background image

EWWD120~540MBYNN

Packaged water-cooled water chillers

4PW22684-1A

Installation manual

8

Defining of the changeable digital/analog inputs and outputs

Besides locked inputs and outputs there are a number of changeable
inputs and outputs of which the function can be chosen from several
possibilities.

Possible functions for changeable digital inputs are:

: no function is appointed to the changeable digital input.

: no function is appointed to the changeable digital input,

but the input status can be read in the “input/output” menu.

 

: to switch between setpoints.

 

: to remotely switch the unit on or off.

 

:  to limit the capacity of the unit to the

entered values.

 

:  to remotely switch the unit between

cooling and heating.

Possible functions for the changeable digital output are:

 

: no function is appointed to the changeable digital

output.

 

: no function is appointed to the changeable digital

output, but the output is closed.

 

:  can be used to steer a cooling/heating

reversing valve.

   

:  can be used to steer a second evaporator

pump.

 

: can be used to steer the condenser pump.

 

: indicates when the unit is working at 100%.

Possible configurations for the changeable analog input are:

: no function is appointed to the changeable analog input.

 

:

 

:

!

:

!

:

This allows the user to define a setpoint in function of an analog input
as mentioned above. Refer to 

"Defining the setpoint signal setting" on

page 8

.

   

: to control the leaving water temperature of

a DICN system.

Defining the setpoint signal setting

The setpoint signal is used to change the setpoint by an external
analog input signal on a stand alone unit or on Slave 1 in a DICN
system.

Example

Setting of the probe offset

It is possible to enter a correction value for certain measured
temperatures (inlet water evaporator temperature and mixed outlet
water evaporator temperature). This in order to correct a possible
measurement fault. The default value of the probe offset, is equal to 0.

Steering the pump manually

There is the possibility to turn the pump on or off manually. This
means that when the unit is off the pump can also be turned on at
any time to check the pump.

Defining the BMS settings

The BMS parameters allowing communication between the unit and
the supervisory system can be modified with the 

 

 and

the 

 

  screen of the service menu. The BMS

parameters are:

 

 screen:

   

:  if set to 

  (yes), the unit can be

commanded and configured from a supervisory system. If set to

  (no), the supervisory system can only read out values but

cannot modify them.

   

: used to address the PCB.

: indicates the communication protocol. If the optional

gateway is used to connect the units to a supervisory system,
the protocol is 

.

 

 screen:

  

: indicates the type of serial connection. The default

is set to 

"#

.

 

: indicates the speed of communication. The default

setting of 

$ %&'

 must be used when the optional gateway

is connected.

Defining the thermostat settings

Defining the thermostat settings for inlet and outlet water temperature
of a, b and c can only be set in the service menu.

H

OW

 

TO

 

CONTINUE

After installation and connection of the packaged water-cooled water
chiller, the complete system should be checked and tested as
described in "Checks before initial start-up" in the operation manual
supplied with the unit.

Fill out the brief operation instructions form and fix it visibly near the
operating site of the refrigeration system.

in setpoints menu

in service menu


Remark

(  

 is only 

available when input 

 (

!

 or 

!

) is selected.

Result

Display in readout menu

A

at 0 V 

 12.0°C

 ) *

B

at 1 V 

 12.0°C + 5.0°C = 17.0°C

 ) +*

,  ) *

   ) *

  ) +*

  ) +*

-.

))  

(  ) #*

B

1 V

A

0 V

To define the thermostat settings of the
inlet and outlet water temperature.

-.  

)" )# )*

 )#*

Summary of Contents for EWWD120MBYNN

Page 1: ...INSTALLATION MANUAL EWWD120MBYNN EWWD180MBYNN EWWD240MBYNN EWWD280MBYNN EWWD360MBYNN EWWD440MBYNN EWWD500MBYNN EWWD520MBYNN EWWD540MBYNN Packaged water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retag...

Page 4: ...10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication Voltage free contacts general operation pumpcontact alarm operation circuit 1 operation circ...

Page 5: ...enerated by the unit does not disturb anyone 5 Ensure that water cannot cause any damage to the location in case it drips out of the unit INSPECTING AND HANDLING THE UNIT At delivery the unit should b...

Page 6: ...d couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWWD120 The water outlet pipe containing the outlet water temperature sen...

Page 7: ...isted in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes o...

Page 8: ...ltage free contacts to indicate the status of the unit These voltage free contacts can be wired as described on the wiring diagram The maximum allowable current is 4 A Remote inputs Besides the voltag...

Page 9: ...s EWWD360 540 Specifications of the cable 6 ray telephone cable with a maximum cable resistance of 0 1 m 2 For units in a DICN configuration the digital controllers of the units can be installed remot...

Page 10: ...ist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEF...

Page 11: ...certain measured temperatures inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe off...

Page 12: ...all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master...

Page 13: ...shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this bu...

Page 14: ...Installation manual 11 EWWD120 540MBYNN Packaged water cooled water chillers 4PW22684 1A NOTES...

Page 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergen...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22684 1A...

Reviews: