D-EIMWC00908-16EN - 40/52
IMPORTANT
The symptoms of a low refrigerant charge, that may be due to refrigerant leak, are:
low evaporation pressure
high suction and discharge superheat
low super-cooling value
Additionally a low level of liquid refrigerant inside the evaporator may be recognized.
In this case, add R134a refrigerant only. The system has been provided with a charge connection between the
expansion valve and the evaporator. Charge refrigerant until working conditions return to normal.
Remember to reposition the valve cover when finished.