background image

 

 

D-EIMWC01008-16_03EN - 5/35 

INTRODUCTION 

This manual is an important supporting document for qualified personnel but it is not intended to replace such 
personnel. 

 

 

READ THIS MANUAL CAREFULLY BEFORE INSTALLING AND STARTING UP THE UNIT.   
IMPROPER INSTALLATION COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, 
LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT OR INJURE TO PEOPLE. 

 

 

THE UNIT MUST BE INSTALLED BY A PROFESSIONAL OPERATOR/TECHNICIAN  
UNIT STARTUP HAS TO BE PERFORMED BY AUTHORIZED AND TRAINED 
PROFESSIONAL 
ALL ACTIVITIES HAVE TO BE PERFORMED ACCORDING TO LOCAL LAWS AND 
REGULATION. 

 

 

UNIT INSTALLATION AND START UP IS ABOSOLUTELY FORBIDDEN IF ALL 
INSTRUCTION CONTAINED IN THIS MANUAL ARE NOT CLEAR. 
IF CASE OF DOUBT CONTACT THE MANUFACTURER REPRESENTATIVE FOR ADVICE 
AND INFORMATION. 

 
 

1.1 

Precautions against residual risks  

1.  install the unit according to the instructions set out in this manual

 

2.  regularly carry out all the maintenance operations foreseen in this manual 
3.  wear protective equipment (gloves, eye protection, hard hat, etc.) suited to the work in hand; do not wear clothes 

or accessories that can get caught or sucked in by flows of air; tie back long hair before entering the unit 

4.  before opening the machine panelling make sure that it is firmly hinged to the machine  
5.  the fins on heat exchangers and the edges of metal components and panels can cause cuts  
6.  do not remove the guards from mobile components while the unit is operating 
7.  make sure that mobile component guards are fitted correctly before restarting the unit  
8.  fans, motors and belts drives might be running: before entering, always wait for these to stop and take appropriate 

measures to prevent them from starting up 

9.  the surfaces of the machine and pipes can get very hot or cold and cause the risk of scalding  
10.  never exceed the maximum pressure limit (PS) of the water circuit of the unit.  
11.  before removing parts on the pressurised water circuits, close the section of the piping concerned and drain the 

fluid gradually to stabilise the pressure at the atmospheric level 

12.  do not use your hands to check possible refrigerant leaks 
13.  disable the unit from the mains using the main switch before opening the control panel 
14.  check that the unit has been grounded correctly before starting it  
15.  install the machine in a suitable area; in particular, do not install it outdoors if it is intended for use indoors  
16.  do  not  use  cables  with  inadequate  sections  nor  extension  co rd  connections,  even  for  very  short  periods  or 

emergencies 

17.  for  units  with  power  correction  capacitors,  wait  5  minutes  after  removing  the  electric  power  supply  before 

accessing the inside of the switch board 

18.  if the unit is equipped with compressors with integrated inverter, disconnect it from the mains and wait a minimum 

of 20 minutes before accessing it to carry out maintenance: residual energy in the components, which takes at 
least this length of time to dissipate, poses the risk of electrocution 

19.  the  unit  contains  pressurised  refrigerant  gas:  the  pressurised  equipment  must  not  be  touched  except  during 

maintenance, which must be entrusted to qualified and authorised personnel  

20.  connect up the utilities to the unit following the indications set out in this manual and on the panelling of the unit 

itself 

21.  In  order  to  avoid  an  environmental  risk,  make  sure  that  any  leaking  fluid  is  collected  in  suitable  devices  in 

accordance with local regulations. 

22.  if a part needs to be dismantled, make sure it is correctly re-assembled before starting the unit 
23.  when the rules in force  require the installation of fire -fighting systems near the machine,  check that these are 

suitable  for  extinguishing  fires  on  electrical  equipment  and  on  the  lubricating  oil  of  the  compressor  and  the 
refrigerant, as specified on the safety data sheets of these fluids 

24.  when the unit is equipped with devices for venting overpressure (safety valves): when these valves are triggered, 

the refrigerant gas is released at a high temperature and speed; prevent the release of gas from harming people 
or objects and, if necessary, discharge the gas according to the provisions of EN 378-3 and the local regulations 
in force. 

25.  keep all the safety devices in good working order and check them periodically according to the regulations in force 
26.  keep all lubricants in suitably marked containers 
27.  do not store inflammable liquids near the unit 
28.  solder or braze only empty pipes after removing all traces of lubricant oil; do not use flames or other heat sources 

in the vicinity of pipes containing refrigerant fluid 

29.  do not use naked flames near the unit 

Summary of Contents for EWWD-J

Page 1: ...structions REV 03 Date 04 2021 Supersedes D EIMWC01008 16_02EU Installation Operation and Maintenance Manual EWWD EWLD J EWWH EWLH J EWWS EWLS J Installation Operation and Maintenance Manual D EIMWC01...

Page 2: ...GUIDELINES FOR REMOTE CONDENSER APPLICATION EWLD J EWLH and EWLS versions 22 6 1 Installation information for condenserless units 22 6 1 1 Precautions when handling piping 22 6 1 2 Leak test and vacu...

Page 3: ...alve Condenser Shut off valve Filter drier Shut off valve charge valve Solenoid valve Liquid indicator 1 2 3 4 5 6 7 8 Control equipment High Pressure Switch 21 0bar Pressure Transducer Temperature Tr...

Page 4: ...EWLH80J SS 190J SS EWLS110J SS 270J SS Label Identification Figure 2 Description of the labels applied to the electrical panel 1 Unit nameplate data 5 Manufacturer s logo 2 Lifting instructions 6 Eme...

Page 5: ...el 14 check that the unit has been grounded correctly before starting it 15 install the machine in a suitable area in particular do not install it outdoors if it is intended for use indoors 16 do not...

Page 6: ...sfers heat to the water An expansion valve which allows the pressure of condensed liquid refrigerant to be reduced from condensation pressure to evaporation pressure A water cooled evaporator where th...

Page 7: ...9 31 7 70 50 13 18 69 20 69 7 2 26 12 4 43 32 7 92 51 13 51 70 21 16 6 2 34 13 4 58 33 8 15 52 13 85 71 21 64 5 2 43 14 4 73 34 8 39 53 14 20 72 22 13 4 2 53 15 4 88 35 8 63 54 14 55 73 22 62 3 2 62 1...

Page 8: ...a and R513A According to the standard EN 378 1 2016 any refrigerant system that contains R134a or R513A can be installed without any restriction in open air or machinery rooms Anyway the building owne...

Page 9: ...and including the charge and safety classification of the refrigerant used shall be conducted to determine whether it is necessary to place the refrigerating system in a separate refrigeration machine...

Page 10: ...gerants heavier than air and at the highest point for refrigerants lighter than air Detectors shall be continuously monitored for functioning In the case of a detector failure the emergency sequence s...

Page 11: ...ndensing atmosphere may damage electronic components 4 2 Operation The Daikin EWWD J EWLD J EWWH J EWLH J EWWS J EWLS J packaged water cooled water chillers are designed for indoor installation and us...

Page 12: ...D EIMWC01008 16_03EN 12 35 4 2 2 Operation range EWWD J 1 Operation with Glycol below 4 C Evap LWT EWLD J 1 Operation with Glycol below 4 C Evap LWT...

Page 13: ...vap LWT 2 Option111 and operation with Glycol below 4 C Evap LWT 3 Option111 4 Option 111 Option 189 5 Option 189 EWLH J 1 Operation with Glycol below 4 C Evap LWT 2 Option111 and operation with Glyco...

Page 14: ...D EIMWC01008 16_03EN 14 35 EWWS J 1 Operation with Glycol below 4 C Evap LWT EWLS J 1 Operation with Glycol below 4 C Evap LWT...

Page 15: ...re 3 Lifting When handling the unit take into account the following 1 List the unit preferably with a crane and belts in accordance with the instructions on the unit The length of the ropes 1 to be us...

Page 16: ...x the unit on a concrete base with anchor bolts 1 Anchor bolt 2 Washer 3 Rubber plate 4 Row cork or rubber sheet 5 Ground 6 Concrete floor 7 Ditch Figure 4 Unit Levelling Fix anchor bolts into the con...

Page 17: ...antee the cleaning of the water pipes between the water filter and the BPHE Recommended maximum opening for strainer mesh is 0 87 mm DX S T 1 0 mm BPHE 1 2 mm Flooded Precautions for correct use 9 BPH...

Page 18: ...ection pipes prior the operation see figure Connecting the filter The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied Victaulic coup...

Page 19: ...nge as specified in the table below and a minimum water volume is required in the system Model Minimum water flow l min Maximum water flow l min EWWD120J EWLD110J EWWH090J EWLH080J EWWS120J EWLS110J 1...

Page 20: ...anti freeze electrical resistance which provides adequate anti freeze protection at temperatures as low as 18 C However unless the heat exchangers are completely empty and cleaned with anti freeze so...

Page 21: ...gram terminals L1 L2 and L3 5 Supply water to the evaporator and verify if waterflow is within the limits as given in the table under Water charge flow and quality 6 The piping must be completely purg...

Page 22: ...e used For copper to copper joints use a phos copper solder with 6 to 8 silver content A high silver content brazing rod must be used for copper to brass or copper to steel joints Only use oxy acetyle...

Page 23: ...must be between 3 and 8 K c Verify the oil sight glass Level must be within the sight glass d Verify the liquid line sight glass It should be sealed and not indicate moisture in the refrigerant e As l...

Page 24: ...D EIMWC01008 16_03EN 24 35 Figure 5 Condenser located with no elevation difference Figure 6 Condenser located above the unit...

Page 25: ...alves etc Table 2 shows the equivalent length of pipe for various nonferrous valves and fittings Follow these steps when calculating line size 1 Start with an initial approximation of equivalent lengt...

Page 26: ...oling may be affected In these situations insulate the liquid lines Reference for liquid line sizing is shown in Table 3 It has to be used for reference only for circuit working with condensing temper...

Page 27: ...234ze R513A 6 2 4 Oil charge In remote condenser application the oil charge into the compressor has to take into account that a percentage of oil around 1 is usually mixed into the refrigerant so some...

Page 28: ...dards for industrial environments Therefore it is not intended for use in residential areas e g installations where the product is connected to a low voltage public distribution system Should this pro...

Page 29: ...al areas e g installations where the product is connected to a low voltage public distribution system Should this product need to be connected to a low voltage public distribution system specific addi...

Page 30: ...operating manual and the wiring diagram in order to understand start up sequence operation shutdown sequence and operation of all the safety devices During the unit s initial start up phase a technici...

Page 31: ...sure that the work area is properly ventilated before working on the refrigerant circuit or before welding brazing or soldering work ensure that the leak detection equipment being used is non sparking...

Page 32: ...be read on a daily basis thus keeping high observation standards 4 Replace the oil filter when the pressure drop across it reaches 2 0 bar 5 Check for any dissolved metals TAN Total Acid Number 0 10...

Page 33: ...unbalance between phases exceeding 3 The unit must stay turned off until the electrical problem has been solved 4 No safety device either mechanical electrical or electronic must be disabled or overri...

Page 34: ...ed inside the electrical panel Fill in with indelible ink the refrigerant charge label supplied with the product as following instructions Any refrigerant charge for each circuit 1 2 3 added during co...

Page 35: ...e of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe...

Reviews: