along with the documentation Before machine installation and commissioning the people involved in this activity must have acquired the information necessary to carry out these tasks applying all the information collected in this book Do not allow unauthorized and or unskilled personnel to access the unit The chiller has to be installed in open air or machinery room locatio...

Page 10: ...be done with due consideration of local airflow patterns accounting for location sources of ventilation and louvers Consideration shall also be given to the possibility of mechanical damage or contamination At least one detector shall be installed in each machinery room or the occupied space being considered and or at the lowest underground room for refrigerants heavier than air and at the highest...

Page 11: ... technicians Before beginning any work on the system the personnel shall assure that all security precautions have been taken Always protect the operating personnel with personal protective equipment appropriate for the tasks to be performed Common individual devices are Helmet goggles gloves caps safety shoes Additional individual and group protective equipment should be adopted after an adequate...

Page 12: ...h the product NOTE Take care for contamination of the remote condenser In order to avoid blocking of the system It is impossible for the manufacturer to control the contamination of the foreign condenser of the installer The unit has a strict contamination level 11 PREPARING CHECKING AND CONNECTING THE WATER CIRCUIT The units are equipped with a water inlet and water outlet for connection to a chi...

Page 13: ...ransmitting vibration and noise 6 For units in double circuit configuration with common leaving water control ELWT be sure to foresee an insertion hole for the additional water temperature sensor Sensor and sensor holder are optional parts The insertion hole shall be 1 4 GAS female thread and should be located in the mixed waterflow of the chillers Make sure that the sensortip is in the waterflow ...

Page 14: ...e relef valve on the condenser and pipe to each pressure relief valve on the evaporator Cross section and length of the discharge line must comply with local codes 15 FIELD WIRING All field wiring and components must be installed by a licensed electrician and must compy with relevant European and national regulations The field wiring must be carried out in accordance with the wiring diagram suppli...

Page 15: ... sent to specific refuse collection centres Oil must be collected and sent to specific refuse collection centres 16 BEFORE STARTING The unit should not be started not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off va...

Page 16: ...mp VFD D L Demand Limit DI Digital Inputs DO Digital Outputs DPS Double Set Point EF Esternal Fault EFS Evaporator Flow Switch EFS 1 Evaporator Flow Switch 1 EFS 2 Evaporator Flow Switch 2 GA General Alarm KPC Condensator Water Pump KPE 1 Evaporator Water Pump 1 KPE 2 Evaporator Water Pump 2 PS Power Supply Q10 Main Switch S O Setpoint Override TW1 Tower 1 Fan Step TW2 Tower 2 Fan Step TW3 Tower 3...

Page 17: ...D EIMWC01006 11EU 17 20 17 FACTORY AND FIELD CHARGED UNITS INSTRUCTIONS Errore Non si possono creare oggetti dalla modifica di codici di campo 18 FIELD CHARGED UNITS INSTRUCTIONS ...

Page 18: ...frigerant charge Factory Field h Greenhouse gas emission of the total refrigerant charge expressed as tonnes of CO2 equivalent m Refrigerant type n GWP Global Warming Potential p Unit serial number 2 The filled out label must be adhered inside the electrical panel Periodical inspections for refrigerant leaks may be required depending on European or local legislation Please contact your local deale...

Page 19: ... of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publication All content is copyrighted by...

Page 20: ...D EIMWC01006 11EU 20 20 ...

Reviews: